3.INSTALLATION AND CONNECTION
3.5 Swimming Pool Heat Pumps Electrical Wiring
NOTE: Although the unit heat exchanger is electrically isolated from the rest of the unit, it
required to protect you against short circuits inside the unit. Bonding is also required.
The unit has a separate molded-in junction box with a standard electrical conduit nipple already in
place. Just remove the screws and the front panel, feed your supply lines in through the conduit
nipple and wire-nut the electric supply wires to the three connections already in the junction box
(four connections if three phase). To complete electrical hookup, connect Heat Pump by electrical
ies)
to a dedicated AC power supply branch circuit equipped with the proper circuit breaker,
disconnect or time delay fuse protection.
Disconnect - A disconnect means (circuit breaker , fused or un-fused switch) should be located
within sight of and readily accessible from the unit, This is common practice on commercial and
residential air conditioners and heat pumps. It prevents remotely-energizing unattended equipment
3.6 Initial startup of the Unit
NOTE-
circulate water through the heat exchanger.
Start up Procedure - After installation is completed, you should follow these steps:
1. Turn on your
2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire
controller, It should start in several seconds.
3. After running a few minutes make sure the air leaving the top(side) of the unit is
cooler(Between 5-10 )
4.
5. Allow the unit and pool pump to run 24 hours per day until desired pool water emperature is
reached. When the water-
automatically restart (as long as your pool pump is running)when the pool temperature drops more
than 2 below set temperature.
Time Delay- The unit is equipped with a 3 minute built-in solid state restart delay included to
protect control circuit components and to eliminate restart cycling and contactor chatter. This time
delay will automatically restart the unit approximately 3 minutes after each control circuit
interruption. Even a brief power interruption will activate the solid state 3 minute restart delay and
prevent the unit from starting until the 5 minute countdown is completed. Power interruptions
n.
12
version 3, release 05th Nov 2017
Summary of Contents for PHFD-02610
Page 1: ...SWIMMING POOL HEAT PUMP UNIT POMPA DI CALORE PER PISCINA version 3 release 05th Nov 2017...
Page 29: ...6 APPENDIX 3 Circuit diagram of the unit 27 PHFD 02715 version 3 release 05th Nov 2017...
Page 30: ...6 APPENDIX 3 Circuit diagram of the unit 28 PHFD 02720 version 3 release 05th Nov 2017...
Page 31: ...6 APPENDIX 3 Circuit diagram of the unit 29 PHFD 02730 version 3 release 05th Nov 2017...
Page 32: ...6 APPENDIX 3 Circuit diagram of the unit 30 PHFD 02740 version 3 release 05th Nov 2017...