33
AQ-OP-00010_E
B.3.5 Absorption Voltage vs. Charge Current, 30°C
Minimum
Charge
Current (A)
Absorption Voltage
Schneider
Outback
MidNite
SMA
Morningstar
0
54.4
2.26
13.60
12
55.4
2.31
13.85
24
56.4
2.35
14.10
36
57.4
2.39
14.35
48
58.4
2.43
14.60
60
59.4
2.48
14.85
72
60.4
2.52
15.10
84
61.4
2.56
15.35
96
62.4
2.60
15.60
108
63.4
2.64
15.85
120
64.4
2.68
16.00
132
65.4
2.73
16.00
144
66.4
2.77
16.00
B.4 Reference Cycles for Lab Use
It is common to perform reference cycles to verify the capacity of the battery in a lab environment. Due
to the unique characteristics of the Aquion Battery, it is important to use a standard test plan in order to
ensure the results can be compared to the manufacturer specifications. Please use the following
parameters when performing reference cycles:
Step
Mode
Value
End Type
1
Constant Current Charge
24 A
60.8 V
2
Constant Voltage Charge
60.8 V
12 A
3
Constant Current Discharge
24 A
30.4 V
4
Rest
0 A
2 hours