23. Event Logger
The System Controller contains a logging function which will store information for the most
recent 50 events on each Detector.
For each Fire or Fault activation, the controller will store:
If there have been power-cycle events on the controller, all timing information will be lost for
those events that occurred prior to the most recent of the power-cycles.
To erase and restart the event logger, press and hold ‘left’ and ‘right’ keys together when
displaying any of the event log entries. Press ‘tick’ when prompted by ‘SurE’.
To access the event log, press tick on the Event Logger icon when the relevant detector is
highlighted:
Event
Code
Event Number
01 is the most recent event
02 is the event before 01
03 is the event before 02, and so on
• The event code – This is the same as the error code (E-__) that would be displayed during
the Fault, or one of the following:
• 99 - Log erased
• 98 - Power cycle
• 97 - Fire Detected
• 96 - Remote Fire Test initiated
• 95 - AUTO initiated
• 94 - LASER activated
• 93 - ‘Home’ initiated
• The elapsed time since the event occurred
• The duration of the event
• The signal strength when the event occurred (if applicable)
• The AGC value when the event occurred (if applicable)