APsystems YC1000-3 Installation/User Manual
11
Installation Procedures
Step 4 - Connecting APsystems Microinverters to the PV Module
Place the PV modules into position on the racking and connect the DC input cables to the
microinverters based on optimum layout configuration (up to four PV modules per
microinverter).
CH4 CH3
CH2 CH1
Figure 6
The status LED for on each microinverter will blink green three (3) times to indicate
normal operation once DC power is applied.It is important to understand that this “start
up” sequence occurs once the first module is connected to the microinvert and is
successfully generating DC power. The “start up” sequence does NOT reoccur as
additional modules are connected to the same microinverter.
Step 5 - Install a Bus Cable End Cap at the end of AC bus cable
a
b
.
Set the parts on the cable.
c
.
Insert five wires into the core wires hole of the
body.
d
.
Insert seal and Clamp Finger into the body ,then
tighten the nut, torque 2.5±0.5NM.
Figure 7