7
Getting Started
⚠
CAUTION
Always use a grounded outlet that meets minimum voltage supply requirements for
industrial equipment. Do not use with portable power generators.
⚠
CAUTION
Always open valves slowly for safety, and to check for leaks.
⚠
CAUTION
The G1Single is equipped with a 550psi (38.6 kg/cm
2
) pressure shut off switch to protect
the machine from damage. This does not prevent overfilling of the storage container.
(See Page 6)
PREPARING FOR OPERATION
Before connecting or operating the G1Single, verify that your accessory equipment is in good working
condition:
•
.
A leaking hose may cause venting of refrigerant, and may introduce atmospheric air
or other contaminants into the recovered refrigerant. Examine the
gaskets on each hose
to ensure
they are intact, checking for any damage or wear that may lead to leaks.
•
Examine your external manifold gauges for proper valve operation and calibration of the gauges.
Contact the manifold gauge manufacturer for instructions in this process.
•
Check your
refrigerant scale
with a known weight to ensure that is operating correctly. A malfunctioning
scale may not alert you to the amount of refrigerant in the storage container.
•
Check that the
debris screen at the inlet fitting
is clean before starting every job. This screen
prevents damage to the machine that may get past the inline filter. When pumping dirty/used
refrigerant, this screen may quickly clog and slow the process when used without an inline filter.
•
Verify the
power source
provides adequate voltage at the machine while it is running (within 10% of
the rated power). When using an extension cord, follow the sizing guidelines on Page 4.
•
Remove all “Schrader”-type
access valve cores
from the access fitting. Remove
core depressors
from the hoses. Hoses going into the tank and hoses connected to the outlet of the G1Single should
be completely open and free from any restrictions (no core depressors, no “quick disconnect” fittings).
•
Use a
new inline filter dryer
with the machine when pumping dirty refrigerant. Replace the filter dryer
after each use. If the filter has exceeded its capacity, this may affect the performance of the machine.
•
To maximize recovery speeds
: use the shortest length of 3/8” hoses possible. Even with 1/4” fittings,
the larger hose can deliver better performance during vapor recovery. When using a Manifold Gauge
Set, use a manifold with a 3/8” or larger diameter bore to maximize liquid and vapor refrigerant flow.
•
When using 3/8” hoses and manifolds, some slight valve throttling on the Manifold Gauge Set may be
helpful in reducing compressor noise in some conditions (such as with very cold refrigerant), though
it is not required for proper operation of the machine.
✪
For additional refrigerant recovery tips, see pages 12 and 13.
ACCESSORY EQUIPMENT
Additional tools and equipment are used to connect the G1Single to the system you are recovering
refrigerant from. Verify operational details and safety information from the manufacturers of other
equipment before use.
G1SINGLE OPERATION MANUAL
© 2012 APPION INC. - ALL RIGHTS RESERVED
⚠
CAUTION