Instruction manual – AQ 110 arc protection unit
77 (80
)
12.6
B
INARY
O
UTPUT
BO1
Rated voltage
+24V dc (internally wetted)
Rated current
20mA (max)
Number of outputs
1
12.7
B
INARY
I
NPUTS
BI1,
BI2
Rated voltage
24 or 110 or 220Vdc
Rated current
3 mA
Number of inputs
2
12.8
D
ISTURBANCE TESTS
EMC test
CE approved and tested according to EN
50081-2, EN 50082-2
Emission
- Conducted (EN 55011 class A)
0.15 - 30 MHz
- Emitted (EN 55011 class A)
30 - 1 000 MHz
Immunity
- Static discharge (ESD) (According to
IEC244-22-2 and EN61000-4-2, class III)
Air discharge 15 kV
Contact discharge 8 kV
- Fast transients (EFT) (According to
EN61000-4-4, class III and IEC801-4, level
4)
Power supply input 4kV, 5/50ns
other inputs and outputs 4kV, 5/50ns
- Surge (According to EN61000-4-5
[09/96], level 4)
Between wires 2 kV / 1.2/50µs
Between wire and earth 4 kV / 1.2/50µs
- RF electromagnetic field test (According.
to EN 61000-4-3, class III)
f = 80….1000 MHz 10V /m
- Conducted RF field (According. to EN
61000-4-6, class III)
f = 150 kHz….80 MHz 10V
12.9
V
OLTAGE TESTS
Insulation test voltage acc- to IEC
60255-5
2 kV, 50Hz, 1min
Impulse test voltage acc- to IEC 60255-
5
5 kV, 1.2/50us, 0.5J
12.10
M
ECHANICAL TESTS
Vibration test
2 ... 13.2 Hz ±3.5mm
13.2 ... 100Hz, ±1.0g
Shock/Bump test acc. to IEC 60255-
21-2
20g, 1000 bumps/dir.