Archive MT6070 i Series Installation Instruction Download Page 2

 

EasyBuilder 8000 Software Settings 

Launch EasyBuilder 8000 software, select your   
project file, press F7 shortcut key to open 
the download dialog box:   
 
Select Ethernet > IP tab > Enter your HMI IP 
  > Click Download to download this project   
file to HMI. 
 
( Please refer to EasyBuilder 8000 User Manual 
  for software operation details ) 
 

Communication Connections 

 

COM1 

COM2 [RS232] 

 

 

 

 

 

 

 

COM1

 / 

COM3 [RS485] 

COM3 [RS232]

 

 

 

 

 

 

 

 

DIP SW Settings 

 

 

 

 

Power 

The MT6000/8000i can be powered by DC power only, voltage range: 24±20% Volts DC, 
compatible with most controller DC systems. The power conditioning circuitry inside the unit is 
accomplished by a switching power supply. The peak starting current can be as high as 2A.

 

Fusing 
Require- 
ments 

If the display does not come on within 5 seconds of power up, remove power. An internal fuse 
will prevent damage if the polarity of the DC power is incorrect. Check wiring for proper 
connections and try to power up again. 

High 
Voltage 

An Internal fuse will prevent damage for over voltage condition however it isn’t guaranteed. DC 
voltage sources should provide proper isolation from main AC power and similar hazards. 

Emergency 
Stop 

A Hard-wired EMERGENCY STOP should be fitted in any system using an MT6000/8000i to 

comply with ICS Safety Recommendations. 

Supply 
Voltage 
Condition 

Do not power the MT6000/8000i and inductive DC loads, or input circuitry to the controller, with 
the same power supply. Note: The 24 VDC output from some controllers may not have enough 
current to power the MT6000/8000i. 

Wire 
Routing 

a. Wire lengths should be minimized (Max: 500m shielded, 300m unshielded). 
b. Wires should be run in pairs with a neutral or common paired with a hot or signal line. 
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices. 
d. Keep AC, high energy, and rapidly switching DC wiring separate from signal wires. 
e. Equip ungrounded DC supplies with a resistor and capacitor in parallel to earth ground. 

This provides a path for static and high frequency dissipation. Typical values to use are 1MOhm 
and 4700pF. 

 

Hardware 
Considerations

The system designer should be aware that devices in Controller systems could fail and thereby 
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead 
to equipment start-up, which could result in property damage and/or physical injury to the 
operator. 
If you use any programmable control systems that require an operator, be aware that this 
potential safety hazard exists and take appropriate precautions. Although the specific design 
steps depend on your particular application, the following precautions generally apply to 
installation of solid-state programmable control devices, and conform to the guidelines for 
installation of Controllers recommended in NEMA ICS 3-304 Control Standards.

 

Programming 
Considerations
 

To conform with ICS Safety Recommendations, checks should be placed in the controller to 
ensure that all writable registers that control critical parts of plant or machinery have limit 
checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of 
personnel. 
 

 

 

DANGER

Limited Warranty                                                                                                        

 

This product is limited warranted against defects in design and manufacture. The proven 

defective product will either be repaired or replaced, at Weintek’s discretion. This warranty 

shall not cover any product which is   

 

(a) Out of warranty period which is 1 year from the date of purchase. 
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.   
(c) Product has been repaired or taken apart by unauthorized technicians.   
(d) Products whose identification markings have been removed or damaged.

 

PIN#

Symbol 

COM1 [RS232] 

COM2 [RS232] 

Not used 

 

 

RxD 

Received Data 

 

TxD 

Transmitted Data 

 

TxD 

 

Transmitted Data 

GND 

Signal Ground 

RxD 

 

Received Data 

RTS 

Ready to send output 

 

CTS 

Clear to send input 

 

Not used 

 

 

PIN#

Symbol 

Com1 
[RS485]2w

Com1 
[RS485]4w

Com3 
[RS485] 

Com3 
[RS232] 

Rx- 

Data- 

Rx- 

 

 

Rx+ 

Data+ 

Rx+ 

 

 

Tx- 

 

Tx- 

 

 

Tx+ 

 

Tx+ 

 

 

GND 

Signal Ground 

Data- 

 

 

Data- 

 

TxD 

 

 

 

Transmit 

RXD 

 

 

 

Receive 

Data+ 

 

 

Data+ 

 

SW1 

SW2 

SW3 

SW4

Mode 

ON 

OFF 

OFF 

ON

 

Touch Screen Calibration Mode 

OFF

ON 

OFF 

ON

 

Hide HMI System Setting Bar 

OFF

OFF 

ON 

ON

 

Boot Loader Mode 

OFF

OFF 

OFF 

ON 

Normal 

OFF

OFF 

OFF 

OFF

Not supported 

CAUTION

NOTE: 

Make sure that all local and national electrical standards are met when 

installing the unit. Contact your local authorities to determine which codes apply. 

NOTE:  

1. COM1 [RS232] RTS/CTS & COM3 [RS232] can’t be used 

simultaneously. 

2. COM1 [RS485] / COM3 [RS485] with isolation protection.

GME680700_MT6/8070iH2/iH3_MT6/8100iV2_Installation_120509