Group 22 variation (CNTR change)
0: Var 1
1: Var 2
2: Var 5
3: Var 6
2: Var 5
Selects the variation of the control signal change.
Group 30 variation (AI)
0: Var 1
1: Var 2
2: Var 3
3: Var 4
4: Var 5
4: Var 5
Selects the variation of the analog signal.
Group 32 variation (AI change)
0: Var 1
1: Var 2
2: Var 3
3: Var 4
4: Var 5
5: Var 7
4: Var 5
Selects the variation of the analog signal change.
Setting the analog change deadbands
Table. 6.1.7. - 128. Analog change deadband settings.
Name
Range
Step
Default
Description
General deadband
0.1…10.0 %
0.1 %
2 %
Determines the general data reporting deadband settings.
Active energy deadband
0.1…1000.0
kWh
0.1
kWh
2 kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0
kW
0.1
kW
2 kW
Determines the data reporting deadband settings for this
measurement.
Reactive power deadband 0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0
kVA
0.1
kVA
2 kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00 Hz 0.01
Hz
0.1 Hz
Determines the data reporting deadband settings for this
measurement.
Current deadband
0.01…50.00 A 0.01 A 5 A
Determines the data reporting deadband settings for this
measurement.
Residual
current deadband
0.01…50.00 A 0.01 A 0.2 A
Determines the data reporting deadband settings for this
measurement.
Voltage deadband
0.01…
5000.00 V
0.01 V
200 V
Determines the data reporting deadband settings for this
measurement.
Residual
voltage deadband
0.01…
5000.00 V
0.01 V
200 V
Determines the data reporting deadband settings for this
measurement.
Angle
measurement deadband
0.1…5.0 deg
0.1
deg
1 deg
Determines the data reporting deadband settings for this
measurement.
Integration time
0…10 000 ms
1 ms
-
Displays the integration time of the protocol.
6.1.8. IEC 101/104
The standards IEC 60870-5-101 and IEC 60870-5-104 are closely related. Both are derived from the
IEC 60870-5 standard. On the physical layer the IEC 101 protocol uses serial communication whereas
the IEC 104 protocol uses Ethernet communication. The IEC 101/104 implementation works as a slave
in the unbalanced mode.