5
also wait 5 minutes minimum between cooling and heating cycles.
This is intended to help protect the compressor from short cycling.
Some newer compressors already have a time delay built in and
do not require this feature. Your compressor manufacturer can tell
you if the lockout feature is already present in their system. When
the thermostat compressor time delay occurs it will fl ash the
Snowfl ake
and
Flame icons
for about fi ve minutes.
4.
Select Temperature Display Adjustment 3 LO to 3 HI
–
Allows you to adjust the room temperature display up to 3° higher
or lower. Your thermostat was accurately calibrated at the factory
but you have the option to change the display temperature to match
other temperature measuring devices. The current or adjusted room
temperature will be displayed on the left side of the display.
5. To exit the confi guration menu, move the SYSTEM switch from the
OFF position.
6
7
8
6
9
10
8
5
4
3
2
1
FIGURE 5 – Thermostat buttons, display and switches
CONFIGURATION MENU
The confi guration menu allows you to set certain thermostat operating
characteristics to your system or personal requirements.
1. To enter the confi guration menu, with SYSTEM switch in OFF
position, hold
and
for at least two seconds.
2.
Select Fast or Slow Cycling
– In the run mode, if the setpoint
temperature is manually raised by 3°F (2°C) or more above the actual
temperature with the TEMPERATURE UP key, and the fast second
stage feature is enabled (FA on), the second stage will energize
immediately. With FA off, second stage will not energize until the
setpoint temperature is 1°F or more beyond actual temperature for
more than ten minutes.
3.
Select Compressor Lockout CL OFF or ON
– Selecting CL ON
will cause the thermostat to wait 5 minutes before turning on the
compressor if the heating and cooling system loses power. It will
CONFIGURATION MENU
Step
Press Button(s)
Displayed
(Factory Default)
Press
or
to select:
1
Set SYSTEM switch
to OFF
2
and
for
at least 2 seconds
FA (ON)
OFF
3
and
momentarily
CL (OFF)
ON
4
and
momentarily
0 HI (0)
3 LO to 3 HI
5
Move SYSTEM
switch from OFF
Return to normal operation
SPECIFICATIONS
ELECTRICAL DATA
Electrical Rating:
20 to 30 VAC 50/60 Hz.
0.05 to 1.0 Amps (Load per terminal)
1.5 Amps Maximum Total Load
(All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range:
32°F to 105°F
Operating Humidity Range:
0 to 90% RH (non-condensing)
Shipping Temperature Range:
-40°F to 150°F
CLEANING THE THERMOSTAT
If the surface of the thermostat becomes dirty it can be cleaned with
plain water or a non-abrasive household cleaner including glass
cleaner. When using any cleaner, be careful not to get any into the
interior of the thermostat.
Do not spray any liquid directly onto
the thermostat.
Spray the cleaner onto a soft cloth and wipe the
surface of the thermostat.
TROUBLESHOOTING
RESET OPERATION
If a voltage spike or static discharge blanks out the display or causes
erratic thermostat operation you can reset the thermostat by pressing
and
at the same time when system is switched from “OFF”
to “HEAT” position. This also resets the factory defaults. If the thermostat
has power, has been reset and still does not function correctly, contact
your heating/cooling service person or place of purchase.
BATTERIES
For optimum performance, we recommend replacing batteries once a
year with fresh “AAA” Energizer
®
alkaline batteries.