Wiring Details

All wiring terminals will accept solid or stranded cables up to 2.5mm²

Address Setting

The address of the Output Unit is set using the lower seven segments of the DIL switch. Each 

segment of the switch must be set to “0” or “1”, using a small screwdriver or similar tool. A 

complete list of address settings is shown below. 

 

    DIL switch 

 

DIL switch 

 

DIL switch 

 

DIL switch     

DIL switch  

addr  

setting addr setting  addr setting addr setting addr  set-

ting
  1234567 

 1234567 

  1234567 

 1234567 

 1234567

 

 

1000000 11 

1101000 21 

1010100 31 

1111100 41 

1001010

 

 

0100000 12 

0011000 22 

0110100 32 

0000010 42 

0101010

 

 

1100000 13 

1011000 23 

1110100 33 

1000010 43 

1101010

 

 

0010000 14 

0111000 24 

0001100 34 

0100010 44 

0011010

 

 

1010000 15 

1111000 25 

1001100 35 

1100010 45 

1011010

 

 

0110000 16 

0000100 26 

0101100 36 

0010010 46 

0111010

 

 

1110000 17 

1000100 27 

1101100 37 

1010010 47 

1111010

 

 

0001000 18 

0100100 28 

0011100 38 

0110010 48 

0000110

 

 

1001000 19 

1100100 29 

1011100 39 

1110010 49 

1000110

 

10 

0101000 20 

0010100 30 

0111100 40 

0001010 50 

0100110

 

51 1100110   

61 1011110 

71  1110001 

81 1000101 

91 1101101 

 

 

52 

0010110 62 

0111110 72 

0001001 82 

0100101 92 

0011101 

 

 

53 1010110 

  63 1111110 

73  1001001 

83 1100101 

93 1011101 

 

54 0110110   

64 0000001 

74  0101001 

84 0010101 

94 0111101 

  55 

1110110 65 

1000001 75 

1101001 85 

1010101 95 

1111101 

  56 

0001110 66 

0100001 76 

0011001 86 

0110101 96 

0000011 

 

57 

1001110 67 

1100001 77 

1011001 87 

1110101 97 

1000011 

 

58 

0101110 68 

0010001 78 

0111001 88 

0001101 98 

0100011 

  59 

1101110 69 

1010001 79 

1111001 89 

1001101 99 

1100011 

 

60 0011110 

70 0110001 

80  0000101 

90 0101101  100 0010011 

 

 101 

1010011 111 

1111011 121 1001111

 102 

0110011 112 

0000111 122 0101111

 103 

1110011 113 

1000111 123 1101111

 104 

0001011 114 

0100111 124 0011111

 105 

1001011 115 

1100111 125 1011111

 106 

0101011 116 

0010111 126 0111111

 107 1101011  117 1010111
 108 0011011  118 0110111
 109 1011011  119 1110111
 110 0111011  120 0001111

Commissioning

It is important that the Output Unit be fully tested after installation. An XP95 Test Set, part no 

55000-870, may be used to carry out functional testing of individual units. It can also be used to 

perform data integrity tests of an entire loop.

Note: If this product has been subjected to excessive shock during transportation, it may be 

received with the relay contacts in the ‘set’ position. Reset the relay by subjecting it to one 

operating cycle before commissioning the system.

LED Indicators

 

  Isolator    

Illuminated yellow when a short circuit on the loop causes the 

  

  

integral isolator to operate

   Relay On  

Illuminated red when relay is energised

The use of the red LED can be disabled by setting the ‘LED ENABLE’ segment of the DIL switch 

to ‘0’.

Current consumption at 28V (no protocol)

 LED 

Enabled

 

switch-on surge 160ms 

4mA

 quiescent 

 

500

μ

A

 relay 

operated 

1.8mA

 

relay operated (LED disabled) 

600

μ

A

For a full technical speci

fi

 cation of the Output Unit, please refer to the Output Unit PIN Sheet, 

PP2093. For further information on isolators, please refer to PP2090. 

N/O

N/C

COM

N/C COM N/O

-

+
+

-

 –  +

 –  +

XP95 LOOP

RELAY CONTACT 1
1A at 30V MAX 30V AC or DC 

L1

L2

L1

L2

L1 and L2 are polarity sensitive

RELAY 
CONTACT 2
1A at 30V
MAX 30V AC 
or DC