Aqua Logic DSHP Series Installation & Operating Instructions Manual Download Page 3

Copyright© 2016 Aqua Logic, Inc.   Effective date of 1/2016 

 

 

 

 

 

Very Important! 

 

1.

 

The standard target fluid temperature is limited to a range of 40° F to 80° F on all Delta Star Heat pumps. Without 

special factory installed equipment, possible damage to the unit can occur when attempting to access fluid 

temperatures outside this range.  Aqua Logic, Inc.’s warranty does not apply to application temperatures under 

40°F or above 80° F without special factory modifications. 

 

Compressor crankcase heater must installed when ambient air temperature is 60°F and below.  

 

2.

 

Water going to the heat pump should be protected by filters to keep debris from collecting in the evaporator and 

condenser shells.  Clogged shells lead to heat exchange problems and will void the warranty. 

 

3.

 

Improperly installed or out of adjustment rapid sand filters can put sand into the stream of water flowing into the 

heat pump.  This condition is similar to “sand blasting” and may abrade holes in plumbing lines or the evaporator 

and condenser.  Conditions like these would void the Aqua Logic, Inc. warranty. 

 

40° F to 80° F Pool Temperature Applications 

 

Wetted parts contain titanium, PVC plastic, rubber, and polymer.  These materials are non-reactive with fresh and 

salt water.  You must consult with Aqua Logic, Inc. if any other fluids are to be pumped through the heat pump. 

 

If humid or wet conditions exist where heat pump is to be located, care must be taken to prevent water from 

getting on electrical components.   

 

4.

 

On some heat pump models, allow only qualified licensed personnel to supply electric power to heat pump.  

Installation must be done in accordance with local and national electrical code.  Delta Star heat pumps need a 

fusible disconnect installed within five feet.  The heat pump needs a dedicated power supply.  

Do not 

share the 

power feed with any other peripheral devices such as pumps, ultraviolet light sterilizers, or filters.  Install an 

interlock device such as a water flow switch which prevents the heat pump from energizing without the pump 

being on. 

 

5.

 

Double check electrical specifications on unit’s electrical access cover plate making sure of voltage, amperage, 

phase, and cps before energizing.  (

Do not

 remove any covers with electrical power on.) 

 

6.

 

Fluid must flow through the heat pump at all times.

  See heat pump specification sheet or product label for 

minimum and maximum flow rates.  Flow rates less than specification may result in evaporator freeze-up and 

cracking of the evaporator shells. Also over heating of the heat pump can occur due to lack of water flow to the 

condenser.  Aqua Logic Inc. does not warranty evaporator shells operating under low flow conditions and 

compressor burn outs due to overheating. 

 

7.

 

Incoming water pressure to the evaporator must not exceed 50 psi and condenser must not exceed 100 psi.  Over 

pressuring the evaporator and condenser may cause damage to the shells, which is 

not 

covered under warranty.   

 

 

 

 

 

Summary of Contents for DSHP Series

Page 1: ...s heat pump It has been designed and built to provide years of reliable trouble free service It provides a precise water temperature control up to 1 0 F 0 7 C accuracy and features a continuous LCD di...

Page 2: ...PECTION Protect yourself File your claim immediately with the transportation company Remember Aqua logic Inc is not responsible for any damage after the carrier accepts a shipment Claim for FULL VALUE...

Page 3: ...exist where heat pump is to be located care must be taken to prevent water from getting on electrical components 4 On some heat pump models allow only qualified licensed personnel to supply electric p...

Page 4: ...tings on the front of the heat pump Be careful not to over tighten the plastic fittings 3 Install flow switch if supplied either on the water inlet or outlet side with at least 12 inches of straight p...

Page 5: ...mp and set the correct water flow rate 2 Apply power to the unit 3 Adjust temperature controller set point to desired water temperature See Heat pump Control Set up Cooling When the temperature contro...

Page 6: ...s either up key to increase or the down key to select the correct Stage 1 mode Stage 1 MUST be in the H1 mode for correct operation 5 Press the SET key again to access the chill mode set point tempera...

Page 7: ...the heat pump If there is no air or low air flow through the condenser the pressure will build up and cause the switch to trip off When there a refrigerant leak the switch will protect the heat pump f...

Page 8: ...d or bleach into the water DO pour water into acid or bleach solution DO NOT perform acid and bleach flushing at the same time The gas generated by the mixture is poisonous and can result in serious i...

Page 9: ...OK Wiring Replace flow switch Pressure Cutout Switch 1 Check condenser entering water flow and water temperature 2 Check for low refrigerant pressure Check Refrigerant level 3 Liquid gauge high pressu...

Page 10: ...intenance by user or their agent Damage caused due to misapplication of product Damage caused by corrosion abuse accident alteration or improper use Damage caused by flood fire earthquake tornado or o...

Reviews: