Troubleshooting Using Displayed Codes
Interpreting Error Codes
The HP7R heat pump microprocessor controller is designed to be self-diagnostic through the display
of various fault codes.
Owners & Operators: If you believe you are experiencing a problem with the heater, and feel a need to
call the factory for assistance, it will be beneficial to let the factory Service Representative know which
code is being displayed. Having this information at hand will permit the Service Representative to work
through–with you–any site related issues causing or contributing to the problem. Then, if after working
through site-related issues the heater is still not functioning correctly, the Service Representative will
offer to set up a service visit. As necessary, please Contact AquaCal Customer Support Group (800-
786-7751).
Dealers and Service Centers: For troubleshooting use, listed below are all possible fault messages
output by the microprocessor, what the codes mean, and possible causes with solutions for the
indicated problem. Please contact AquaCal Technical Support Group, as necessary (800-786-7751).
Controls Configuration & Adjustments...
WARNING !
Failure to heed the following may result in permanent
injury or death.
Heat pumps contain no owner or operator repairable components. Repairs must not be
attempted by untrained and/or unqualified individuals. If service is deemed necessary, contact
installing dealer or AquaCal Customer Support at (800) 786-7751.
(H
EAT
-O
NLY
U
NITS
)
M essage
Error Description
Possible Cause
[dPO]
Defrost Sensor Open
Cut or loose sensor wiring
[PO]
W ater Tem perature Sensor
Open
Cut or loose sensor wiring
[dPC]
Defrost Sensor Shorted
Short circuit in defrost sensor wiring or defective sensor.
[PC]
W ater Tem perature Sensor
Shorted
Short circuit in water tem perature sensor or defective sensor.
[LP]
Refrigerant System Low
Pressure Switch Open
System refrigerant charge low, defective low pressure switch, clogged
evaporator coil, or defective wiring.
[HP]
Refrigerant System High
Pressure Switch Open
Low water flow, defective high pressure switch, or defective wiring.
[HP5]
5 High Pressure Faults W ithin
One (1) Call for Heating or
Cooling (Lock Out Condition)
See causes for [HP]
[LP5]
5 Low Pressure Faults W ithin
One (1) Call for Heating or
Cooling (Lock Out Condition)
See causes for [LP]
[OTA]
Over Tem perature Alarm <
Tem perature over 110
o
F (Unit
Locked)
Defective com pressor contactor, defective controller, or defective
water tem perature sensor.
[FLO]
Low or No W ater Flow
Detected
Circulating pum p off, water filter dirty, isolation valves set improperly,
or defective pressure switch.
[FS]
Heater in Defrost Mode
Norm al function in lower air tem peratures. Fan continues to run and
compressor is off. Com pressor will restart when air-coil tem perature
reaches 38
o
F or above.
[CSE]
Control System Error
Controller m ay need to be reset. Disconnect then reconnect power to
controller. If error continues, replace control board, display board, or
both.
[CEr] Com m unication
Fault
Loss of com m unication between main board and display board. Reset
controller or replace com m unication cable.