background image

R

C

NOT

USED

ODT

INPUTS

OUTPUTS

POWER

W G

VENT

Gf

VENTILATION CONTROL

R

C

W

Y

G

R

C

W

Y

G

THERMOSTAT

HVAC SYSTEM CONTROL

WIRE NUT – FIELD SUPPLIED

EXISTING WIRE
NEW WIRE

OPTIONAL DISCONNECT SWITCH – LABEL

“MECHANICAL VENTILATION” 

DO NOT 

REMOVE THE PRE-INSTALLED YELLOW WIRES

WHEN WIRING TO THE HVAC SYSTEM.

FIGURE 7 

– VENTILATOR WIRING

WIRING

The ventilator control is wired to the HVAC equipment as shown in 

FIGURE 7

 to provide the control with power and to signal the control 

that the HVAC system is operating . When ventilation is needed but the 
HVAC system is not running, the ventilator will turn on the HVAC system 
blower to temper the outdoor air by mixing it with indoor air .

If the “Minutes per Hour” dial on the ventilator control is not readily 
accessible, install an optional switch to break the ventilator control “R” 
wire as shown in 

FIGURE 7

 . Label the switch so as to differentiate it 

from other switches (“Mechanical Ventilation” label is provided in the 
carton with the ventilator) .

1. 

Disconnect power to the HVAC system prior to wiring to the HVAC 
system controls .

2. 

Run standard thermostat wire (18-22 AWG) as needed between the 
ventilator, HVAC system and the disconnect switch .

3. 

Wire as shown in 

FIGURE 7

 .

4. 

Label the disconnect switch to differentiate it from other switches .

SET UP

The control can be set up to prevent ventilation during the hottest or 
coldest periods of the day . When the outdoor temperature exceeds 
the high value or falls below the low value, ventilation will stop and 
additional ventilation will be brought in at a later time . See 

Start Up and 

Sequence of Operation

 section for details .

1. 

Remove the knob then remove the cover to adjust the high/low 
temperature limit (see 

FIGURE 8

) .

2. 

Use a small flat head screwdriver to turn the potentiometer to 
select:

 

A

 –  No limit, time only

 

B

 –  105°F high limit, 20°F low limit

 

C

 –  100°F high limit, 30°F low limit

 

D

 –  95°F high limit, 40°F low limit

R C

ODT W G

VENT

Gf

90-2005

FIGURE 8 

– SET TEMPERATURE LIMITS

TEST

After all ducting and wiring is complete, plug in the ventilator, restore power to the HVAC system and make sure the switch controlling the ventilator’s 
electrical outlet is turned on . Turn the thermostat to the OFF mode to ensure that wiring the HVAC system has been done correctly and then return it 
to the desired mode after testing . Rotate the Vent Time setting knob to Test/Reset:

1. 

The display will show “- -”, the green “Active Ventilation” LED will blink

2. 

The ventilator blower will start

3. 

If the ventilator was properly wired to turn on the HVAC unit blower with ventilation, the HVAC blower will turn on

4. 

If a separate damper was wired to the inlet duct (ventilation air discharges to the return side of the HVAC system), the damper will open

5. 

After one minute the test will end and the display will blink and show the firmware revision level . Return the knob to the OFF position until the 
desired Time Setting is determined .

5

Summary of Contents for 8140

Page 1: ...ON 1 Read all instructions before beginning installation 2 Improper installation may cause property damage or injury Installation service and maintenance must be performed by a qualified service technician VENTILATION CONTROLLER FILTER COVER INLET COLLAR OUTLET COLLAR TABLE OF CONTENTS Introduction and Compliance Statement 2 Specifications 2 Install Electrical Outlet 2 Ventilator Location and Orie...

Page 2: ... time and effectiveness of the ventilation schedule The control will also ensure that ventilation occurs no less than one hour of every four When properly installed and set the Model 8140 8141 Fresh Air Ventilators will meet the mechanical ventilation requirements of Energy Star Certified Homes Version 3 EPA Indoor airPLUS Version 1 2012 2015 International Residential Code IRC 2012 2015 Internatio...

Page 3: ... located above the centerline of the collar see FIGURE 3 to ensure that it closes when the ventilator is off Remove the outlet collar and rotate it 180 if needed to make sure the backdraft damper functions properly 10 FILTER ACCESS 24 MOTOR ACCESS 90 2121 FIGURE 2 CLEARANCES FOR SERVICING CORRECT INCORRECT DAMPER PIVOT CENTERLINE OF COLLAR 90 2121 FIGURE 3 OUTLET COLLAR ORIENTATION MOUNT THE VENTI...

Page 4: ...e air at a location where it will not be directed through a supply duct to one small space but will be distributed to multiple supply registers refer to FIGURE 6 IMPORTANT The end of the insulation must be sealed to prevent condensation from forming inside the insulation If a plastic zip tie is used to secure the insulation to the hood collar also tape the end to seal it against condensation probl...

Page 5: ... hottest or coldest periods of the day When the outdoor temperature exceeds the high value or falls below the low value ventilation will stop and additional ventilation will be brought in at a later time See Start Up and Sequence of Operation section for details 1 Remove the knob then remove the cover to adjust the high low temperature limit see FIGURE 8 2 Use a small flat head screwdriver to turn...

Page 6: ...The ventilator will turn on with the HVAC equipment for the set number of minutes during the one hour cycle period If the HVAC equipment does not turn on enough the ventilator will turn on and will turn on the HVAC system blower if wired to do so at the end of the one hour cycle period to ensure the desired ventilation time is met The first time it turns on it will stay on for five minutes to get ...

Page 7: ... MOTOR 24VAC TRANSFORMER R C NOT USED ODT INPUTS OUTPUTS POWER W G VENT Gf VENTILATION CONTROL M RED BLOWER RUN CAPACITOR GRN BLU BRN BRN BLK WHT MOLEX CONNECTOR BLK GRN L2 WHT L1 BLK CHASSIS GROUND GND CHASSIS GROUND BLK WHT BLK WAGO CONNECTORS DPST RELAY YLW YLW YLW R C NOT USED ODT INPUTS OUTPUTS POWER W G VENT Gf VENTILATION CONTROL FIGURE 9 MODEL 8140 INTERNAL SCHEMATIC FIGURE 10 MODEL 8141 I...

Page 8: ...ERS OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTALLATION Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages so the above exclusion or limitations may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state WARRANTY REGISTRATION...

Reviews: