6.APPENDIX
(2) Cable specification
1.
Single phase unit
Nameplate
maximum
current
Phase line
Earth line
MCB
Creepage protector
Signal line
No more
than 10A
2
1.5mm
2
1.5mm
2
20A
30mA less than 0.1 sec
n
0.5mm2
10~16A
2 2.5mm
2
2.5mm
2
32A
30mA less than 0.1 sec
16~25A
2 4mm
2
4mm
2
40A
30mA less than 0.1 sec
25~32A
2 6mm
2
6mm
2
40A
30mA less than 0.1 sec
32~40A
2 10mm
2
10mm
2
63A
30mA less than 0.1 sec
40 ~63A
2 16mm
2
16mm
2
80A
30mA less than 0.1 sec
63~75A
2 25mm
2
25mm
2
100A 30mA less than 0.1 sec
75~101A
2 25mm
2
25mm
2
125A 30mA less than 0.1 sec
101~123A
2 35mm
2
35mm
2
160A 30mA less than 0.1 sec
123~148A
2 50mm
2
50mm
2
225A 30mA less than 0.1 sec
148~186A
2 70mm
2
70mm
2
250A 30mA less than 0.1 sec
186~224A
2 95mm
2
95mm
2
280A 30mA less than 0.1 sec
2. Three
phase unit
Nameplate
maximum
current
Phase line
Earth line
MCB
Creepage protector
Signal line
No more
than 10A
3
1.5mm
2
1.5mm
2
20A
30mA less than 0.1 sec
n
0.5mm2
10~16A
3 2.5mm
2
2.5mm
2
32A
30mA less than 0.1 sec
16~25A
3 4mm
2
4mm
2
40A
30mA less than 0.1 sec
25~32A
3 6mm
2
6mm
2
40A
30mA less than 0.1 sec
32~40A
3 10mm
2
10mm
2
63A
30mA less than 0.1 sec
40 ~63A
3 16mm
2
16mm
2
80A
30mA less than 0.1 sec
63~75A
3 25mm
2
25mm
2
100A 30mA less than 0.1 sec
75~101A
3 25mm
2
25mm
2
125A 30mA less than 0.1 sec
101~123A 3 35mm
2
35mm
2
160A 30mA less than 0.1 sec
123~148A 3 50mm
2
50mm
2
225A 30mA less than 0.1 sec
148~186A 3 70mm
2
70mm
2
250A 30mA less than 0.1 sec
186~224A 3 95mm
2
95mm
2
280A 30mA less than 0.1 sec
When the unit will be installed at outdoor, please use the cable which can against UV.