GB
GB
c
CAUTION!
HEATER
CONNECTIONS. COMPARE
WITH THE INSTALLATION
NOTE ATTACHED TO THE
DEVICE IN THE FACTORY!
KW
= Cold water
WW
= Hot water
ZL
= Circulation (optional)
F1
= Probe pin 1
F2
= Probe pin 2
WVL
= Supply heating coil
WRL
= Return heating coil
EHP
= E-heating cartridge
(optional)
FL
= Flange/inspection port
25
Aquarea Tank
Technical Data
(GB)
Typ
W 300
W 500
Nominal volume
Ltr.
288
440
Diameter
D
mm
700
Height
H
mm
1294
1921
Diagonal height
N
mm
1393
1990
Weight
kg
139
222
Connection size
R
1"
Cold water
KW
A
mm
55
Hot water
WW
J
mm
1229
1853
Connection size
R
11/4"
Heating supply
WVL
F
mm
784
1279
Heating return
WRL
B
mm
220
Heating
Heating
F1
F2
C
G
mm
466
874
699
1369
FL
mm
150
TK
L
mm
275
Blind flange
mm
450
Heating surface
m²
3,2
6,2
Continuous output
tCW=10°C
kW
68
131
tHW=45°C
l/h
1666
3222
Content of the heat exchanger
l
24
43
Performance indicator
tCW=10°C
11,5
33,5
Insulation strength
M mm
50
Perm. excess operating
pressure
Heating water
bar
10
Potable water
bar
10
Perm. operating temperature
Heating water
°C
110
Potable water
°C
95
IG = Internal thread / AG = External thread
* Subject to change! This thermal insulation is mounted subsequently and can vary. For more information please read separate instruction
manual.
** Without thermal insulation.
*** Vertical external sensor.
26
Aquarea Tank