15
English
INSTALLATION (OPERATION
CARRIED OUT EXCLUSIVELY BY
QUALIFIED PERSONNEL)
Attention! Installation of the appliance for res-
idential ventilation must only be carried out by
qualified personnel to avoid damage or injury.
Attention! To protect the system against
filth and humidity, all the openings must
remain closed until commissioning, for
example using protective covers.
INSTALLATION INSTRUCTIONS
• The residential ventilation appliance can be
installed in dry environments with the temperature
above 12°C, for example in a utility room.
Installation temperature: from +12 °C to +40 °C.
• Relative humidity (installation environment): max.
60%.
• Storage temperature: -20 ° C to +60 ° C.
PLEASE NOTE:
if the temperature in the installation room
drops below 12°C, there could occasionally be condensate
on the external covering of the appliance.
• Position the appliance so that the section up to the
external outlet of the outdoor air and exhaust air
inlet ducts is as short as possible.
• The vibrations produced by the residential venti-
lation appliance must be dampened. The installed
appliance must be soundproofed.
• The residential ventilation appliance is mounted
with a wall bracket (supplied with the machine).
• The appliance can be mounted on the floor using
optional stands.
• The appliance must be accessible to perform
maintenance and repairs.
• Air flow rates must be set correctly in com-
pliance with standard DIN 1946, part 6.
• The appliance can be commissioned after having
completed installation of the entire residential
ventilation system.
WALL INSTALLATION OF APPLIANCE
525
H MIN
MIN 200
485
242,5
50
50
50 50
B
A
20
R5
5
B
OK
262,5
C
- Fastening the bracket to the wall
Take the bracket and apply it to the wall, making sure that it is
attached in a horizontal position using a spirit level, as described
in the figure below (
Fig. 1
).
1 - Position the bracket and drill the necessary holes
(Fig.1).
Make sure the appliance is horizontal.
2 - Secure the bracket by applying the screws.
PLEASE NOTE:
the screws are not included in the supply.
Choose the screws and relative plugs based on the type
of wall.
(Fig. 1)
Model
H MIN
(mm)
A
(mm)
B
(mm)
C
(mm)
ENY-S-170
ENY-SEL-170
ENY-SER-170
1190
600
11
1000
ENY-S-270
ENY-SEL-270
ENY-SER-270
1190
600
11
1000
ENY-S-360
ENY-SEL-360
ENY-SER-360
1190
600
11
1000
ENY-S-460
ENY-SEL-460
ENY-SER-460
1130
660
67.5
940
ENY-SP-180*
ENY-SPEL-180
ENY-SPER-180
1190
600
37.5
1000
ENY-SP-280*
ENY-SPEL-280
ENY-SPER-280
1190
600
37.5
1000
ENY-SP-370*
ENY-SPEL-370
ENY-SPER-370
1130
660
67.5
940
ENY-SP-460*
ENY-SPEL-460
ENY-SPER-460
1130
660
67.5
940
* Dimensions are also valid for enthalpy models