background image

AquaCal

®

Operation Manual

SMART CONTROLLER ENABLED

Important

Read this document before operating / installing this product

For additional product manuals and operation / installation procedures, please visit www.AquaCal.com

LTM0931 REV 1.02

Summary of Contents for GBB BB500

Page 1: ...Manual SMART CONTROLLER ENABLED Important Read this document before operating installing this product For additional product manuals and operation installation procedures please visit www AquaCal com...

Page 2: ......

Page 3: ...all Flex 16 1 6 b Operating Heat Pump With an External Controller 19 1 6 c Operating Heat Pump With an External Flow Switch 19 1 6 d Operating Heat Pump With a Gas Back Up 19 d 1 Using Gas Boost 20 d...

Page 4: ...d service of heat pump must be performed by an authorized service center l Warranties may be voided if the equipment has been improperly installed maintained or serviced l If service is deemed necessa...

Page 5: ...n persons having an adverse medical history or pregnant women should consult a physician before using a hot tub or spa Children and the elderly should be supervised by a responsible adult l Prolonged...

Page 6: ...al Flow Switch 19 1 6 d Operating Heat Pump With a Gas Back Up 19 1 6 e Operating Multiple Connected Heat Pumps 24 1 1 Wake Up Heat Pump The display back light will be off when the heat pump is in sle...

Page 7: ...vigate through menu options Used to decrease temperature set point and navigate through menu options Used to select heat pump s operating mode Also used to edit or confirm options in a menu Indicator...

Page 8: ...controlled by another connected heat pump Remote Controlled by external controller Heat Pump is set to be controlled by an external controller Set to 75 F Maintaining Maintaining a water temperature...

Page 9: ...red Heating light will activate l COOLING MODE After fan and compressor starts the blue Cooling light will activate l AUTO MODE After fan and compressor starts the heat pump will maintain the set temp...

Page 10: ...Up Programming 1 5 a Factory Defaults Certain options have been preset at the factory These options can be overwritten for site specific conditions NOTICE Failure to heed the following may result in d...

Page 11: ...SCHEDULED 24HR SET BACKUP GAS START 9 00 AM SET BACKUP GAS END 5 00 PM SET ENTRY CODE ENABLED OFF OFF ON SET USER ENTRY CODE 01 SET CALL FLEX MODE OFF OFF CALL FLEX 1 5 b Selecting Celsius or Fahrenh...

Page 12: ...Page 9 1 5 c Setting Date and Time Set the heat pump s time and date using the following steps 1 Operation...

Page 13: ...e 10 1 5 d Setting Date and Time Format The heat pump s time and date format can be customized Customize Time The time can be displayed in 24 hour military time the default display is 12 hour 1 Operat...

Page 14: ...Page 11 Customize Date The date can be displayed as Day Month Year the default is Month Day Year 1 Operation...

Page 15: ...Page 12 1 Operation...

Page 16: ...de Option The entry code feature can prevent unauthorized temperature adjustments This feature initiates after the heat pump goes into the sleep mode for the first time NOTICE Failure to heed the foll...

Page 17: ...Page 14 1 Operation...

Page 18: ...n PLEASE NOTE l If the heat pump displays a KEYPAD LOCKED message the heat pump is in sleep mode See Wake Up Heat Pump on page 3 l If an entry code has already been activated the code must be entered...

Page 19: ...rator has the option of changing how this accessory works using either CALL mode FLEX mode or OFF Default Using Call Mode When the accessory is in CALL or override mode the circulation pump will be se...

Page 20: ...n pump does not automatically activate in this mode l If the desired water temperature has not been met by the end of the circulation pump s schedule the normal time off setting will be overridden l T...

Page 21: ...Page 18 Configure for Flex mode 1 Operation...

Page 22: ...as been installed and enabled the heat pump thermostat will automatically switch between pool and spa depending on how the water flow actuators are set The Pool Spa button will be disabled when this d...

Page 23: ...the water temperature falls 2 F below the set temperature and the ambient air temperature is below 60 F l When the set temperature is reached the gas heater deactivates The heat pump then maintains th...

Page 24: ...Page 21 1 Operation...

Page 25: ...e gas heater s schedule must match the circulation pump s schedule l Setting a gas backup heater schedule is only necessary when the gas backup heater has been configured in scheduled mode Example bel...

Page 26: ...Page 23 1 Operation...

Page 27: ...r slaved unit on the display Changes in mode and operation are made on the master primary heat pump only l The master heat pump will automatically start and stop the slaved heat pumps in a timed and c...

