12
-
(3)Ductwork
Prepare the closet ductwork for later connection
to the case.
The total flow rate(CFM) and external static
pressure (ESP) available can be estimated from
the chart below.
The collar on top of the case accepts standard
10"duct.Pull all duct tight. Extra duct slack can
greatly increase Static pressure.
NOTICE:
Flex duct can collapse and cause
airflow restrictions. Do not use flex duct for 90°
bends or unsupported runs of 5 ft. or more.
High
CFM
Medium
CFM
Medium
CFM
Low
CFM
0.00
550
450
425
410
0.04
515
410
395
375
0.10
465
360
350
320
0.15
440
310
300
270
0.20
405
245
240
205
0.25
365
225
180
120
0.30
310
-
110
-
0.00
585
520
520
450
0.04
550
485
485
410
0.10
505
435
435
360
0.15
470
385
385
310
0.20
430
345
345
245
0.25
390
285
285
225
0.30
340
230
230
-
0.00
585
525
525
510
0.04
550
490
490
475
0.10
530
440
440
420
0.15
505
390
390
375
0.20
470
350
350
320
0.25
430
290
290
250
0.30
390
235
235
180
ON
18K
Airflow -CFM
ESP
(in.water)
09K
12K
Indoor Fan CFM
Duct Select Switch
OFF
Inside
wall
metal
duct
Air
discharge
outlet
Leveling legs
3. Using field-supplied screws, bolt the case to the
platform.
1
.
4
.
2
.
Primary female
drain fitting 3/4”
Bolt case
to platform
External
drain
OR
Internal
Drain(s)
NOTE: Piping is not
supplied with the unit.
Obtain locally.