Environmental Monitoring System (EMS-01) Instruction Manual
20
5
Operation
Ensure you have read the
Safety Information
in
section 1
before operating this product.
Configuration of
DIP Switch
settings will determine
sounder, alarm delay
, and
relay latch
activation during operating modes (see
section 4.1
).
Once powered on, the EMS-01 Leak Detector maintains a
background timing scheme
while continuously
monitoring sensor and sensitivity levels
. The unit continuously monitors connected
Aqualeak sensors
to
gather batches of data samples which are averaged over time to determine if a
cable fault
or
leak
has
occurred.
System status
is displayed via
indicator LEDs
and
operation
is undertaken via
capacitive touch buttons
located at the front of the unit:
Figure 17:
Front Panel of the Aqualeak EMS-01 Water Leak Detection System
EMS-01 Mode
Description
Monitor
Standard operating status.
Fault
Cable break detected.
Alarm
Leak detected.
Test
Test relays and Alarm for 15 seconds.
Engineering
Available only in Fault or Alarm modes. Disables relays.
Table 5:
Modes and Capacitive Touch Button Combinations
Mute Button
Test Button
Power Indicator
Alarm Indicator
Fault Indicator
Reset Button