aquilar AquiTron AT-G-DETECT Testing And Calibration Procedure Download Page 2

*Technician use only 

– This procedure 

must be carried 

out by a suitably 

qualifi ed technician in 

accordance with these 

instructions and the 

standards set down 

in their particular 

industry/country.

AT-G-DETECT

Gas Sensing System
Check / Calibration Procedure

A. INTRODUCTION

The frequency and nature of testing or calibration may be determined by local regulation or 
standards.EN378 and the FGAS Regulation require an annual check in accordance with the 
manufacturer’s recommendation.

•  For 1 level models, Aquilar recommends an annual check consisting of resetting units 

electrically to the factory calibration settings and carrying out a bump test to ensure correct 
operation. A gas calibration should be carried out every three years.

•  For 2 level models, Aquilar recommends annual checks by resetting units electrically to 

the factory calibration settings, a bump test and replacement of the sensors with a pre-
calibrated certi

fi

 ed sensor every three years. The alternative to replacement is an on-site 

gas calibration. Sensor replacement may be more cost e

 ective, eliminate end of life 

concerns and constantly renew the detection system

If the sensor is exposed to a large leak it should be tested to ensure correct functionality by 
electrically resetting to the factory calibration settings and carrying out a bump test.

There are two concepts that need to be di

 erentiated: bump test and calibration

LEAK DETECTION SOLUTIONS

1

BUMP TEST

This consists of exposing the sensor to a gas. 
The objective is to establish if the sensor is 
reacting to the gas and all the sensor outputs 
are working correctly. A quanti

fi

 ed bump test 

is one where gas of a know concentration is 
used.

CALIBRATION

This consists of exposing the sensor to a 
calibration gas, setting the “Sensor Standby 
Voltage”, the alarm set points “Alarm 
Threshold Voltages” and checking/adjusting 
all the outputs so that they are activated at 
the speci

fi

 ed alarm gas concentrations when 

exposed to this gas.

It is required by EN378 to record the check results in the Logbook

Before you carry out the test or calibration 
procedure:

1. Advise occupants, plant operators and 

supervisors

2. Check if the AT-G-DETECT is connected 

to external systems such as sprinkler 
systems, plant shut down, external 
sirens and beacons, ventilation etc. and 
disconnect as instructed by the customer.

3. For 1 level systems you must deactivate 

the 3 minute alarm delay, if selected, by 
removing jumpers JP1 to o

  position. For 

2 level systems upon power up there is a 
delay of 3 minutes before the green power 
LED turns on.

4. For bump test or calibration, AT-G-

DETECT’s should be powered up overnight.

5. If a unit has been powered o

  for a 

short time, say due to maintenance, it 
will normalise within a few minutes. If 
sensors have been in long term storage 
or have been turned o

  for a long period, 

normalisation would be much slower. 
However, within 1-2 hours sensors 
should have dropped below the low 
alarm level and be operational. You can 
monitor normalisation progress exactly by 
monitoring the sensor output, see Table 1.

Unit 30, Lawson Hunt Industrial Park, 

Broadbridge Heath, Horsham, West Sussex, 

RH12 3JR
+44 (0) 1403 216100
[email protected]
www.aquilar.co.uk

Summary of Contents for AquiTron AT-G-DETECT

Page 1: ...AT G DETECT Refrigerant Gas Sensing System Check Calibration Procedure AquiTron CA L I B R AT I O N P R O C E D U R E...

Page 2: ...ective is to establish if the sensor is reacting to the gas and all the sensor outputs are working correctly A quantified bump test is one where gas of a know concentration is used CALIBRATION This co...

Page 3: ...r does not go into alarm carry out a gas calibration If the factory set point information is not on the calibration label as with older units check the serial number of your gas detector on the rating...

Page 4: ...OULES 1 Make sure that both the ampoules and the calibration beaker are clean and dry 2 Unscrew the beaker hold screw and place the ampoule so that it sits in the base of the beaker 3 Tighten on the s...

Page 5: ...o the controller to monitor sensor response Expose the sensor to gas from the cylinder You can place the entire sensor into a plastic bag or use a plastic hose hood to direct gas to the sensor head G...

Page 6: ...3 minute alarm delay on a one level system by moving the jumper link at JP1 to the o position Two adjustments are required and they are all performed on the controller unit A Sensor Standby Voltage S...

Page 7: ...used drift B Alarm Threshold Voltage ATV Low Treshhold Connect voltmeter between TP5 0V TP2 Ve set the voltage asshown on the calibration label by adjusting pot P8 High Threshold Connect voltmeter bet...

Page 8: ...r extreme humidity or temperature conditions you may adjust the settings to compensate One Level Systems You should reduce the SSV level in 0 5V increments until the condition clears Two Level Systems...

Page 9: ...libration label You can monitor this as follows 1 level systems Connect a Voltmeter and monitor voltage between Pins 4 Ve 2 Ve of the sensor terminal connector block for each channel in turn CN1 CN2 E...

Reviews: