Applied Comfort ESEC Series Installation & Operation Manual Download Page 10

10 

803161 Rev. 01  

 
The procedure to set the limits is as follows: 
 
Depress the On/Off key, the °F/°C key, and the 
Warmer key simultaneously for 5 seconds to enter the 
limit setup mode. The Warmer and Cooler keys will 
scroll through the R-values indicated in the above 
table. Once the desired R-value has been obtained on 
the display, press the On/Off key to accept the change, 
and then press it again to effect the change and restore 
the normal display. 

 
ELECTROMECHANICAL DIAL CONTROLS

 

 
Room temperature is controlled on both heating and 
cooling by the temperature control knob. Clockwise 
rotation decreases the temperature in the room. 
Counter-clockwise rotation decreases the temperature 
in the room. 
 
Rotate the “Temperature” dial a small amount at a time 
in the direction that you wish the temperature to go. 
Moving the dial more than ½” at a time may over-
compensate, leading to an extreme hot or cold 
situation. Once a comfortable setting is determined and 
set, no other adjustments are necessary. 
 
Over-adjusting the thermostat will not increase the rate 
at which the unit will heat or cool the space; it is 
merely an on-off switch that responds to temperature. 
 
Fan speeds in heating and cooling operation are 
controlled by a “Fan Speed” knob. Rotate the knob to 
the right of “0” for cooling operation, and to the left of 
“0” for heating operation. Rotation of the knob changes 
fan speed as follows: 
 
3 = High Speed 2 = Low Speed  1 = Low Speed 
 

ATTENTION:

 When operating in cooling mode, if 

the compressor is shut off by rotation of either dial, 
then wait for 3 minutes before re-starting the 
compressor.   

 

 

 
Figure 3  
 
Fan Cycling Switch: 
 

The chassis includes a continuous/intermittent fan 
feature.  Located on the left bottom corner of the 
control box is a rocker switch used to switch between 
continuous and intermittent fan operation. 
 
With the rocker switch in the 

“Continuous”

 position, 

as indicated by the label on the front of the unit, the 
indoor fan will continue to operate as long as the unit is 
switched on in either the heating or cooling mode.  The 
fan will operate continuously at the fan speed selected. 
 
With the rocker switch in the 

“Intermittent”

 position, 

and the unit in cooling mode, the indoor fan will 
operate only when there is a call for cooling by the 
adjustable thermostat.  Similarly with the unit in 
heating mode, the indoor fan will operate only when 
there is a call for heating in order to satisfy the heat 
setting on the adjustable thermostat. 
 
It is recommended that continuous fan operation be 
selected in the cooling mode to avoid excessive 
temperature “swings” in the conditioned space. 
 
The most effective indoor temperature sensing and 
highest comfort levels are achieved when room air is 
being drawn continuously across the sensing bulb of 
the unit thermostat. If complaints of large temperature 
swings in the room are experienced, then switch the 
unit to continuous fan operation. 

 

The front cover must be removed to access the switch. 

 
 
 
 
 
 

Summary of Contents for ESEC Series

Page 1: ... TERMINAL HEAT PUMP PTHP AND ESEC SERIES UPFLOW PACKAGED TERMINAL AIR CONDITIONER PTAC INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Page 2: ...ith the PTHP PTAC chassis If it is a replacement situation and the original filter needs replacing or is not even present the filter is available to order as Part No ACCRSFILTER Washable air filters can be cleaned with soap and water Inspect and clean the filter a least once a month or more often as conditions dictate Replace as necessary A dirty clogged filter reduces the efficiency of the system...

Page 3: ...e unit Do not place articles on discharge grille especially liquids Reducing Load To reduce the cooling load draw drapes or blinds in the summer to reflect direct rays from the sun To reduce the cooling and heating load keep windows and doors closed when operating the unit WALL SLEEVE CABINET INSTALLATION Install the wall sleeve cabinet in strict accordance with the wall sleeve installation instru...

Page 4: ...tly connected per the National Electrical Code The plug and cord are considered to be a connector of convenience in order to facilitate easy removal of the chassis for servicing The plug and cord are suitably protected when using the non optional 277 volt sub base 230 208 and 115 volt units are true cord connected units and are provided with a service cord of the LCDI Leakage Current Detection Int...

Page 5: ...e used If so connect the multi wire 24 volt wiring harness to the mating plug protruding beneath the control box as applicable following the detailed instructions on the particular wiring diagram affixed to the specific unit being installed Insulated crimp on connectors are provided at the end of every connection lead to facilitate connections insulation 5 If the unit is equipped with Mechanical k...

Page 6: ...m the unit On Off Key Each press of the key toggles the unit from an OFF state to an ON state or from an ON state to an OFF state Heating and cooling functions as well as the display and all indicating LEDs except for the fan indicators are enabled or disabled with this key When toggled OFF the control preserves only two modes active fan only and room freeze protection Fan Key Each press of the Fa...

Page 7: ...affixed to each particular unit to be converted Conversion involves accessing the high voltage wiring compartment and changing a DIP switch setting on the electronic board Once the DIP switch setting has been changed operation will be in remote thermostat mode as soon as power is restored to the control WARNING The conversion procedure involves exposure to high voltage electrical circuits in the c...

Page 8: ...witch has been set for remote mode The unit will obey the commands from the thermostat only The thermostat will automatically maintain the temperature in the room based on the setting pre set by the user If the thermostat has only single fan speed capability a decision will need to be made as to whether the fan will always run in high speed or low speed and then the appropriate fan speed wiring co...

Page 9: ...e protection remains active when the unit is OFF for either keypad or remote thermostat application as long as the unit is plugged in power is available and a heat source is configured in the unit and is working Compressor Short Cycle Protection If the electronic control shuts the compressor down for any reason a 3 minute time delay will elapse before the compressor is allowed to re start This pre...

Page 10: ...an speed as follows 3 High Speed 2 Low Speed 1 Low Speed ATTENTION When operating in cooling mode if the compressor is shut off by rotation of either dial then wait for 3 minutes before re starting the compressor Figure 3 Fan Cycling Switch The chassis includes a continuous intermittent fan feature Located on the left bottom corner of the control box is a rocker switch used to switch between conti...

Page 11: ...g operation will be suspended and also heat pump heating operation if applicable will switch over to electric resistance heating mode automatically if there is a demand for heat until the outdoor temperature rises to an acceptable point depending on the application Thermostat Temperature Limiting Feature The purpose of temperature limiting is to allow the property owner to control the maximum and ...

Page 12: ...r cool the room to less than 21 1 C 70ºF Experimentation may be necessary to obtain a desirable setting Keep in mind that the actual thermostat temperature sensing occurs at the sensing bulb in the return air stream sensing air being pulled in through the bottom of the front panel near the floor NOTE IF THE ROOM TEMPERATURE IS STILL NOT SATISFACTORY AT THE COOLEST THERMOSTAT SETTING THEN COMPLETEL...

Reviews: