ARAMA DCIPT12 Installation Instructions & Owner'S Manual Download Page 13

- 12-

 

 

 

 

2.  Pull the filter straight up and remove. 

3.  Clean filter with vacuum or with running water. 

Reverse this procedure to reinstall the filter

 

Filter is removed by grasping 

the filter

'

s top and gently

 

pulling up

 

 

 

Front  removal  is  not 
necessary  to

 

remove  the  filter

 

 
 

 
 
 
 

 
 
 

Vent Screen

 

Before cleaning the vent screen, disconnect power to the 
unit  by  unplugging  the  power  cord  at  the  wall  outlet  or 
subbase,  or  disconnect  power  at  the  fuse  box  or  circuit 
breaker. If unit is operated with vent door closed, the vent 
screen does not need 

to be cleaned. 

1.   Remove   the   cabinet   front   as   described   in   Front 
Removal. 

2.  Remove the six screws securing the chassis to the wall 
sleeve. 

3.   Slide the chassis out of the wall sleeve far enough so 
that the vent screen is accessible. 

4.  Clean the vent screen

slide the chassis back into the 

wall sleeve, secure it in place with six screws and reinstall 
the front cabinet. 

Cabinet Front

 

The cabinet front and discharge air  grille can be cleaned 
with  a  water  dampened  cloth.   Under  no  circumstances 
should  hydrocarbon-based  cleaners    (e.g.  acetone, 
benzene,  naphtha  gasoline,  etc.)  or  ammonia  based 
cleaners be used to clean the front or air grilles. Use care 
when cleaning the control area. 

 

 

Y E A R L Y    M A I N T E N A N C E    A N D 
CLEANING

 

NOTE:     

Use  a  mild  biodegradable  detergent  when 

cleaning the unit.  Special care must be taken to protect the 
unit's control board and other electrical components from 
getting any water on them while cleaning. The use of harsh 
or caustic cleaning agents or materials such as  bleach or 
coil cleaners that are not designed for PTAC products will 
cause damage or deterioration of  the aluminum fin or coil 
material and is not recommended. Care must be taken not 
to bend the aluminum fin stock. 

Routine scheduled Maintenance

 

To achieve continuing top performance and high efficiency, 
establish a 

“once a year" cleaning/inspection schedule for 

the  unit.  Take  the  unit  out  of  the  sleeve  and  thoroughly 
clean and rinse.   Be sure to include in the yearly cleaning 
the  evaporator  coil,  and  condenser  coil,  basepan,  and 
drain passages. 

Scheduled  maintenance  can  be  accomplished  by  either 
qualified  local  maintenance  staff  or  by  an  authorized 
servicer. They must follow the instructions described in this 
manual. 

Adverse Operating Conditions Maintenance

 

Units  operating  in  dusty  or  corrosive  locations;  i.e. 
dusty construction site or sea coast, must   be cleaned 
more  often.   A  minimum  of  four  (4)  times  a  year  will 
maintain proper operational conditions and protect unit 
components. 

Wall sleeve

 

Clean  the  wall  sleeve  while  cleaning  the  unit.    The 
caulking around the sleeve should be checked to make 
sure  that  any  potential  air  and  water  openings  around 
the sleeve are properly sealed.  The wall sleeve's level 
should  also  be  rechecked.    Proper  leveling  for  most 
installations  are  a  1

/

4  bubble  tilt  to  the  outside  and 

level  from  right  to  left.   Contact  your  sales  person  for 
detailed maintenance or cleaning instructions. 

 

 

CAUTION!

 

DO NOT USE COMMERCIAL GRADE COIL CLEANERS. SOME 
OF  THESE  CLEANERS  MAY  CONTAIN  ETHYLENE  DIAMINE 
TETRACETIC  ACID  (EDTA)  WHICH  CAN  SHORTEN  THE  LIFE 
OF THE CONDENSER COIL

 

 

Base pan and Condenser coil

 

Before  cleaning  the  base  pan  and  condenser  coil,  turn 
OFF unit mode switch and disconnect power to the unit. 

To disconnect power, either unplug the power cord at the 

wall outlet or subbase, or disconnect power at the fuse box 
or circuit breaker 

1. Create a water tight seal by tightly covering the entire 
control panel area and fan motor with plastic. Creating this 
seal prevents water from entering the control area or the 
fan motor and damaging the unit. 

2.  Spray  condenser  coil  and  base  pan  down  with  water. 
Next  spray  a  mild  biodegradable  detergent  onto  the 
condenser coil and base pan.  Let set for five (5) minutes. 

3.  Rinse condenser coil and base pan with water again

NOTE: 

Ensure water pressure is no higher than that of an 

ordinary garden hose and the water temperature no higher 

than 120

Summary of Contents for DCIPT12

Page 1: ...s Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of specific good sa...

Page 2: ...n death the socket or terminal blocks for p o w e r s u p p l y t o t h e a i r conditioner include 277V and 115V and 208 230V series and the units that have LCDI power cord must connect a Ground Fault Circuit Interrupter 4 D u r i n g i n s t a l l a t i o n t h e w i r e connection must strictly follow the rule which is zero line and fire line of unit should be connected to the zero line and fir...

