Note
: The 933A records complete sets of one-second data around the
occurrence of the event, depending on the set Logging Times. The 933A
stores the main data records in the standard flash module, and stores high-
speed waveform in another 128 MB flash module used exclusively for that
purpose.
Viewing One–Second Log Data
1. Press REVIEW
>
SHOW LOG (soft key) to view a complete list of
one-second log data. See Figure 7.13.
2. Press the REVIEW SELECTIONS soft key to separate all of the one-
second log data into groups, and press the SHOW EVENT LOGS
soft key
3. Look through the one-second data to find the time of occurrence of
the event and press any of the number keys to select a data point.
Figure 7.13: Captured
One–Second Record
4. Press any of the number keys to select the data type for viewing (e.g.
0-Tabular Results).
5. Press any of the soft key selections to choose to view any configured
phase, or to view Min/Max information.
Erasing Captured Waveform Data
To erase any records stored in flash, press the REVIEW key, followed by
the ERASE LOG soft key. You will be asked if you really want to erase
all of the stored data in the flash memory modules. Select either the NO
or YES soft key to proceed.
No partial data erasures are possible
.
114