ELECTRICAL REQUIREMENT
DO NOT POWER THE SPA WITHOUT FIRST FILLING WITH WATER!
DANGER – RISK OF ELECTRIC SHOCK
Installations that do not conform to the following procedures and requirements may expose
users to electric shock. Non-conforming installations will not be covered under warranty.
If installed in the United States, the electrical wiring of this spa must meet the requirements of the
National Electric Code (NEC) and any applicable state or local codes. The electrical circuit must be
installed by an electrical contractor and approved by a local building electrical inspection authority.
1. Installations within 5 feet (1.5 m) of any metal surfaces must ground the metal surfaces to the
hot tub. Use an 8 AWG solid copper wire and attach it to the grounding lug on the control box,
located in the equipment compartment.
2. Only a licensed electrician may install power to the spa.
3. Power supply installation must include a suitably rated ground fault circuit interrupter (GFCI)
as required by NEC Article 680-42. The circuit breaker must be dedicated and should not be
shared with any other appliances. It must be labeled and easily accessible to users.
4. The electrical supply for the spa must include a suitable rated switch or circuit breaker to open
all ungrounded supply conductors to comply with Section 422-20 of the National Electric Code,
ANSI/NFPA 70. The disconnecting means must be readily accessible to the spa’s occupant but
installed at least 5 feet (1.5 m) from the spa water.
5. 230V Power supply lines must be hard wired into the control box. DO NOT use extension or
plug-type cords of any kind. The use of a shut-off box near the hot tub is also recommended.
This box provides a quick and convenient method to shut off power to the hot tub for
emergencies and maintenance.
6. Supply lines must be properly sized as per the NEC. A ground line must be provided that is as
large as the largest current carrying conductor, but no less than 8 AWG. Use copper wiring only.
7. Please open the front cover of the control box, and follow the instructions and wiring diagram
printed on the backside.
8. All 110 V powered models must use the provided 15 foot (4.5 m) GFCI cord and be plugged
directly into a dedicated grounded wall outlet.
9. CAUTION, 230V POWERED SPAS –
These spas must be hard wired to your
household electrical service box only. Do
Not use an extension cord or any other
disconnect-able power cord. The use of
an extension cord or a disconnect-able
power cord is highly dangerous and will
void all warranties!
• Wire size must be appropriate per NEC
and/or local codes.
• Wire size is determined by length of run
from breaker box to spa and maximum
current draw.
• THHN copper core wire is recommended.
• All wiring must be copper to ensure
adequate connections. Do not use aluminum wire.
ELECTRICAL REQUIREMENTS
Serial Number
Equipment Compartment
Summary of Contents for Aryana
Page 1: ...OWNER S MANUAL 110V 230V 60Hz Models 303556 21 A 9 20 ...
Page 48: ...MANUAL DEL PROPIETARIO Modelos de 110 V 230 V 303556 21 A 9 20 ...
Page 49: ...MANUAL DEL USUARIO Modelos de 110 V 230 V 60 Hz 303556 21ES A 9 20 ...
Page 73: ...MANUEL DU PROPRIÉTAIRE Modèles 110 V 230 V 60 Hz 303556 21FR A 9 20 ...