Output Configuration Options
The output type can be set to work in one of two basic modes,
variable
or
threshold
.
Variable Mode Options
Load Power
Should be set to the size of the load connected to the output. This value does not
limit the maximum power from the output but tells the controller what size of
load to expect. This value should match the maximum load size for optimum
performance.
Temp Control
T/Stat
The output will use the mechanical thermostat built into the
heater to control temperature. Note: for this option to be
used the load must be directly connected to the Apollo GEM
output and be >100W
Sensor
The output will use the optional temperature sensor to
control temperature.
None
No temperature control is used for this output. Use this
setting if the output is connected to a contactor or a non-
heating appliance.
Threshold Mode Options
Load Power
Set to the maximum load power and is the export power threshold used to turn
on the load.
Temp Control
As for variable mode above.
ON Del
This is the delay time in seconds that the export power must be above the
threshold before the output is turned on. Delays of between 0-99 seconds can be
programmed.
OFF Del
This is the delay time in seconds that the export power must be below the
threshold before the output is turned off. Delays of between 0-99 seconds can be
programmed.
Min ON Time
This is the delay time in minutes that the output will remain on once turned on
regardless of whether the export power remains above the threshold. This setting
is used for appliances which once turned on must be allowed to finish a cycle etc.
GEM-D Installation Manual
Apollo GEM
Installation & User Manual
Apollo GEM
Installation Manual