C.8 Option 10: Inlet Power Supply Description
107
C.8
Option 10: Inlet Power Supply Description
C.8.1
110 to 350 VDC, 85 to 250 VAC, 47 to 440 Hz Terminal Power Strip,
SWC
Option 10 replaces the standard IEC-320 power input module with a three-position, screw-type
terminal block, including Surge Withstand Capability (SWC). This feature is intended for use
in installations where it is necessary or desirable to have the instrument power hard-wired. See
Figure C.6.
Figure C.6: Option 10 Power Supply Inlet
Description
C.8.2
Specifications
Input Power:
AC Voltage Range:
85 to 250 VAC
Frequency Range:
47 to 440 Hz
DC Voltage Range:
110 to 350 VDC
Input Power:
<
20 Watts
Terminal Block:
Terminal Assignment:*
Ground, (
−
), (+), left to right, viewed from rear
Block Size:
15 mm W x 18 mm H x 30 mm D. (5/8” x 0.75” x 1 3/16”)
Approvals:
U. L. recognized; C.S.A. approved
*For AC operation, input line may be connected between (+) and (
−
), without
regard to polarity; however proper grounding should always be employed
Fuse:
Type:
Bussman GDC-1A
Current Rating:
1 Ampere, fast-acting
Voltage Rating:
250 Volts
Size:
5 mm x 20 mm
Surge Withstand Protection (SWC)
Provides input Surge Withstand Capability (SWC) in compliance with both ANSI C37.90 and IEC
801-4.
Connections
All input power line connections to the rear-panel terminal strip should be made using appropriate
power cables which have the insulation removed about 1/4” from the end or as required for tinning.
If a DC source is used, connect the positive lead to the positive (+) terminal, connect the negative
lead to the negative (
−
) terminal and a safety ground lead to the “G” terminal when viewing the
instrument from the rear (see Figure C.6).
Summary of Contents for 1092A
Page 4: ...iv ...
Page 18: ...xviii LIST OF TABLES ...
Page 129: ...C 10 Option 20A Four Fiber Optic Outputs 111 Figure C 7 Option 20A Jumper Locations ...
Page 131: ...C 11 Option 27 8 Channel High Drive 113 Figure C 8 Option 27 Jumper Locations ...
Page 148: ...130 Options List Figure C 10 Option 29 Connector Signal Locations ...