Environmental Monitoring System (EMS-01) Instruction Manual
13
B.
Connect Sensor Cable (SCY) using LC10/LCB100 and Start of Line
Figure 8:
Sensor Cable Connection using LC10/LCB100 and Start of Line (No EOL Switch)
Connect the Sensor Cable using LC10/LCB100 and Start of Line (SOL) as follows:
1.
Ensure that the unit is powered OFF.
Connect the
leader cable
into the
sensor
input terminal
on the unit. Do not connect
the green or white cores
(
Figure 6
).
2.
Cable the opposite end of the
leader cable
in to the
Start of Line
(SOL;
Figure 8
).
3.
Plug the
sensor cable
into the connection
on the
SOL
.
4.
Once all sensor cables are connected, plug
the End of Line (EOL) terminator into the
end of the last run of the sensor cable.
LOOP TERMINAL
block not used
Green and white
cores not used
Belden 9534 Cable to
EMS Zone Input
Secure cable under clamp
strap
SENSE TERMINAL
Red Core: +/1
Black Core: -/2