6. Trouble Shooting 

Use the table below to solve minor problems. 

Problem 

LCD/LED/Buzzer 

Explanation / Possible cause 

What to do 

When power fails, 

the backup time is 
shorten. 

Battery low alarm 
issue quickly. 

Battery voltage is too low. 

Charge  the  unit  at  least  8 
hours. 

Battery  capacity  is  not  full  even 
after charge the unit for at least 8 

hours. 

Check  the  date  code  of  the 
battery.  If  the  batteries  are 

too old, replace the batteries. 

Mains exist but the 
unit works in 

battery mode. 

Input voltage is 
displayed as 0 on the 

LCD and green LED is 
flashing. 

Input protector is tripped 

Check if AC breaker is tripped 

and  AC  wiring  is  connected 
well. 

Green LED is flashing.  Insufficient quality of AC power. 

(Shore or Generator) 

1. Check if AC wires are too 

thin and/or too long. 
2. Check if generator (if 

applied) is working well or if 
input voltage range setting is 
correct. (UPS

Appliance) 

Green LED is flashing.  Set “Solar First” as the priority of 

output source. 

Change output source priority 

to Utility first. 

No LED display on 
the front panel 
when the utility 

power is normal. 

No LED display. 

Battery is not connected well. 

Check the external battery 
cable and terminal. Make sure 

all the battery connections to 
the unit are all correct. 

Battery defect.   

Replace the batteries. 

Buzzer beeps 
continuously and 

red LED is on. 

Fault code 00 

Output short circuited.   

Check if wiring is connected 
well and remove abnormal 
load.   

Fault code 01 

Overload error. The inverter is 

overload 110% and time is up. 

Reduce the connected load by 
switching off some 

equipment. 

Fault code 02 

Battery weak 

1. Re-charge battery. 
2. Replace battery. 

Fault code 03 

Output voltage too high 

Return to repair center. 

Fault code 04 

Main relay stick 

Return to repair center. 

Fault code 05 

Fan fault 

Replace the fan. 

Fault code 06 

Internal temperature of inverter 
component is over 100°C. 

Check whether the air flow of 

the unit is blocked or whether 
the ambient temperature is 
too high. 

Fault code 07 

Output voltage too low 

Return to repair center. 

Fault code 08 

Battery is over-charged.   

Return to repair center. 

The battery voltage is too high. 

Check if spec and quantity of 

batteries are meet 
requirements. 

If there is any abnormal situations occur, which doesn't list above, please call the service people immediately 

for professional examine. 

Summary of Contents for Inverex S1200 XP Solar

Page 1: ...Model No S1200 XP Solar S2400 XP Solar 720W 1440W V 1 0 Quick Guide...

Page 2: ...Table of Contents 1 Introduction 1 2 Important Safety Warning SAVE THESE INSTRUCTIONS 1 3 Product Overview 2 4 Installation 2 5 Operation 5 6 Trouble Shooting 12 7 Specifications 13...

Page 3: ...ualified service center when service or repair is required WARNING Provide ventilation to outdoors from the battery compartment The battery enclosure should be designed to prevent accumulation and con...

Page 4: ...ry terminal RED cable to the positive terminal BLACK cable to the negative terminal WARNING Please use the appropriate battery cable Please refer to Important Safety Warnings Section for the details S...

Page 5: ...rnal battery terminals Step 8 Take the DC breaker on Connect to Solar Panel CAUTION Before connecting to PV modules please install separately a DC circuit breaker between inverter and PV modules WARNI...

Page 6: ...PV module numbers in parallel Take S1200 inverter as an example to select proper PV modules After considering Voc of PV module not exceeds 40Vdc and max Vmpp of PV module close to 15Vdc or within 15Vd...

Page 7: ...down BAT MODE Buzzing continuously Line mode LCD Display Display Function Input source information Indicates the AC input Indicates the PV input Indicate input voltage input frequency battery voltage...

Page 8: ...ng mode Press UP or DOWN button to select setting programs And then press ENTER button to confirm the selection or ESC button to exit Setting Programs Program Description Selectable option 00 Exit set...

Page 9: ...ge Wide default If selected acceptable AC input voltage range will be within 90 280VAC Narrow If selected acceptable AC input voltage range will be within 170 280VAC 06 Auto restart when overload occu...

Page 10: ...t priority Utility will charge battery only when solar energy is not available Utility first Utility will charge battery as first priority Solar energy will charge battery only when utility power is n...

Page 11: ...uency PV voltage charging current battery voltage output voltage output frequency load percentage load in Watt load in VA load in Watt DC discharging current main CPU Version and second CPU Version Se...

Page 12: ...PU version checking Secondary CPU version 00003 03 Output frequency Output frequency 50Hz Operating Mode Description Operation mode Description LCD display Standby mode Note Standby mode The inverter...

Page 13: ...rence Code Fault Code Fault Event Icon on Fault Code Fault Event Icon on 00 Output short circuit 05 Fan locked 01 Over load time out 06 Over temperature 02 Battery weak 07 Output voltage too low 03 Ou...

Page 14: ...ity power is normal No LED display Battery is not connected well Check the external battery cable and terminal Make sure all the battery connections to the unit are all correct Battery defect Replace...

Page 15: ...Time 20 ms typical Waveform Simulated Sine Wave BATTERY Battery Voltage 12 VDC 24 VDC Floating Charge Voltage 13 7 VDC 0 25 VDC 27 4 VDC 0 5 VDC Maximum Charge Current 10A or 20A SOLAR CHARGER Chargi...

Reviews: