3
2
Wiring Details
To maintain the integrity of the ‘type A’ product it is essential that suitable cable glands be
used.
Maximum Loop Current Consumption at 24V
Operating
temperature
–20ºC to +60ºC (T4)
–20°C to +40°C (T5)
The test set can also perform data integrity tests of an entire system.
Note: the test key must remain inserted for at least 2 seconds to ensure the correct CIE
response.
Address Setting
The address of the Manual Call Point is set using the DIL switch. All segments of the switch
are set to 0 or 1, using a small screwdriver or similar tool.
A complete list of address settings is shown in the following table.
DIL switch
DIL switch
DIL switch
DIL switch
DIL
switch
setting
setting
setting
setting
setting
addr 1234567 addr 1234567 addr 1234567 addr 1234567 addr 1234567
1
1000000 11
1101000 21
1010100 31
1111100 41
1001010
2
0100000 12
0011000 22
0110100 32
0000010 42
0101010
3
1100000 13
1011000 23
1110100 33
1000010 43
1101010
4
0010000 14
0111000 24
0001100 34
0100010 44
0011010
5
1010000 15
1111000 25
1001100 35
1100010 45
1011010
6
0110000 16
0000100 26
0101100 36
0010010 46
0111010
7
1110000 17
1000100 27
1101100 37
1010010 47
1111010
8
0001000 18
0100100 28
0011100 38
0110010 48
0000110
9
1001000 19
1100100 29
1011100 39
1110010 49
1000110
10
0101000 20
0010100 30
0111100 40
0001010 50
0100110
51 1100110
61 1011110
71 1110001
81 1000101
91 1101101
52
0010110 62
0111110 72
0001001 82
0100101 92
0011101
53 1010110
63 1111110
73 1001001
83 1100101
93 1011101
54 0110110
64 0000001
74 0101001
84 0010101
94 0111101
55
1110110 65
1000001 75
1101001 85
1010101 95
1111101
56
0001110 66
0100001 76
0011001 86
0110101 96
0000011
57
1001110 67
1100001 77
1011001 87
1110101 97
1000011
58
0101110 68
0010001 78
0111001 88
0001101 98
0100011
59
1101110 69
1010001 79
1111001 89
1001101 99
1100011
60
0011110 70
0110001 80
0000101 90
0101101
100
0010011
101
1010011 106
0101011 111 1111011 116
0010111 121
1001111
102
0110011 107
1101011 112 0000111 117
1010111 122
0101111
103
1110011 108
0011011 113 1000111 118
0110111 123
1101111
104
0001011 109
1011011 114 0100111 119
1110111 124
0011111
105
1001011 110
0111011 115 1100111 120
0001111 125
1011111
126 0111111
The switch in Fig 2 shows address setting 78 as an example of how to set the address
Troubleshooting
Before investigating individual units for faults, it is important to check that the system wiring
is fault free. Earth faults on data loops or interface zone wiring may cause communication
errors.
Many fault conditions are the result of simple wiring errors. Check all connections to the
unit. Do not overtighten screws when mounting the backbox.
Fault Finding
Problem
Possible
Cause
No response or missing
Incorrect address setting
Loop terminal incorrectly
fi
tted
Incorrect wiring (polarity reversed)
Alarm condition
Glass or element incorrectly
fi
tted or broken
Test key not removed
Operating voltage
14-22V DC
Quiescent
230
μ
A
Alarm Current (max LED on)
4mA
IP
rating
IP67
LED Indicator
Illuminated red (under CIE control) when call point is operated
Commissioning
Manual call points must be installed to comply with the requirements of the ATEX directive
or another applicable codes of regulations. All unused cable entry ports must be sealed
using suitable stopping plugs to give the required level of ingress protection.
Ensure that a glass or deformable element is
fi
tted to each call point before testing. Use the
test key provided to check the operation of each device. An XP95 Test Set, part no. 55000-
870, may be used to carry out functional testing of individual units (from the safe area only).
Fig 2
Terminal block connections
and address 78 set
1
2
3
4
5
6
7
O
N
0
1
0
1
1
1
0
ON
= 0
Loop connections
+
+
–
–
Fig 1
Backbox
93mm
95
m
m
Fig 3
Cover removal