XP95A & Soteria UL 268 7th Edition Detectors
Installation Instructions
General
These instructions apply to the Apollo Soteria UL Bases. Please refer to the table below for
instructions on how to install:
Applicable Wiring Diagram (page 3)
Applicable Products
Fig. 1 - New Installs (supports isolation)
SA5000-210 – Soteria UL Base - 4”
SA5000-230 – Soteria UL Base - 6”
Fig. 2 - Retro
fi
ts or Isolator bypassed
with a Remote LED
SA5000-210 - Soteria UL Base - 4”
SA5000-230 - Soteria UL Base - 6”
Fig. 3 - Retro
fi
ts or Isolator bypassed
with a Common Remote LED
SA5000-210 - Soteria UL Base - 4”
SA5000-230 - Soteria UL Base - 6”
Installation
These products must be installed in accordance with the applicable NFPA standards, local
codes and jurisdictional authorities. Failure to follow these instructions may result in failure of
the detectors to report an alarm condition. Apollo Fire Detectors Limited is not responsible
for detectors which are improperly installed, maintained or tested.
Before installing these products, check the continuity, polarity and insulation resistance
of all wiring. Check that installation is in accordance with the
fi
re system drawings and
conforms to all applicable local codes such as NFPA 72.
Use 3" octagonal box for direct connection to the base. 4" octagonal and 4" square boxes
may be used with compatible UL listed mounting brackets. When mounting on a wall, install
4" to 12" from the ceiling. Secure the base to the electrical box with appropriate screws.
Do not overtighten the screws
. For information on how to set the address of each device
correctly refer to the section 'XPERT 8 Card Addressing' overleaf.
If you are using shielded cable, please follow the instructions below:
1. Connect the shield to the terminal on the base.
2. When shielded loop cable is used, connection of the shield, also known as the functional
earth (FE), must be terminated in accordance with the control panel manufacturer’s
recommendations and local codes.
3. Unless instructed otherwise, ensure that all segments of the loop cable has functional
earth (FE) continuity and take care that it is isolated from building earth (also known as
protective earth (PE)) points such as metalwork, cable trays or junction boxes.
PLEASE NOTE:
Smoke detectors are NOT to be used with detector guards.
During construction work it is essential that the detector has it’s dust cover
fi
tted. The
build-up of dust inside a detector can lead to a trouble signal or false alarm.
1
4
39215-345/Issue 2
Technical Data XP95A Detectors
Detector Model No
SA5150-650APO**
SA5150-750APO**
SA5800-450APO
Detector Type
Soteria UL
Smoke Detector
Soteria UL Multi-Criteria
Detector (Smoke/Heat)
Discovery/Soteria UL
Non-isolating Heat Detector
Equivalent Obsolete
Dectector
58000-650
58000-750
58000-450
UL Listed Voltage
17- 28 V dc
17 - 28 V dc
17- 28 V dc
Modulation Voltage
(V peak to peak)
5 - 9 V
5 - 9 V
5 - 9 V
Maximum Alarm
Current LED on*
4 mA
4 mA
3.5 mA
Surge Current*
1 mA
1 mA
1 mA
Supervisory Current*
500
μ
A
500
μ
A
500
μ
A
Additional Remote
LED Current*
5 mA
5 mA
5 mA
Heat Element Rating
N/A
Modes 1,3,4 Rate of Rise (RoR)
20ºF/min (11ºC/min). Mode 5
135ºF (57ºC)
135ºF (57ºC) - 210ºF (99ºC)
Sensitivity
As SA5050-250APO
As SA5050-350APO
N/A
UL/ULC Instruction
Smoke-automatic
fi
re detec-
tor for use with a S5022 UL/
ULC listed base
Smoke-automatic
fi
re
detector head with integral
heat detector for use with a
S5022 UL/ULC listed base
Heat-automatic
fi
re detector
for use with a S5022 UL/ULC
listed base
Test Method
Please refer to test methods in the table above
Control Panel
Refer to www.apollo-
fi
re.co.uk for compatible panels
* All current measurements made with polling off **Isolation feature is only available in SA5150-650APO and SA5150-750APO
Technical Data Soteria UL Detectors
Detector Model No
SA5050-250APO
SA5050-350APO
SA5500-450APO
Detector Type
XP95A Smoke Detector
XP95A Multi-Criteria
Detector (Smoke/Heat)
XP95A Heat Detector
Equivalent Obsolete
Dectector
55000-650
55000-886
55000-450
UL Listed Voltage
17 - 28 V dc
17 - 28 V dc
17 - 28 V dc
Modulation Voltage
(V peak to peak)
5 - 9 V
5 - 9 V
5 - 9 V
Maximum Alarm
Current LED on*
4 mA
4 mA
2.5 mA
Surge Current*
1 mA
1 mA
1 mA
Supervisory Current*
340
μ
A
500
μ
A
250
μ
A
Additional Remote
LED Current*
5 mA
5 mA
5 mA
Heat Element Rating
N/A
Rate of Rise (RoR) 20ºF/min
(11ºC/min)
131ºF (55ºC)
Sensitivity
UL 1.23%/Ft -2.09%/Ft
ULC 1.44%- 2.3%/Ft
UL 1.23%/Ft -2.09%/Ft
ULC 1.44%- 2.3%/Ft
N/A
UL/ULC Instruction
Smoke-automatic
fi
re detec-
tor for use with a S5022 UL/
ULC listed base
Smoke-automatic
fi
re
detector head with integral
heat detector for use with a
S5022 UL/ULC listed base
Heat-automatic
fi
re
detector for use with a
S5022 UL/ULC listed base
Test Method
Please refer to the panel manufacturer instructions
Spray with any of the following smoke products:
• Solo Detector Testers Solo A10 • Smoke Sabre Smoke
Detector Tester • Solo Detector Testers Solo 365 • Solo
Detector Testers Testi
fi
e
Hair Dryer
Control Panel
Refer to www.apollo-
fi
re.co.uk for compatible panels