128
Options List
B.8.4
Output Load and Loop Example: Unmodulated IRIG-B
When designing circuits for connection to the output bus, several factors must be considered.
1. Loop Resistance
2. Type and quantity of loads connected
3. Maximum loop distance desired
Table B.3 provides a matrix of these factors using the Schweitzer relay(s) as the output load(s). The loop
distance figures were obtained using the following types of Belden Wire (cross-referenced to corresponding
part number):
AWG20
AWG18
AWG16
AWG14
AWG12
Shielded
8762
8760
8719
8720
8718
Non-Shielded
8205
8461
8471
8473
8477
Total Loop
Output Load and Voltage Drop – SEL Relays(1)
Loop Length (ft.)
Resistance
at 0.25 V drop
at 0.5 V drop
I(mA)
#SEL-2xx(2)
I(mA)
#SEL-3xx
AWG20
AWG18
AWG16
AWG14
AWG12
10 Ω
25
2
50
5
500
800
1200
2000
3000
5 Ω
50
5
100
10
250
400
600
1000
1500
2.5 Ω
100
10
200
20
125
200
300
500
750
1 Ω
250
25
500(3)
50
50
80
120
200
300
Table B.3: Example, Output Load and Loop Distance Matrix
1. Output Load and Voltage Drop, # SEL-3xx is the number of relays connected as output load.
2. For SEL-2xx, using pairs of relays with inputs of each pair in series, the maximum number of relays
is two times that for SEL-3xx.
3. Using 2 drivers in parallel. Parallel connection may be made using AWG22 wire.