Archgard 25-BVI20N-2 User'S Installation, Operation And Maintenance Manual Download Page 2

5.08: 

Modifications to NFPA-54, Chapter 10

 

 (2) Revise 10.8.3 by adding the following additional requirements: 
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part 
for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is 
less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following 
requirements shall be satisfied:  
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled 
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-
up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe 
that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, build-
ing or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to 
secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors 
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon 
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. 
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a 
period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery 
operated carbon monoxide detector with an alarm shall be installed. 
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provi-
sions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.  
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of 
eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or 
equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, 

"GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS". 

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the instal-
lation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions 
of 248 CMR 5.08(2)(a)1 through 4.  
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as 
adopted by the Board; and  
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, 
building or structure used in whole or in part for residential purposes.  
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Prod-
uct Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the 
equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 
1. Detailed instructions for the installation of the venting system design or the venting system components; and 
2. A complete parts list for the venting system design or venting system.  
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a 
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies 
"special venting systems", the following requirements shall be satisfied by the manufacturer: 
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and  
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list 
and detailed installation instructions.  
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting in-
structions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at 
the completion of the installation.  

 

                                           

STATE OF MASSACHUSETTS  REQUIREMENTS 

 

For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter li-

censed in the Commonwealth of Massachusetts. 

 

For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length. 

 

The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance 

with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is 

installed. 

 

For the State of Massachusetts the appliances individual shut 

 off must be a t-handle type valve. 

f i r e - p a r t s . c o m

Summary of Contents for 25-BVI20N-2

Page 1: ...er from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Do not use this appliance if any part has been under water Immediately...

Page 2: ...of the side wall horizontally vented gas fueled equipment shall not approve the instal lation unless upon inspection the inspector observes carbon monoxide detectors and signage installed in accordan...

Page 3: ...means less expensive to operate Adjustable Heat The flame aesthetics and heat output can be adjusted to suit the owner s moods and heating needs Solid Construction Constructed mainly of 16 and 18 gau...

Page 4: ...Placement 15 Operation Instructions 20 Maintenance 22 Troubleshooting Instructions 23 Servicing 25 APPENDIX A Installation Into Vented Gas Fireplaces 28 Suitable Host Fireplaces Specific Installation...

Page 5: ...rpeting bedding material etc It is imperative that the control compartments burners and circulating air passageways for the appliance be kept clean CAUTION FOR YOUR SAFETY Do not install or operate yo...

Page 6: ...on in a bedroom or a bedsitting room and conforms to CR89 001 We recommend that our gas hearth products be installed and serviced by professionals who are certified in the U S by the National Fireplac...

Page 7: ...LASS DOOR REMOVABLE CONTROL COVER SURROUND FRONT VIEW SPARKER APPLIANCE DIMENSIONS A B I K J A 30 768 mm B 23 584 mm C 15 387 mm D 11 286 mm E 4 102 mm F 19 489 mm G 5 127 mm H 5 146 mm I 24 616 mm J...

Page 8: ...y built wood burning and specific zero clearance vented gas fireplaces Due to constant additions contact Archgard Industries for an updated list of suitable gas fireplaces This appliance cannot be enc...

Page 9: ...l fit if X is more than 5 It will also fit if X is less than 5 but Y is higher than 8 See Flue connector offset vent diagram 19 495 mm SIDE VIEW X Y Z Flue connector straight up vent Flue connector of...

Page 10: ...ght up vent Flue connector offset vent MINIMUM ZERO CLEARANCE WOOD BURNING FIREPLACE DIMENSIONS 17 432 mm 25 635 mm 12 305 mm TOP VIEW 15 387 mm X Y Z SIDE VIEW The standard flue adapter will fit if X...

Page 11: ...d to a chimney flue serving a separate solid fuel burning appliance The appliance may be vented using 4 in diameter aluminum or stainless steel flexible gas liner running inside a masonry chimney or t...

Page 12: ...t tip screw driver and placing a test gauge on the tap The minimum permissible gas supply pressure is 4 5 in w c 1 2 kPa for natural gas and 11 0 in w c 2 8 kPa for propane Maximum gas supply pressure...

Page 13: ...e bracket that best suit your application INSTALLATION INSTRUCTIONS Continued 1 2 3 The spill switch is manual reset type that can be reset by pressing the pin between the two wire terminals with a sm...

Page 14: ...off the appliance Remove the control cover by sliding it off the bottom door assembly There is a buckle latch located in the bottom centre lift the lever on the back of the latch to release it Unhook...

Page 15: ...amount and type supplied with the unit LOG PLACEMENT WARNING Do not place the logs or branches in any configuration other than the one shown A fire explosion or excessive carbon monoxide CO may result...

Page 16: ...g locator pins and pre drilled holes in log Log will sit as shown in the photo below STEP 2 Locate log 2 and place onto the left side of the burner using locator pins and pre drilled holes in log Log...

Page 17: ...the locator pins and pre drilled holes in log Log should sit as shown in photo below STEP 4 Locate log 4 and place onto right side of burner using the locator pins and pre drilled holes in log Log sh...

Page 18: ...or pins and pre drilled holes in log Log should sit as shown in photo below STEP 6 Locate log 6 and place onto rear log using the locator pins and pre drilled holes in log Log should sit behind right...

Page 19: ...nto rear log using the locator pins and pre drilled holes in log Log should sit behind left grate tine as shown in photo below FINAL LOG PLACEMENT Please note that all logs should be placed exactly as...

Page 20: ...fire or explosion BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gases are heavier than air and will settle on the floor IF YOU SMELL GAS f...

Page 21: ...pilot Press slightly and turn control knob counterclockwise to PILOT position depress control knob and light pilot by repeatedly pressing the sparker Venting of air may take place at the pilot prior t...

Page 22: ...ic glass cleaner and a non abrasive cloth available from your local dealer Carefully remove the logs and if present gently brush off any loose carbon deposits This job is best done outside the house w...

Page 23: ...locked or the gas valve may be defective 5 Check wiring and connections to spill switch Pilot will not remain on after being lit 1 Press the control knob all the way in 2 Hold the control knob in for...

Page 24: ...rect ohms reading Replace if required 7 Check for proper drafting of the appliance Correct if drafting is occurring into the room 8 Spill switch has tripped Reset by hand when appliance has cooled Soo...

Page 25: ...ate air shutter by hand The primary air opening size can be easily seen Tighten the air shutter set screw after adjustment CAUTION Adjust the primary air shutter only when the appliance is cool to the...

Page 26: ...the firebox Disconnect the spade connectors to the fan Carefully remove the fan Reverse the above instructions to install the new fan SPEED CONTROL LINE CONVECTION FAN GROUND 110 F 43 C N O THERMAL SN...

Page 27: ...y loosening and removing the two mounting screws located next to the two back log locating tabs Shut of the gas to the appliance and disconnect the gas line to the appliance If the appliance has a rem...

Page 28: ...ed list of gas fireplaces and any additional installation instructions The host gas fireplace s certification will be nullified and will no longer be usable for its original purpose A warning plate pr...

Page 29: ...e or trim any baffles inside the firebox that may be obstructing the direct passage to the flue connector Remove or trim any decorative facing or baffles inside the firebox that may interfere with the...

Page 30: ...it is being inserted into the host fireplace Level the EURO 25 as described in manual Complete the installation of the surround and accessories as described in the manual Check for proper venting of t...

Page 31: ...al injury or loss of life SAMPLE MODIFICATION WARNING PLATE 303 0050 WARNING This fireplace has been modified for use with the Archgard EURO 25 gas insert Usage without the EURO 25 gas insert may caus...

Page 32: ...e host gas fireplace is complete See Appendix A of the Euro 25 manual for further instructions All installation requirements in the manual must also be carefully observed and followed 7 Use Archgard 2...

Page 33: ...Euro 25 manual for further instructions All installation requirements in the manual must also be carefully observed and followed 6 Use Archgard 25 ICKIT5 connector kit to connect the insert to the hos...

Page 34: ...carefully observed and followed 8 Use Archgard 25 ICKIT5 connector kit to connect the insert to the host s B vent or connect a 4 diameter flexible aluminum gas vent from the insert to the host s vent...

Page 35: ...lete See Appendix A of the Euro 25 manual for further instructions All installation requirements in the manual must also be carefully observed and followed 8 Use Archgard 25 ICKIT5 connector kit to co...

Page 36: ...25 ICKIT5 connector kit to connect the insert to the host s B vent or connect a 4 diameter flexible aluminum gas vent from the insert to the host s vent cap Optional custom surround is available for t...

Page 37: ...DRESS PHONE NUMBER COMPANY NAME ADDRESS PHONE NUMBER APPLIANCE MODEL NUMBER 25 BVI20N 2 SERIAL NUMBER GAS TYPE NATURAL GAS LPG VALVE TYPE Robertshaw 7000MVRB DATE PURCHASED INSTALLATION INSTALLER NAME...

Page 38: ...help please have the following information Model of your Fireplace Serial Number Place of Purchase Date of Purchase Problem Description NOTE Warranty may be void if work is carried out by an unqualifi...

Page 39: ...AL RESET 1 EA 305 0027 SWITCH BLANK ON OFF CARLING 9711 1 EA 307 0020 GLASS CERAMIC 12 500 x 15 719 BAY CENTER 1 EA 307 0055 GLASS CERAMIC 12 500 x 4 BAY SIDE 2 EA 308 0005 PIEZO IGNITOR c w NUT JBS 6...

Page 40: ...25 BVI20N 2 40 NOTES fire parts com...

Page 41: ...State Prov ZIP Phone _____ Dealer s Name Address City State Prov ZIP Phone _____ Installer s Name Address City State Prov ZIP Phone _____ Why did you choose this product Thank you for purchasing our p...

Page 42: ...fire parts com...

Page 43: ...Archgard Industries Ltd 7116 Beatty Drive Mission B C V2V 6B4 Canada Website www archgard com fire parts com...

Reviews: