Aprilaire 8920W Safety & Installation Instructions Download Page 2

Wire specifications:

18-24 gauge thermostat wire

Installation notes:

•   Ensure power at the HVAC equipment is off . 
•   Loosen screw terminals, insert stripped wire and 

re-tighten .

•   Push the excess wire back into the opening and plug the 

wall opening to prevent drafts .

 

 Connection to terminal 1 at equipment control module

 

 Connection to terminal 2 at equipment control module

 

 Connection to terminal 3 at equipment control module

T1 & T2 

  

Remote temperature sensor (optional)

INSTALLATION

THERMOSTAT INSTALLATION LOCATION RECOMMENDATIONS

EQUIPMENT CONTROL MODULE INSTALLATION LOCATION RECOMMENDATIONS

Thermostat should be mounted:

•   On an interior wall, in a frequently 

occupied space .

•   Approximately 5‘ above floor .
•   At least 18” from outside wall .
•   Thermostat can be mounted to a 

vertical junction box .

Equipment control module should be mounted:

•   In a location where the temperature will not exceed 

158°F (70°C) or drop below 32°F (0°C) .

Do not mount thermostat:

•   Behind doors, in corners or other dead air spaces .
•   In direct sunlight, near lighting fixtures, or other appliances that 

give off heat .

•   On an outside or unconditioned area wall .
•   In the flow of a supply register, in stairwells, or near outside doors .
•   On a wall with concealed pipes or ductwork . 

REMOTE TEMPERATURE SENSOR (OPTIONAL)

THERMOSTAT WIRING

A remote temperature sensor can be used for control if the thermostat is to be mounted in a concealed location 
or a remote sensor can be averaged with the thermostat sensor to control a large space . An 8051 flush mount 
or 8053 surface mount remote temperature sensor can be attached to the T1 and T2 terminals and mounted in a 
recommended area . The remote sensor must be enabled in the installer setup menu, and once enabled will override 
or be averaged with the thermostat’s internal temperature sensor, based on the setting .

Remote temperature sensor should be mounted:

•   On an interior wall, in a frequently occupied space .
•   Approximately 5‘ above floor .
•   At least 18” from outside wall .
•   Using less than 300’ of wire .

Do not mount remote sensor:

•   Behind doors, in corners or other dead air spaces .
•   In direct sunlight, near lighting fixtures, or other 

appliances that give off heat .

•   On an outside or unconditioned area wall .
•   In the flow of a supply register, in stairwells, or near 

outside doors .

•   On a wall with concealed pipes or ductwork . 
•   Near 120 VAC lines .

THERMOSTAT MOUNTING

EQUIPMENT CONTROL MODULE MOUNTING

1 .  Remove the rear mounting plate from the thermostat . 
2 .  Pull wires through the opening on the rear mounting plate .
3 .  Position and level the mounting plate of the thermostat on wall and 

mark the hole locations with a pencil .

4 .  Drill 1/4” holes and insert supplied anchors (drywall only) .
5 .  Place mounting plate over anchors, insert and tighten screws .
6 .  Seal wire entry holes to prevent drafts affecting temperature readings .

The equipment control module has the following features to simplify mounting and wiring and provide for a clean 
and neat installation .
•   Six (6) mounting holes . One on each corner and two centered top and bottom . Any combination of these holes 

may be utilized . Mount the equipment control module using 2 to 4 #8 screws appropriate for the mounting surface 
substrate . (See 

Figure 2

 .)

•   Wires can be routed through 

the top, bottom, sides or back .

•   Nylon wire ties can be used 

to secure wires in 10 places .

Installation Steps

1 .  Select mounting location .
2 .  Pull from bottom to remove 

front cover . (See 

Figure 1

 .)

3 .  Mount base using 2 to 4 #8 

screws (field supplied) .

INSTALLATION

Do not mount equipment control module:

•   On foundation walls or on the HVAC equipment or 

ductwork . These locations can cause moisture to 
condense on the equipment control module .

Figure 1

Figure 2

Note:

 Installer must touch a grounded metal object before handling the equipment control module to avoid potential 

damage due to electrical discharge .

90-2122

90-2123

90-2124

English

 3

2 

English

Summary of Contents for 8920W

Page 1: ...bles 10 12 General system settings table 10 Thermostat system settings table 11 12 Indoor Air Quality system settings tables 13 16 Humidifier system settings table 13 14 Dehumidifier system settings table 14 Air cleaning system settings table 15 Fresh air system settings table 15 16 Installer system test 16 Wi Fi setup 16 Quick reference to controls display 17 18 Thermostat features 18 Troubleshoo...

Page 2: ...perature sensor should be mounted On an interior wall in a frequently occupied space Approximately 5 above floor At least 18 from outside wall Using less than 300 of wire Do not mount remote sensor Behind doors in corners or other dead air spaces In direct sunlight near lighting fixtures or other appliances that give off heat On an outside or unconditioned area wall In the flow of a supply registe...

Page 3: ...2 sensor to the ODT terminals and enabling the outdoor sensor in the installer setup menu When an outdoor sensor is installed the features below will be enabled In heat pump mode the outdoor temperature sensor can be used to efficiently utilize an air source heat pump When the outdoor temperature is less than the Low Balance Point the heat pump will be locked out and only auxiliary heating will be...

Page 4: ...OLING LOCATE SENSOR IN SHADED AREA CONVENTIONAL HEAT COOL TWO TRANSFORMER REMOVE JUMPER HEATING TRANSFORMER COOLING TRANSFORMER C R W W2 B Y Y2 O G L RH RC C 3 EQ HP HC G Y3 Y2 Y W3 W2 W TRANSFORMER THERMOSTAT 1 2 2nd COOLING 1st COOLING FAN 1st HEATING 2nd HEATING 3rd HEATING 3rd COOLING 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source 1 RE...

Page 5: ...FAULT DETECT REVERSING VALVE REVERSING VALVE 2nd HEATING 1st HEATING FAN 1st COMPRESSOR 2nd COMPRESSOR 2 1 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source INDOOR AIR QUALITY WIRING DIAGRAMS INDOOR AIR QUALITY WIRING WITH SEPARATE TRANSFORMERS INDOOR AIR QUALITY WIRING WITH A SINGLE TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER VNT DH HUM ...

Page 6: ...compressor stages Heat Pump mode only One Two Number of Auxiliary Heat Stages Select number of auxiliary heat stages Heat Pump mode only One Two Number of Stages of Heat Select number of heat stages Heat Cool mode only One Two Three Number of Stages of Cool Select number of cool stages Heat Cool mode only One Two Three Remote Temperature Sensor Installed Select if the remote sensor is attached and...

Page 7: ...ettings are only present dependent upon the value of other settings The use of an outdoor temperature sensor recommended enables additional Indoor Air Quality functionality Please refer to the Model 8920W Owner s Manual for further information about thermostat features Note Refer to manuals for humidifier dehumidifier air cleaner and ventilation products for recommended installation and operation ...

Page 8: ...y default setting bold and setting range Fresh Air Vent Installed Selects if ventilation is installed If set to No no other ventilation settings will be available No Yes Display Button Note only available if Fresh Air Installed is set to No Yes No Fresh Air Setup Type Selects if ventilation is configured through the Code setup or Comfort Comfort setup has more lockout options Code setting ensures ...

Page 9: ...MPERATURE SCALE LOCKOUTS AWAY MODE SETTING IF ENABLED AWAY MODE STATUS IF INSTALLED FAN MODE SELECTION CLEAN DISPLAY TOUCHSCREEN IS OFF FOR 30 SECONDS ROOM TEMPERATURE HUMIDITY HEAT SETTING THERMOSTAT NAME System setting Description Factory default setting bold and setting range Enable Low Vent Temperature Limit Enables low ventilation temperature lockout limit Only available if Outdoor Sensor is ...

Page 10: ...ting Equipment Type to make sure it is set to match the installed heating cooling equipment HEATING IS NOT DISPLAYED Check Installer Setting Control Setup is set correctly Change the System Mode to Heat and set the temperature level above the current room temperature COOLING IS NOT DISPLAYED Check Installer Setting Control Setup is set correctly Change the System Mode to Cool and set the temperatu...

Page 11: ... to 50 R H Dehumidification 40 to 90 R H SPECIFICATIONS Electrical Operating voltage 24VAC 18 30VAC Current Maximum 2 5A total 1 0A single output Maximum surge current 5A Environment Temperature shipping 30 to 150 F 34 to 65 C Temperature thermostat operating 32 to 120 F 0 to 48 C Temperature equipment control module operating 32 to 158 F 0 to 70 C Relative humidity Operating 5 to 90 R H non conde...

Reviews: