background image

2

3

 

 

DIL switch 

 

DIL switch 

 

DIL switch 

 

DIL switch 

 

DIL switch  

  setting 

 setting 

  setting 

 setting 

 setting

 

addr 1234567 addr  1234567 addr  1234567 addr  1234567 addr  1234567

 

 

1000000 11 

1101000 21 

1010100 31 

1111100 41 

1001010

 

 

0100000 12 

0011000 22 

0110100 32 

0000010 42 

0101010

 

 

1100000 13 

1011000 23 

1110100 33 

1000010 43 

1101010

 

 

0010000 14 

0111000 24 

0001100 34 

0100010 44 

0011010

 

 

1010000 15 

1111000 25 

1001100 35 

1100010 45 

1011010

 

 

0110000 16 

0000100 26 

0101100 36 

0010010 46 

0111010

 

 

1110000 17 

1000100 27 

1101100 37 

1010010 47 

1111010

 

 

0001000 18 

0100100 28 

0011100 38 

0110010 48 

0000110

 

 

1001000 19 

1100100 29 

1011100 39 

1110010 49 

1000110

 

10 

0101000 20 

0010100 30 

0111100 40 

0001010 50 

0100110

 

51 1100110   

61 1011110 

71  1110001 

81 1000101 

91 1101101 

 

 

52 

0010110 62 

0111110 72 

0001001 82 

0100101 92 

0011101 

 

 

53 1010110 

  63 1111110 

73  1001001 

83 1100101 

93 1011101 

 

 

54 0110110   

64 0000001 

74  0101001 

84 0010101 

94 0111101 

 

  55 

1110110 65 

1000001 75 

1101001 85 

1010101 95 

1111101 

 

  56 

0001110 66 

0100001 76 

0011001 86 

0110101 96 

0000011 

 

 

57 

1001110 67 

1100001 77 

1011001 87 

1110101 97 

1000011 

 

58 

0101110 68 

0010001 78 

0111001 88 

0001101 98 

0100011 

 

  59 

1101110 69 

1010001 79 

1111001 89 

1001101 99 

1100011 

 

 

60 0011110 

70 0110001 

80  0000101 

90 0101101  100 0010011

 101 

1010011 106 

0101011 111 1111011 116 

0010111 121 

1001111 

 102 

0110011 107 

1101011 112 0000111 117 

1010111 122 

0101111

 103 

1110011 108 

0011011 113 1000111 118 

0110111 123 

1101111

 104 

0001011 109 

1011011 114 0100111 119 

1110111 124 

0011111 

 105 

1001011 110 

0111011 115 1100111 120 

0001111 125 

1011111

   

  

   

  

126 0111111

Group Address Setting

In Group mode the Sounder Control Unit responds to an additional address referred to as the 

“group address”, which is used to activate groups of Sounder Control Units simultaneously. (The 

unit continues to respond to its own individual address and report its status from that address in 

the normal way.) The group address is selected by the four-segment DIL switch which is factory-

set to 0000. A group address may be any spare address within–and only within–the range 112 

to 126 inclusive. The required group address is set by moving one or more of the segments on 

the switch to “1”. The following table shows the settings for the group address switch. 

  DIL 

switch   DIL 

switch

 

addr setting  addr  setting
  1248 

 1248

 112 1111 

121 0110

 113 0111 

122 1010

 114 1011 

123 0010

 115 0011 

124 1100

 116 1101 

125 0100

 117 0101 

126 1000

 118 1001 
 119 0001
 120 1110

Commissioning

It is important that the Sounder Control Unit be fully tested after installation. An XP95 Test Set, 

part no 55000-870, may be used to carry out functional testing of individual units. It can also 

be used to perform data integrity tests of an entire loop. For a full technical specifi cation of 

the Sounder Control Unit, please refer to the Sounder Control Unit PIN Sheet, PP2094. For further 

information on isolators, please refer to PP2090.

Fuse: 1.0A, anti-surge  Local supply: 24V (9—32V )   Sounder zone end-of-line resistor: 10K



 ¹/

3

Watt

Wiring Details

All wiring terminals accept solid or stranded cables up to 2.5mm².

L1 (–ve)

L2 (+ve)

LOOP

SOUNDER 

CONTROL UNIT

Note: Polarity must be observed

N/C

COM

N/O

S

SOUNDER –

FUSE

V

e

x –

V

e

x +

LOCAL POWER SUPPLY

FAULT

INPUT

Sounders 

with

polarising

diodes

NORMALLY

CLOSED

FAULT

CONTACT

FAULT INPUT

NOT USED

(WIRE LINK 

MUST BE 

FITTED)

NORMALLY OPEN

FAULT CONTACT

10K

Ω

EOL

VEXT +

VEXT –

VEXT +

VEXT –

+

+

Current consumption at 28V (no protocol)

 

switch-on surge, max 120ms  4.0mA

 quiescent 

 

1.5mA

 sounders 

operated 

1.7mA

 fault 

3.6mA

LED Indicators

Three LEDs are fi tted to the PCB to indicate functions as follows:

 

  Isolator    

Illuminated yellow when a short circuit on the loop 

 

 

 

causes the integral isolator to operate

 

  Sounders On 

Illuminated red when sounder relay is energised

 

  Fault 

 

Illuminated yellow under any fault condition (except group

 

  address 

confl ict)

Address Setting

The Sounder Control Unit is designed to be polled by the control panel in two ways, individually 

or as part of a group. Two DIL switches are provided for setting the addresses. 

Note: one switch is sealed with a sticky label. This label should not be removed unless the unit is 

to be controlled as part of a group. 

Individual Address Setting

The individual address of the Sounder Control Unit is set using the seven-segment DIL switch. 

Each segment of the switch must be set to “0” or “1”, using a small screwdriver or similar tool. A 

complete list of address settings is shown opposite.

Reviews: