I) Input/Output: 1P2W+G 220V or 230V or 240V 

 

 

 

 

II) Input: 1P2W+G 220V or 230V or 240V, Output: 1P3W+G 110/220V or 115/230V 

or 120/240V, With Isolation Transformer 

Connection for dual Output: 110/220V or 115/230V or 120/240V 

 

 

 

  Connection for single output 110V or 115V or 120V 

 

 

Note:  you  must  make  sure  that  the  input  and  output  wires  and  the  input  and  output 

terminals are connected tightly. 

 

Summary of Contents for PlusIII-10KLRB

Page 1: ...USER MANUAL PlusIII 6KLRB PlusIII 10KLRB ...

Page 2: ...ld overload the UPS system e g laser printers to the UPS outlet socket Place cables in such a way that no one can step on or trip overthem Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Installation for Plus III 6KLRB Plus III 10KLRB Warning This is a product for restricted sales distribution to in...

Page 3: ...ts inside the UPS system are still connected to the battery and are still electrically live and dangerous Before carrying out any kind of servicing and or maintenance disconnect the batteries and verify that no current is presentand no hazardous voltage exist in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the requir...

Page 4: ...fuse of the same type and of the same amperage in order to avoid fire hazards Do not dismantle the UPS system 2 Description of commonly used notations Some or all of the following Notations may be used in this manual and may appear in your application process Therefore all users should be familiar with them and understand their explanations ...

Page 5: ... while input rated voltage is 230VAC OUTPUT Model No Plus III 6KLRB PlusIII 10KLRB Power rating 6kVA 5 4k W 10kVA 9k W Voltage 208 220 230 240 1 士 1 VAC Frequency 50 60 1 0 05 Hz Battery mode Wave form Sinusoidal Load type PF 0 5 1 lagging THDV 2 full linear load 5 full non linear load Overload In Line mode 10 min 105 125 1 min 125 150 10 s 150 100 ms 170 In Battery mode 2 min 105 125 30 s 125 150...

Page 6: ... the basis of 1000m 3 2 Typical Backup Time Typical values at 25 C in minutes Model No 100 Load Plus III 6KLRB 5 PlusIII 10KLRB 4 3 3 Unpacking and Inspection 1 Unpack the packaging and check the package contents The shipping package contains A UPS A user manual A communication cable A battery cable for Plus III 6KLRB PlusIII 10KLRB only 2 Inspect the appearance of the UPS to see if there is any d...

Page 7: ...rofessional personnel For safety please cut off the mains power switch before installation The battery breaker also needs to be cut off if it is a long backup time model 1 Open the terminal block cover located on the rear panel of the UPS please refer to the appearance diagram 2 For Plus III 6KLRB UPS it is recommended to select the UL1015 10AWG 6mm2 wire or other insulated wire which complies wit...

Page 8: ...1P3W G 110 220V or 115 230V or 120 240V With Isolation Transformer Connection for dual Output 110 220V or 115 230V or 120 240V Connection for single output 110V or 115V or 120V Note you must make sure that the input and output wires and the input and output terminals are connected tightly ...

Page 9: ...he utility power supply 10 Suggest charging the batteries for 8 hours before use After connection turn the inputbreaker in the ON position the UPS will charge the batteries automatically You can also use the UPS immediately without charging the batteries first but the backup time may be less than the standard value 11 If it is necessary to connect the inductance load such as a monitor or a laser p...

Page 10: ...ed to the 10KE in parallel with blue and brown wires the negative pole of the battery is connected to the 10KE in parallel with black and white wires the greenand yellow ribbon wire is connected to the ground of the battery cabinet 3 To complete the connection by plugging the connector of the external battery cable into the external battery socket of the UPS Do not attempt to connect any loads to ...

Page 11: ... 5 4 5 to clear EPO status then UPS would stop alarm and recover to Bypass model And UPS needs be turned on by manual operation The polarity of connector could be inversed by setting in LCD menu in the chapter of 5 4 7 Contact your local distributor for further information before modifying the settings 4 Rear View ...

Page 12: ...ackground to amber Besides the LCD the UPS has four colorized LEDs to provide more convenient information Fig 5 1 Control Panel Table 5 1 Control Button Functions The Button Function Illustration Power on When the unit is no power and has connected with battery press this button for 100ms 1s topower on Turn on When the unit is powered on and is in Bypass mode press this button for 1s to turn on Tu...

Page 13: ...nition UPS state Normal LED Green Battery LED Yellow Bypass LED Yellow Fault LED Red Bypass mode with no output Bypass mode with output Turning on Line mode Battery mode HE mode Battery test mode Fault mode Warning mode ...

Page 14: ...fication and settings through the front panel display During powering on the LCD would display the Welcome logo for several seconds and then enter to the default page which shows the UPS status summary The display automatically returns to the default UPS status summary screen when no button has been pressed for 15 minutes On the UPS status summary screen it provides the following information Statu...

Page 15: ...isplayed corresponding to current operating mode or status 5 2 1 Line mode The example of LCD display in Line mode is shown in the following diagram The symbol of operating in Line mode Fig 5 3 Line mode Input Output 220 V 273 0 V 220 V 60 Hz 60 Hz 100 5400 W ...

Page 16: ...nce every 4 seconds 5 2 3 Bypass with output The LCD display in bypass mode with output is shown in the following diagram The UPS does not have the backup function when it is in bypass mode The power used by the load is supplied from the mains power via internal filter The UPS will beep once every 2 minutes in bypass mode Fig 5 5 Bypass mode with output ...

Page 17: ...s power via internal filter while the mains power is in normal range so the high efficiency could be gained in the HE mode Once the mains power is loss or abnormal the UPS would transfer to Line mode or Battery mode and the load is supplied continuously The symbol of operating in ECO mode Fig 5 7 HE mode 1 The function could be enabled through the LCD setting or the software Winpower etc 2 It is a...

Page 18: ...e function could be enabled through the LCD setting or the software Winpower etc 2 The load should be derated to 60 in converter mode 5 2 7 Warning When the warning occurs it illustrates that there are some abnormal problems during the operation of UPS Normally the problems are not fataland the UPS continues working but they should be paid attention to or the UPS may fail The detailed warning tabl...

Page 19: ...bypass and keep alarming The backlight of LCD would also turn to red The detailed fault table is shown in chapter of 7 5 2 9 Other status When the UPS is overload the alarm will beep twice every second Some unnecessary loads should be get rid of one by one to decrease the loadsconnected to the UPS less than 90 of its nominal power capacity ...

Page 20: ...y test LEDs would be lighted circularly and the symbol of battery test would be shown on the display And if the battery status detected is battery disconnected the symbol of battery failure would be shown and UPS would alarm ...

Page 21: ...ton continuously for more than 1 second the buzzer will beep for 1s UPS starts to turn on 4 A few seconds later the UPS turns into Line mode If the mainspower is abnormal the UPS will transfer to Battery mode without output interruption of the UPS 5 3 2 Turning on UPS without mains 1 Check allthe connection is correct Check the breaker of external battery pack is in ON position 2 By pressing butto...

Page 22: ...he output at once 2 A few seconds later LCD shuts down and no voltage is available fromthe UPS output 5 4 LCD Operation Except the default UPS status summary screen the user could get moreuseful information about UPS current status detailed various measurements old eventswhich ever occurred UPS own identification and could change the settings to fit the user own requirements optimize the function ...

Page 23: ...essing on the menu of UPS status the display would enter the next UPS status menu tree The content of UPS status menu tree is same as the default UPS status summary menu By pressing 1s the display would return the last main menu tree ...

Page 24: ...ve been recorded here The information includes the illustration the event code and the operating time of UPS when the event happened By press or 1s all the event could be displayed one by one The max number of record is 50 when the number is larger than 50 the oldest one would be changed to the newest information By pressing 1s the display would return the last main menu tree ...

Page 25: ...Fig 5 16 Event menu tree ...

Page 26: ...ay would enterthe next measurement menu tree A lot of detailed useful information could be checked here Ex the output voltage and frequency the output current the load capacity the input voltage and frequency etc By pressing 1s the display would return the last main menu tree ...

Page 27: ...m to do the battery test at the same time 4 Clear EPO status once EPO status is enabled the UPS output would be cut off To recover to normal status first EPO connector should be closed and enter this menu to clear EPO status then UPS would stop alarm and recover to Bypass model And UPS needs be turned on by manual operation 5 Reset fault status when fault occurs UPS would keep in Fault mode and al...

Page 28: ......

Page 29: ...ve status couldn t be cleared 5 4 6 The identification menu By press on the menu of Identification the display would enter the next identification menu tree The identification information includes UPS serial number firmware serial number model type would be shown here By press 1s the display would return the last main menu tree ...

Page 30: ......

Page 31: ...e option set by user may result in potential failures or protecting function loss even directly damage the load battery or UPS The most of settings could only be done while UPS is in Bypass mode By press on the menu of Identification the display would enter the next setting menu tree if User password is disabled If User password is enabled the user should enter the password by press and then enter...

Page 32: ...ord is AAAA when enabled Read the chapter of 6 1 and 6 2 before using high efficiency or converter function Ensure the real battery quantity is same as the setting or the batteries would be damagedpermanently ...

Page 33: ...Example set rated output voltage value ...

Page 34: ... in HEmode It is also called economy mode Once the mainspoweris loss or abnormal the UPS would transfer to Line mode or Battery mode and the load is supplied continuously The great virtue is overall high efficiency 0 96 of UPS to save powerfor user But the disadvantage is 1 the load can not be protected as well as in Line mode for the load is directly supplied from the mains 2 the transfer time of...

Page 35: ... fault UPS number that the system can handle simultaneously When the X islarger the reliability of the power systemis higher For occasions where reliability is highly depended on N X is the optimal mode As long as the UPS is equipped with parallel cables up to 4 UPSs can be connected in parallel to realize output power sharing and power redundancy 6 3 2 Parallel installationand operation How to in...

Page 36: ...ters The difference between the wires of input and output of the UPSs is required to be less than 20 10 Do not switch on the output breakerof each UPS switchon the input breaker ofthe each UPS the UPS should work in bypass with output observe their displayto check if there are any warning or fault information measure the outputvoltage of each UPS separately tocheck if the voltage difference betwee...

Page 37: ...lly set the own maintenance switch of each UPS from UPS to BPS 4 Set the main maintenance switch or static switch from UPS to BPS switch off the main output breaker and the main input breaker the UPSs would shut down 5 Ensure the UPSs shut down totally add the new UPS and reinstall the new UPS parallel system by following step 1 to 9 of last chapter install a new parallel UPS system 6 Switch on th...

Page 38: ...stem 5 If the removed UPS or the remained UPS will be used in a stand alone mode then JP1 and JP2 on the terminal block should be connected with a short connection wire 6 Switch on the main input breaker and the main output breaker and set the main maintenance switch or static switch from BPS to UPS then set the UPS own maintenance switch from BPS to UPS and screw the maintenance cover plate back ...

Page 39: ...es not operate correctly first check the operating informationon the LCD display Please attempt to solve the problem using the table below If the problem still persists consult your dealer 7 1 Trouble Shooting According To Warning Indication ...

Page 40: ......

Page 41: ...7 2Trouble Shooting According To Fault Indication ...

Page 42: ...er serial number 2 Date on which the problem occurred 3 LCD LEDdisplay information Buzzer alarm status 4 Mainspower condition load type and capacity environment temperature ventilation condition 5 The information battery capacity quantity of external battery pack if theUPS is S model 6 Other information for complete description of the problem ...

Page 43: ...arging and over discharging The UPS should be charged once every 4 to 6 months if it has not been used for a long time In the regions of hot climates the battery should be charged and discharged every 2 months The standard charging time should beat least 12 hours Under normal conditions the battery life lasts 3 to 5 years In case if the battery is found not in good condition earlier replacement sh...

Page 44: ...S has independent dry contactinterface Please contact your local distributor for details The following is the pin assignment and description of DB 9 connector 9 3 3RS 232 Interface optional The RS 232 port is available for UPS monitoring control and firmware updates The cable pins for the RS 232 communication port are identified in the following illustration ...

Page 45: ...or further information 10 Software Free Software Download WinPower WinPower is a UPS monitoring software which provides user friendly interface to monitor and control UPS This unique software provides safely auto shutdown for multi computer systems while power failure With this software users can monitor and control any UPSon the same LAN which communicated with local computer through RS232 or USB...

Page 46: ...d follow the instruction described on the website to download the software 3 When downloading all required files from the internet enter the serial No 511C1 01220 0100 478DF2Ato install the software When thecomputer restarts the WinPower software will appear as a green plug icon located in the system tray near the clock ...