Wiring Details
All wiring terminals will accept solid or stranded cables up to 2.5mm²
Address Setting
The address of the Output Unit is set using the lower seven segments of the DIL switch. Each
segment of the switch must be set to “0” or “1”, using a small screwdriver or similar tool. A
complete list of address settings is shown below.
DIL switch
DIL switch
DIL switch
DIL switch
DIL switch
addr
setting addr setting addr setting addr setting addr set-
ting
1234567
1234567
1234567
1234567
1234567
1
1000000 11
1101000 21
1010100 31
1111100 41
1001010
2
0100000 12
0011000 22
0110100 32
0000010 42
0101010
3
1100000 13
1011000 23
1110100 33
1000010 43
1101010
4
0010000 14
0111000 24
0001100 34
0100010 44
0011010
5
1010000 15
1111000 25
1001100 35
1100010 45
1011010
6
0110000 16
0000100 26
0101100 36
0010010 46
0111010
7
1110000 17
1000100 27
1101100 37
1010010 47
1111010
8
0001000 18
0100100 28
0011100 38
0110010 48
0000110
9
1001000 19
1100100 29
1011100 39
1110010 49
1000110
10
0101000 20
0010100 30
0111100 40
0001010 50
0100110
51 1100110
61 1011110
71 1110001
81 1000101
91 1101101
52
0010110 62
0111110 72
0001001 82
0100101 92
0011101
53 1010110
63 1111110
73 1001001
83 1100101
93 1011101
54 0110110
64 0000001
74 0101001
84 0010101
94 0111101
55
1110110 65
1000001 75
1101001 85
1010101 95
1111101
56
0001110 66
0100001 76
0011001 86
0110101 96
0000011
57
1001110 67
1100001 77
1011001 87
1110101 97
1000011
58
0101110 68
0010001 78
0111001 88
0001101 98
0100011
59
1101110 69
1010001 79
1111001 89
1001101 99
1100011
60 0011110
70 0110001
80 0000101
90 0101101 100 0010011
101
1010011 111
1111011 121 1001111
102
0110011 112
0000111 122 0101111
103
1110011 113
1000111 123 1101111
104
0001011 114
0100111 124 0011111
105
1001011 115
1100111 125 1011111
106
0101011 116
0010111 126 0111111
107 1101011 117 1010111
108 0011011 118 0110111
109 1011011 119 1110111
110 0111011 120 0001111
Commissioning
It is important that the Output Unit be fully tested after installation. An XP95 Test Set, part no
55000-870, may be used to carry out functional testing of individual units. It can also be used to
perform data integrity tests of an entire loop.
Note: If this product has been subjected to excessive shock during transportation, it may be
received with the relay contacts in the ‘set’ position. Reset the relay by subjecting it to one
operating cycle before commissioning the system.
LED Indicators
Isolator
Illuminated yellow when a short circuit on the loop causes the
integral isolator to operate
Relay On
Illuminated red when relay is energised
The use of the red LED can be disabled by setting the ‘LED ENABLE’ segment of the DIL switch
to ‘0’.
Current consumption at 28V (no protocol)
LED
Enabled
switch-on surge 160ms
4mA
quiescent
500
μ
A
relay
operated
1.8mA
relay operated (LED disabled)
600
μ
A
For a full technical speci
fi
cation of the Output Unit, please refer to the Output Unit PIN Sheet,
PP2093. For further information on isolators, please refer to PP2090.
N/O
N/C
COM
N/C COM N/O
-
+
+
-
– +
– +
XP95 LOOP
RELAY CONTACT 1
1A at 30V MAX 30V AC or DC
L1
L2
L1
L2
L1 and L2 are polarity sensitive
RELAY
CONTACT 2
1A at 30V
MAX 30V AC
or DC