20
AT-MGS-402 User Manual
Read
Write
Register
Address
Func Code 04
(read input registers)
Item Group
Notes
R
X
30003
Sensor 1 Modbus error code
Sensor 1
Exception code from Modbus standard
R
X
30004
Sensor 1 concentration
Sensor 1
0-65535
R
X
30005
Sensor 1 status code
Sensor 1
0 = Offline
1 = Warm-up
2 = Online
R
X
30006
Sensor 1 Fault code
(high byte)
Sensor 1
Sensor specific
R
X
30007
Sensor 1 sensor fault code
Sensor 1
Sensor specific
R
X
30008
Sensor 1
°
C
Sensor 1
Sensor specific
R
X
30009
Sensor 1 Cal expired flag
Sensor 1
0 = Cal Valid
1 = Cal expired
R
X
30010
Sensor 1 Low alarm flag
Sensor 1
0 = No Alarm
1 = Alarm
R
X
30011
Sensor 1 High alarm flag
Sensor 1
0 = No alarm
1 = Alarm
R
X
30012
Sensor 1 Saturation flag
Sensor 1
0 = Unsaturated
1 = Saturated
R
X
30013
Sensor 1 Underflow flag
Sensor 1
0 = Normal
1 = Underflow
R
X
30014
Sensor 1 Instrument
Type code
Sensor 1
1 = MGS400
R
W
30015
Sensor 1 Node Address
Sensor 1
1-254
R
X
30016
Sensor 1 Sensor Type code
Sensor 1
Sensor specific
R
X
30017
Sensor 1 Concentration Units
Sensor 1
1 = ppm
2 = ppb
3 = %VOL
4 = %LEL
R
X
30018
Sensor 1 Scale Factor
Sensor 1
Power of 10 used on concentration,
divide conc by 10^x for
R
X
30019
Sensor 1 Gas Type Text Char 1,2 Sensor 1
ASCII characters
R
X
30020
Sensor 1 Gas Type Text Char 3,4 Sensor 1
ASCII characters
R
X
30021
Sensor 1 Gas Type Text Char 5,6 Sensor 1
ASCII characters
R
X
30022
Sensor 1 Gas Type Text Char 7,8 Sensor 1
ASCII characters
R
X
30023
Sensor 1 Gas Type Text Char
9,10
Sensor 1
ASCII characters
R
X
30024
Sensor 1 SID Text Char 1,2
Sensor 1
ASCII characters
R
X
30025
Sensor 1 SID Text Char 3,4
Sensor 1
ASCII characters
R
X
30026
Sensor 1 SID Text Char 5,6
Sensor 1
ASCII characters