Page 28: ...equipment l Do not allow water to flow through heat pump when refinishing or acid washing a pool Either use an installed bypass to route water away from heat pump or deactivate filter pump l To avoid...

Page 29: ...not spray water directly into the interior of the heat pump damage to components may result l Do not use chemicals on the display panel Cleaning 1 Wash outside cabinet using a low pressure water hose...

Page 30: ...olishing Agents The trademarks used in approved polishing agents are property of their owners and are not related to AquaCal 2 3 Clearances l Proper air circulation is required for the heat pump to op...

Page 31: ...30 V Titanium ThermoLink 120 GPM 280 GPM BB500 60 Hz 460 V Titanium ThermoLink 120 GPM 280 GPM PLEASE NOTE If minimum flow rates are not met heat pump performance is reduced and performance will suffe...

Page 32: ...r headed towards the heat pump to the half open position 5 Adjust the valves controlling water leading away from the heat pump to a fully open position 6 Activate the pool water filtration pump 7 Slow...

Page 33: ...prevent physical injury or damage to equipment For tasks requiring handling refrigerant an HVAC license is required Recommended Inspection Checklist 1 Clean Evaporator Coil As Applicable 2 Check Conta...

Page 34: ...oving water will not freeze Temporarily set the filter pump s time clock for continuous operation during light freeze conditions Hard Freeze Conditions A hard freeze is when the ambient air temperatur...

Page 35: ...FAULT 36 WATER TEMP SENSOR SHORT or WATER TEMP SENSOR OPEN 36 Issues and resolutions A Front Panel Warning Indicator is Red Select Units 36 Blank Display 36 Display Panel Not Responding 37 Displays D...

Page 36: ...sult in damage to equipment l Service by unauthorized personnel will void the heat pump warranty AIR TEMP SENSOR OPEN or AIR TEMP SENSOR SHORT ISSUE Open or shorted air sensor RESOLUTION A qualified t...

Page 37: ...e 29 HIGH WATER TEMPERATURE ISSUE Incoming water temperature has exceeded 110 F 43 C and the unit has been deactivated The heat pump will not operate until incoming water temperature drops to 100 F 38...

Page 38: ...w pressure faults during one call for heating or cooling RESOLUTION 1 Deactivate then reactivate power to the heat pump to clear error 2 Troubleshoot the low pressure issue causing the error l See LOW...

Page 39: ...irs must not be attempted by untrained or unqualified individuals l The heat pump contains refrigerant under pressure Repairs to the refrigerant circuit must not be attempted by untrained or unqualifi...

Page 40: ...sent through the coil to rapidly remove ice or frost During this process the melting of the ice may appear as steam coming off the heat pump This is normal Displays NO SYSTEM FIRMWARE ISSUE The heat p...

Page 41: ...splay illuminated l If not confirm the main breaker located at the power supply panel and the disconnect switch located near the heat pump are both turned on l If the display still does not illuminate...

Page 42: ...SSUE The heat pump will not deactivate RESOLUTION PLEASE NOTE When heat pump is set to off the display will show the current water temperature or no water flow indicator 1 Confirm the correct mode has...

Page 43: ...being heated not flowing into the pool 5 Confirm heat pump is transferring heat into the water l Measure the temperature of air discharge coming out of the heat pump fan If discharge air is between 8...

Page 44: ...ving heat out of the water 7 Confirm that filter pump has a sufficient run time The heat pump will not run or cool the water without water flow l See Cooling Recommendations on page 44 Ice Forming on...

Page 45: ...uced as a by product of the heat pump s refrigeration process The heat pump can produce up to 30 gallons of condensation per hour depending on the humidity of the ambient air Determine if the water is...

Page 46: ...4 1 Identifying Model Specifications 1 Find Data Plate The data plate is usually posted on the side of the equipment or the inside of the heat pump s access plate 2 Find the model number on the data...

Page 47: ...se a pool cover or blanket to reduce heating time 4 4 Cooling Recommendations The following recommendations will reduce the amount of time required to cool a pool or cold plunge application If unsure...

Page 48: ...xtend the swimming season l AquaCal recommends Lo Chlor Aqua Blanket Over Temperature Alarm Kit l This kit is an additional safety device It disables the heat pump if any malfunction occurs that allow...

Page 49: ...Page 46 Temperature Port Kit STK0133 l This port can be used to adjust water flow using Delta T l The kit comes with port installation components and a temperature probe 4 Appendix...

Page 50: ......

Page 51: ......

Reviews: