background image

11

FILTER CLEANING

Normally, the fresh air filter will need to be removed and cleaned every six months, but check it after the first three months following 

installation to determine if more or less frequent cleaning will be necessary. After cleaning the filter inside the ventilator, clean off 

the screen at the fresh air intake hood on the outside of the house� The most common cause of reduced ventilation is a clogged air 

intake hood�

START UP AND SEQUENCE OF OPERATION

Set the Ventilation Time knob to the setting that was determined in the previous section� The ventilator will turn on with the HVAC 

equipment for the set number of minutes during the one-hour cycle period� If the HVAC equipment does not turn on enough, the 

ventilator will turn on, and will turn on the HVAC system blower if wired to do so, at the end of the one-hour cycle period to ensure 

the desired ventilation time is met. The first time it turns on, it will stay on for five minutes to get an accurate air temperature 

measurement� If the air temperature is within the range that is set (see 

SET UP

), the ventilator will turn on for the amount of time 

selected within the one-hour cycle period�
If the air temperature is outside of the set range, then no additional ventilation will occur for another hour, and the cycle period will 

automatically adjust to four hours� When the ventilator starts again, it will sample the air temperature and if in range, will meet the set 

amount of ventilation during the four-hour cycle period. For example, if the Vent Time was set to 25 minutes per hour and the first time 

the ventilator came on it measured an air temperature above the high limit setting, it would turn off after five minutes. The control will 

automatically change the cycle period to four hours and work to provide the additional 95 total minutes of ventilation (25 min/hr * 

4 hours = 100 minutes, minus the five minutes of the first air sampling) during the four-hour cycle period.
If the air temperature is still out of range, the control will automatically switch to an 8-hour cycle period, then a 12-hour cycle period 

and finally a 24-hour cycle period. During 8, 12 and 24 hour cycle periods, the total ventilation time increases to compensate for 

ventilation effectiveness as defined in ASHRAE Standard 62.2-2010. When the cycle period automatically adjusts to 24-hours, the 

control will turn on ventilation to meet the requirements even if the temperature is outside of the set limits�

To clean the ventilator filter 

(see 

FIGURE 11

):

1. 

Flex the outside edges of 

the filter door to disengage 

it from the housing�

2. 

Lift the filter door to remove 

the filter from the ventilator. 

3. 

Use water to rinse the 

filter and shake the excess 

moisture off the filter.

4. 

Replace the filter in the 

ventilator and press the 

outside edges of the filter 

door to snap it in place�

FILTER DOOR

FIGURE 11

90-2715

Summary of Contents for 8145A

Page 1: ...PORT HIGH PRESSURE PORT HIGH PRESSURE PORT INLET COLLAR AND NORMALLY CLOSED POWER DAMPER INLET COLLAR AND NORMALLY CLOSED POWER DAMPER OUTLET COLLAR OUTLET COLLAR SURFACE MOUNT BRACKET LOCATION JOIST MOUNT BRACKET LOCATION INSTALLATION OPERATING INSTRUCTIONS Model 8145A Fresh Air Ventilator Ventilation ...

Page 2: ...2 Improper installation may cause property damage or injury Installation service and maintenance must be performed by a qualified service technician TABLE OF CONTENTS Safety Instructions 2 Introduction and Compliance Statement 3 Specifications 3 Install Electrical Outlet 4 Ventilator Location and Orientation 4 Mount the Ventilator 5 Mount Intake Hood 6 Install Ductwork 6 Wiring the Control to the ...

Page 3: ... Fresh Air Ventilator will meet the mechanical ventilation requirements of Energy Star Certified Homes EPA Indoor airPLUS 2012 2018 International Residential Code IRC 2012 2018 International Energy Conservation Code IECC California Energy Commission Title 24 ASHRAE Standard 62 2 2010 ASHRAE Standard 62 2 2013 2016 SPECIFICATIONS TABLE 1 SPECIFICATIONS External Static Pressure w c Airflow CFM Effic...

Page 4: ...ount the blower at least 3 3 feet 1 0 m from any accessible opening of the duct Choose a location for the ventilator that is within 6 feet of the outlet into which the ventilator will be plugged Allow space for filter removal and service as shown in FIGURE 2 The ventilator can be mounted in any orientation 12 FILTER ACCESS 24 FAN ACCESS 90 2514 FIGURE 2 CLEARANCES FOR SERVICING INSTALL ELECTRICAL ...

Page 5: ...into the proper locations as shown in FIGURE 4 Use the mounting locations nearest the cover for mounting between floor joists or hanging from rafters Use the mounting locations near the bottom of the unit for surface mounting i e to a flat wall ceiling surface or bottom of joists 3 Screw the ventilator brackets into joists or a strong platform using the 10 x 3 4 screws provided The ventilator weig...

Page 6: ...the hood with caulk INSTALL DUCTWORK Install 6 diameter flexible insulated duct from the round inlet collar of the unit to the intake hood and from the oval outlet collar of the unit to the HVAC system Duct the outlet of the ventilator to the return side of the HVAC system refer to FIGURE 5 IMPORTANT The end of the insulation must be sealed to prevent condensation from forming inside the insulatio...

Page 7: ...T W G VENT GF R C W Y G R C W Y G THERMOSTAT HVAC SYSTEM CONTROL WIRE NUT FIELD SUPPLIED EXISTING WIRE NEW WIRING GF VENT G W ODT NOT USED C R VENTILATION CONTROL R C W Y G G Y W C R THERMOSTAT HVAC SYSTEM CONTROL EXISTING WIRE NEW WIRING 90 2714 FIGURE 6 REMOVE CONTROL KNOB AND COVER FIGURE 7 PREFERRED VENTILATOR TURNS ON THE HVAC SYSTEM BLOWER AS NEEDED DO NOT REMOVE THE PRE INSTALLED YELLOW OR ...

Page 8: ...ink and show the firmware revision level Return the knob to the OFF position until the desired Time Setting is determined R C ODT W G VENT Gf 90 2005 FIGURE 9 ADJUST HIGH LOW TEMPERATURE LIMIT SET UP The control can be set up to prevent ventilation during the hottest or coldest periods of the day When the outdoor temperature exceeds the high value or falls below the low value ventilation will stop...

Page 9: ... the cover of the ventilator or TABLE 2 to convert the pressure reading to delivered airflow If the pressure reading falls between listed values either use the lower value or interpolate between values CFM Lower Value Higher Value Lower Value 10 Pressure Reading Lower Value Pressure The following is an example a Measured Pressure Reading is 0 34 w c b TABLE 2 lists 200 CFM 0 3 w c and 170 0 4 w c ...

Page 10: ...SELECT VENT TIME 1 Measure the outdoor air flow CFM through the duct that is bringing in only outdoor air 2 Use the CFM Delivered along with the CFM required to find the Cycle Time per hour setting from TABLE 4 For example if the ventilator is providing 120 CFM and the requirement is 70 CFM set the time to 35 minutes 3 Use the control knob to set the vent time to the determined minutes per hour NO...

Page 11: ...four hours When the ventilator starts again it will sample the air temperature and if in range will meet the set amount of ventilation during the four hour cycle period For example if the Vent Time was set to 25 minutes per hour and the first time the ventilator came on it measured an air temperature above the high limit setting it would turn off after five minutes The control will automatically c...

Page 12: ...S VOID DUE TO FAILURE TO USE A QUALIFIED CONTRACTOR ALL DISCLAIMERS OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTALLATION Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages so the above exclusion or limitations may not apply to you This warranty gives you specific legal rights and you may also have o...

Reviews: