WARNING !!!! Dealer & Service Center Use Only
Warning !
MAKE CERTAIN POWER SUPPLY TO HEATPUMP and CONTROLLER IS DISCONNECTED PRIOR
TO CONTINIUING. FAILURE TO DISCONNECT ELECTRICAL POWER MAY RESULT IN SERIOUS
INJURY OR DEATH.
1. String 18/3 cable from the controller to the heat pump.
2. Locate
the
MICROPROCESSOR POWER BOARD
inside the heat pumps electric box. (See figure 1)
3. Connect the 18/3 cable from the controllers low voltage heater terminals to the
MICROPROCESSOR
POWER BOARD
Jandy terminal block, terminals
X
,
Y
and
Z.
The terminals are as follows:
X
is the
HIGH/SPA
terminal,
Z
is
LOW/POOL
terminal, and
Y
is the
COM/OFF
terminal. (See figure 3 below)
4.
RECONNECT POWER TO THE HEATPUMP.
5. Simultaneously, press and hold, both the
UP
and
Down
arrow keys until
CF1
is displayed.
6. While
CF1
is displayed press the
POOL/SPA
key repeatedly until
LOC
is displayed. Now press the
UP
arrow repeatedly until
050
is displayed.
7. Press
the
POOL/SPA
key repeatedly until
JAO
is displayed. Press the
UP
arrow repeatedly until
3
is
displayed.
8. After a delay of approximately 10 seconds, the water temperature is displayed. Set the heat pumps
thermostats to the desired temperature settings. The heat pumps thermostats are now ready to be
selected by the controller.
*
NOTE
The Compool CP30 uses low voltage pigtails instead of terminals.
Figure 3