Commissioning

The installation must conform to BS5839–1 (or applicable local codes).

Transparent Hinged Cover

To provide additional protection against accidental operation, a      

Transparent Hinged Cover, part no 44251-189, is available or 44251-175 for 

multiples of 10. 

A

B

C

Removal

A

B

C

1. Hold

2. Push

LED Indicator

Illuminated red when call point is operated.

Troubleshooting

Before investigating individual units for faults, it is important to 

check that the system wiring is fault free. Earth faults on data loops 

or interface zone wiring may cause communication errors.

 

 

           

 

Problem 

         

Possible Cause

  Control panel reports zone fault          Incorrect zone wiring

 

 

 

 

         Detector Removed

 

 

 

 

         EOL device missing or incorrectly fi tted           

                 

        Control panel reports alarm          MCP not reset

 

 

 

 

         Incorrect EOL device

    MCP does not activate alarm           Incorrect wiring

 

 

 

 

         Incompatible control panel

 

 