Status LED

The REACH Wireless Sounder Base includes a 360° LED 
indicator which to indicate status conditions. See table 1.

Table 1:   REACH Wireless Device Status & LED 

Indication

Device Status

LED Indication

Tamper Not 

Activated

Tamper 

Activated

Power Up

Blinks green four times

Power Up (dip-switch ON)

Blinks red four times

Entering Wake-Up

Blinks alternatively green/red four 

times

Link Success

Blinks green four times, then 

repeats

Link Failure

Enters wake-up mode and signals 

‘Entering wake-up mode’ following 

this failure

Normal Condition

LED off

LED off

Activation

LED off

Red on

Battery Faults

LED off

Amber blinking 

every 5s

Tamper Fault

LED off

Replaced

Blinks amber two times

Tone & Volume Selection DIP Switch Settings

Device Addressing

Device addressing is handled by the REACH Wireless Loop-
Interface device (RW1700-030APO).

Devices are soft-addressed automatically when pairing with 
the Loop Interface and can be changed manually. Hard-
addressing using Apollo XPERT cards are not supported.

Table 2:  REACH Wireless DIP Switch Functionality

DIP Switch 

Number

DIP Switch Group Function

Notes

1

Tone Selection

Check Tone Table 

(Table 6)

2

3

4

5

6

Volume Selection

Check Volume 

Table (Table 3)

7

8

High/Low Power LED Output

N/A

Table 3:  REACH Wireless Volume Table

Volume

DIP Configuration

High*

11

Medium High

01

Medium Low

10

Low

00

*EN54-3 certified, for Tone Table (Table 6), see appendix

 

Communication 

REACH Wireless Devices use ‘radio-frequency’ wireless 
communication to connect to the Loop-Interface.

The Loop-Interface (RW1700-030APO) translates the wireless 
communication into wired Apollo protocol communication, 
with each device addressable individually by the fire panel. 
See datasheets for the Loop-Interface for more information.

Base Compatibility

This device is compatible with the following detector products 
(see table 4). It can also be used standalone with a blanking 
cap (see table 5).

Table 4:  REACH Wireless Detector Compatibility

Part Number

Product Name

RW1000-400APO

REACH Wireless Heat Detector

RW1000-600APO

REACH Wireless Optical Smoke 

Detector

RW1000-700APO

REACH Wireless Multisensor 

Optical/Heat Detector

Table 5:  REACH Wireless Blanking Cap Compatibility

Part Number

Product Name

RW1300-010

REACH Wireless AV Base Cap - White

RW1300-020

REACH Wireless AV Base Cap - Red

Maintenance and Service 

Maintenance must be performed in accordance with all 
applicable standards. Clean the detector externally using a 
soft damp cloth. For full cleaning and recalibration detectors 
should be returned to Apollo Fire Detectors.  

Batteries

REACH Wireless devices are supplied with two CR123 bat-
teries, battery A and B. The device switches periodically 
between the two batteries on a controlled sequence. For cor-
rect operation of the device, both batteries are required with 
adequate capacity reserves.

When battery A reaches a low power threshold, it will trig-