Locking Mechanism

The detectors can be locked into the base by removing a tab as shown in Fig. 2.

To unlock the detector, insert a 1.5mm hex driver or similar diameter tool into the small hole 

opposite the XPERT card and twist the detector anti-clockwise.

The XPander base module can be locked to the mounting plate by means of a grub screw. 

Access to which is through the base module cover label opposite the XPERT card

The address of the unit is set using the XPERT card, see table overleaf. Commission the 

detector according to the XPander commissioning guide PP2286.

XPERT Card Addressing

The XPander XPERT card is specifi cally designed for XPander products and has profi led 

address pips for ease of installation. The use of standard XPERT cards is not recommended. 

Select the desired address and remove the pips indicated in black. Remove pips with a  

small screwdriver. 

© Apollo Fire Detectors Limited 2007 TP

Fig 1   Mounting Details

Snip along marked lines and remove this 

part to lock the detector to the base.

© Apollo Fire Detectors Limited 2008/TP

Fig 2.   Locking Mechanism

XPERT Card Insertion and Removal

Removal requires access to the inner section of the base. Detach the detector from its 

base. Insert a fl at-blade screwdriver just inside the rim of the base above the XPERT card 

and disengage the card retaining clip whilst pulling the XPERT card out.

Battery Type

Panasonic

Varta

6 x AA 1.5V Alkaline Panasonic Powerline (Size M, LR6)

6 x AA 1.5V Alkaline Varta Industrial (4006, LR6)

When replacing batteries, allow the device to power down for a period of two minutes 

before installing replacements.

Note: When replacement batteries are required all batteries must be replaced together.

Technical Data

Operating voltage                                  2.8-5VDC

Operating temperature               –10°C to +50°C