EasyBuilder 8000 Software Settings
Launch EasyBuilder 8000 software, select your
project file, press F7 shortcut key to open
the download dialog box:
Select Ethernet > IP tab > Enter your HMI IP
> Click Download to download this project
file to HMI.
( Please refer to EasyBuilder 8000 User Manual
for software operation details )
Communication Connections
COM1
/
COM2 [RS232]
COM1
/
COM3 [RS485]
COM3 [RS232]
DIP SW Settings
Power
The MT6000/8000i can be powered by DC power only, voltage range: 24±20% Volts DC,
compatible with most controller DC systems. The power conditioning circuitry inside the unit is
accomplished by a switching power supply. The peak starting current can be as high as 2A.
Fusing
Require-
ments
If the display does not come on within 5 seconds of power up, remove power. An internal fuse
will prevent damage if the polarity of the DC power is incorrect. Check wiring for proper
connections and try to power up again.
High
Voltage
An Internal fuse will prevent damage for over voltage condition however it isn’t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency
Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using an MT6000/8000i to
comply with ICS Safety Recommendations.
Supply
Voltage
Condition
Do not power the MT6000/8000i and inductive DC loads, or input circuitry to the controller, with
the same power supply. Note: The 24 VDC output from some controllers may not have enough
current to power the MT6000/8000i.
Wire
Routing
a. Wire lengths should be minimized (Max: 500m shielded, 300m unshielded).
b. Wires should be run in pairs with a neutral or common paired with a hot or signal line.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC wiring separate from signal wires.
e. Equip ungrounded DC supplies with a resistor and capacitor in parallel to earth ground.
This provides a path for static and high frequency dissipation. Typical values to use are 1MOhm
and 4700pF.
Hardware
Considerations
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead
to equipment start-up, which could result in property damage and/or physical injury to the
operator.
If you use any programmable control systems that require an operator, be aware that this
potential safety hazard exists and take appropriate precautions. Although the specific design
steps depend on your particular application, the following precautions generally apply to
installation of solid-state programmable control devices, and conform to the guidelines for
installation of Controllers recommended in NEMA ICS 3-304 Control Standards.
Programming
Considerations
To conform with ICS Safety Recommendations, checks should be placed in the controller to
ensure that all writable registers that control critical parts of plant or machinery have limit
checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of
personnel.
6
DANGER
Limited Warranty
This product is limited warranted against defects in design and manufacture. The proven
defective product will either be repaired or replaced, at Weintek’s discretion. This warranty
shall not cover any product which is
(a) Out of warranty period which is 1 year from the date of purchase.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
7
PIN#
Symbol
COM1 [RS232]
COM2 [RS232]
1
Not used
2
RxD
Received Data
3
TxD
Transmitted Data
4
TxD
Transmitted Data
5
GND
Signal Ground
6
RxD
Received Data
7
RTS
Ready to send output
8
CTS
Clear to send input
9
Not used
PIN#
Symbol
Com1
[RS485]2w
Com1
[RS485]4w
Com3
[RS485]
Com3
[RS232]
1
Rx-
Data-
Rx-
2
Rx+
Data+
Rx+
3
Tx-
Tx-
4
Tx+
Tx+
5
GND
Signal Ground
6
Data-
Data-
7
TxD
Transmit
8
RXD
Receive
9
Data+
Data+
SW1
SW2
SW3
SW4
Mode
ON
OFF
OFF
ON
Touch Screen Calibration Mode
OFF
ON
OFF
ON
Hide HMI System Setting Bar
OFF
OFF
ON
ON
Boot Loader Mode
OFF
OFF
OFF
ON
Normal
OFF
OFF
OFF
OFF
Not supported
CAUTION
NOTE:
Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
NOTE:
1. COM1 [RS232] RTS/CTS & COM3 [RS232] can’t be used
simultaneously.
2. COM1 [RS485] / COM3 [RS485] with isolation protection.
8