Page 3: ...which operational mode is active FAN ON OFF System safety protections To ensure the system running safely electric control has the following protections for problem solving please refer to d i a g n o s t i c c o d e s s o l u t i o n s a n d troubleshooting sections A Outdoor unit overload protection in COOLING mode When condenser coil temperature exceeds the presetting point compressor decreases...

Page 4: ...icated All units have two fan motors for quiet operation and maximum operating efficiency Motors are permanently lubricated to reduce maintenance and totally enclosed to keep dirt and water out of the motor windings Indoor Fan Speed Selections LOW HIGH Unit may be operated in low fan speed or high fan speed Some speed may not be present based on unit capacities LS Control front desk control The un...

Page 5: ...ule Indoor Fan Electric heater Front and discharge grille Outdoor coil Inverter compressor Electronic control module assembly Power cord coverplate not show Control box Indoor coil WALL SLEEVE ASSEMBLY OPTIONAL ACCESSORY Two kinds of wall sleeve are optional for customers one is reassemble wall sleeve and the other one is welding integrated wall sleeve Removable Wall Sleeve The removable wall slee...

Page 6: ...ficient space margins around the unit to facilitate maintenance and repairs refer to Figs 3 and 4 Chart 2 SUB FLOOR Fig 5 Note Do not remove the stiffener support from inside the wall case until the chassis is to be installed NOTE NO 1 means using field supplied sleeve angles 16 18 24 NO 2 means not using field supplied sleeve angles 1 2 Fig 3 In order for condensate water to drain properly inside...

Page 7: ... set and require no adjustment 2 Check the indoor and outdoor grilles for obstructions to air flow The unit must be located where curtains furniture trees or other objects do not block the air flow to and from the unit If air is obstructed and or deflected back into the unit the air conditioner compressor may cycle on and off rapidly This could damage the compressor or possibly void the warranty A...

Page 8: ...Receptacles Sub bases WARNING TO AVOID THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE USE ONLY COPPER CONDUCTORS WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT USE AN EXTENSION CORD WITH THIS UNIT WARNING TO AVOID THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE DO NOT INSTALL WITH POWER CORD STRETCHED OR UNDER A STRAIN AS THIS MAY CREATE LOOSE PLU...

Page 9: ...mounted control panel Operation mode indicator Fan speed indicator Present time indicator TEMP indicator Indicate set temperature Keyboard locked indicator Timer time indicator TEMP setting button This button is used to sent the room temperature Pressing of or button the temperature setting is increased or decreased FAN SPEED button Press this button to select the high low autospeed of air deliver...

Page 10: ...nd then close the back cover NOTE For some type this function may be not exist SENIOR OPERATION Under OFF mode hold COOL and FAN SPEED two keys at the same time continuously for 5 seconds This time display d0 indicates that system has entered the senior operation status COOL key is used to switch parameter code and parameter value or keys are used to switch parameter code or set parameter value ON...

Page 11: ...pped If this switch is put to OFF position it will be no freeze protection 6 Electric memory Default setting is ON Fig 13 Shipping Screw Location If the unit is cut out of power during the operation when it is powered up again all last settings will be remembered and the operation will follow the last mode Manual turn on the unit operation mode will be the last settings If this switch is put to OF...

Page 12: ...ONALINJURYOR DEATH 15 Discharge Air 55 Discharge Air M O N T H LY M AI N T E N AN C E AN D CLEANING IntakeAir Filters To properly maintain the operational performance of your PTAC unit it is extremely important that the inlet air filters be cleaned once per month or more often if operated in dusty or dirty locations or conditions The intake air filters are constructed of durable polypropylene The ...

Page 13: ...ction schedule for the unit Take the unit out of the sleeve and thoroughly clean and rinse Be sure to include in the yearly cleaning the evaporator coil and condenser coil basepan and drain passages Scheduled maintenance can be accomplished by either qualified local maintenance staff or by an authorized servicer They must follow the instructions described in this manual Adverse Operating Condition...

Page 14: ...er objects for proper operation Restricted discharge or intake air will reduce the unit s operational performance In severe airflow restrictions damage can occur to unit components such as the compressor electric heater or fan motor NORMAL OPERATING SOUNDS AND CONDITIONS Water trickling sounds Water is picked up and distributed over the coil This improves the efficiency and helps with water remova...

Page 15: ... sensor is broken replace it E9 Compressor discharge temperature fault Check the sensor s plug is firmly connected If the sensor is broken replace it EC DC compressor starting failure or compressor driving fault Check the DIPswitches on the main board 3 position in red color is correct it must matches the wiring diagram Make sure the compressor power wires is firmly connected EH Indoor EEPROM faul...

Page 16: ...minutes on starting the compressor after a power outage or restarting after it has been turned off to prevent tripping of the compressor overload Make sure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher temperature setting Remove and clean filters Allow sufficient amount of time for unit to heat or cool the room Start heating or cooling ea...

Reviews: