Applied Comfort NYWC Series Installation & Operation Manual Download Page 9

9

802961 Rev. 00  

comfortable setting is determined and set, no other 
adjustments are necessary. 

Over-adjusting the thermostat will not increase the rate at 
which the unit will heat or cool the space; it is merely an on-
off switch that responds to temperature. 

Fan speeds in heating and cooling operation are controlled 
by a “Fan Speed” knob. Rotate the knob to the right of “0” 
for cooling operation, and to the left of “0” for heating 
operation. Rotation of the knob changes fan speed as 
follows: 

3 = High Speed  2 = Low Speed  1 = Low Speed 

ATTENTION:

 When operating in cooling mode, if the 

compressor is shut off by rotation of the “Temperture” or 
“Fan Speed” dial, then wait for 3 minutes before re-starting 
the compressor.   

Figure

Thermostat Temperature Limiting Feature

   

 

The purpose of temperature limiting is to allow the property 
owner to control the maximum and minimum temperature 
that an end-user can obtain during operation of the unit, and 
can be an important energy saving feature. This is 
accomplished by limiting the thermostat knobs range of 
rotation between preset limits set by the property owner. The 

unit is shipped from the factory allowing a wide range of 
rotation. Altering the range of rotation is easily done. 

Remove the thermostat knob by pulling it with sufficient 
force—DO NOT PRY. Turn the knob over and observe the 
plastic rib coming off the side of the knob stern. The rib is 
designed to engage limiting stop screws that can be arranged 
to limit the maximum and minimum set-point temperatures 
for the thermostat. On the dial plate, just below the 
thermostat shaft you will notice two Phillips head screws 
(with washers) in “Standard Position” (see Fig. 1). This 
allows a wide range of thermostat rotation, representing a 
range of temperatures between approximately 18°C and  
29°C (65ºF and 85ºF). The left screw in Standard Position 
can be removed and re-inserted in four alternate holes 
moving in a clockwise direction in order to reduce the 
maximum allowable set-point temperature for heating. 
Similarly, the right screw can be relocated in four alternate 
holes moving in a counter-clockwise direction to increase 
the minimum allowable set-point for cooling. Moving to the 
next screw location alters the set point limit by about 1.4ºC 
(2.5ºF) (see Fig 2). 

For example, moving the left screw clockwise 4 positions 
over from Standard Position limits the maximum heating 
set-point temperature to 29.4ºC – (4 x 1.4ºC) = 23.8ºC (85ºF 
– (4 x 2.5ºF) = 75ºF). Similarly, moving the cooling set-
point right screw counter-clockwise 2 positions over from 
Standard Position limits the minimum temperature to 18.3ºC 
+ (2 x 1.4ºC) = 21.1ºC (65ºF + (2 x 2.5ºF) = 70º F).  
Therefore in this example roughly speaking, the end user 
cannot heat the room to greater than 23.9°C (75ºF) nor cool 
the room to less than 21.1°C (70ºF) .Experimentation may 
be necessary to obtain a desirable setting. Keep in mind that 
the actual thermostat temperature sensing occurs at the 
sensing bulb in the return air stream, sensing air being pulled 
in through the bottom of the front panel near the floor. 
NOTE : IF THE ROOM TEMPERATURE IS STILL NOT 
SATISFACTORY AT THE COOLEST THERMOSTAT 
SETTING, THEN COMPLETELY REMOVE THE RIGHT 
HAND LIMITING STOP SCREW. 
Before reinstalling the knob, manually turn the thermostat 
shaft so that the rib under the knob will locate in between the 
stop screws once the knob is installed.  Failure to follow this 
step will yield an unintended temperature range. 

Summary of Contents for NYWC Series

Page 1: ...PACKAGED TERMINAL AIR CONDITIONERS Hydronic or Steam Heating and Cooling Unit INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Page 2: ...ting coil and evaporator coil at least annually or more often as dictated by the severity of the particulates and pollutants circulating in the outdoor and indoor operating environments One suggested method is as follows Unimpeded Outdoor Airflow Do not block off the outside air flow to the unit The condenser air inlet and outlet must be free of obstructions and of any external influence that woul...

Page 3: ...lt units are furnished with a NEMA 5 15P or 5 20P non locking plug as applicable The respective plug will require a NEMA 5 15R or 5 20R receptacle to be field provided All 277 Volt units are furnished with a NEMA 7 20P 20 Amp non locking plug and hence will require a NEMA 7 20R receptacle to be field provided Note 277 Volt units are considered to be permanently connected per the National Electrica...

Page 4: ...not be used connect the ends blue orange of the aquastat leads together to permanently complete the aquastat circuit 6 If the unit is equipped with mechanical knob controls and touchpad this variation cannot be adapted to work with a remote thermostat Locate the 24 VAC aquatsat output connector beneath the control box A mating connector and 6 feet of wire leads are supplied to connect to an aquast...

Page 5: ...ing diodes LEDs display the actual temperature of the air entering the unit at floor level The display can also be used to indicate the desired set point temperature for room comfort It is important to remember that the temperature displayed is the temperature sensed at the unit s indoor air inlet and can be significantly different from the bulk room temperature at a distance from the unit On Off ...

Page 6: ...LL THERMOSTAT CONVERSION TO 24V REMOTE THERMOSTAT Except for the wall thermostat and thermostat cable everything is included with the unit to field convert a keypad operated unit to 24 Volt AC wall thermostat operation by qualified service personnel Specific conversion instructions are detailed on the wiring diagram affixed to each particular unit to be converted Conversion involves accessing the ...

Page 7: ... a random 5 to 15 second delay before the electronic control powers up The keypad will be totally disabled once the DIP switch has been set for remote mode The unit will obey the commands from the thermostat only The thermostat will automatically maintain the temperature in the room based on the setting pre set by the user If the thermostat has only single fan speed capability a decision will need...

Page 8: ...own for any reason a 3 minute time delay will elapse before the compressor is allowed to re start This prevents compressor overload during re start due to unequal system refrigerant pressures Indoor Coil Freeze Protection Control of frost on the evaporator coil due to low indoor loads or cold outdoor ambient temperatures is provided The protection remains active when the unit is OFF for either key...

Page 9: ...screws with washers in Standard Position see Fig 1 This allows a wide range of thermostat rotation representing a range of temperatures between approximately 18 C and 29 C 65ºF and 85ºF The left screw in Standard Position can be removed and re inserted in four alternate holes moving in a clockwise direction in order to reduce the maximum allowable set point temperature for heating Similarly the ri...

Reviews: