IMPORTANT

: See your RST-5003 User Manual for complete Modbus programming 

instructions and tropubleshooting tips..

9

General Care

Your RST-5003 is very low maintenance and will need little care as long as it was installed correctly.

However, in general, you should:

• 

Avoid applications for which the control module was not designed, such as extreme 

temperatures, contact with incompatible corrosive chemicals and fumes, or other damaging 

environments.

10

Repair Information

If your RST-5003 control module needs repair, contact us via email, phone, or on-line chat on our 

website. We will issue you an RMA number with instructions.

• 

Phone: 888-525-7300

• 

Email: [email protected]

• 

Online chat at www.apgsensors.com

11

Removal Instructions

• 

Disconnect power source to control module.

• 

Disconnect sensors and network cable to control module.

• 

Remove the control module and store it in a dry place, at a temperature between -40° F and 

180° F.

Network / Internet Connection

Computer

on 

Local 

Network

Computer 

on

Internet

MNU Ultrasonic Sensors

MP Magnetostrictive Float Level Sensors 

4-20 mA Input

(2) Solid State Relays

Modbus

Input

Connection

to

Internet

Server Hosting

Website and 

Logged Data

4-20 mA Type Level Sensor

RST-5003

7

Modbus System Wiring Diagrams

 

NOTE

: Refer to each sensor’s user manual for sensor specific wiring instructions. User 

Manuals for all APG sensors and equipment are available at 

www.apgsensors.com

.

2

4

V

B

G

N

D

A

(Ethernet Port)

270 Ω

terminating

resistor at

last sensor

Sensor 3

V+

A

B

GND

Trunk Line

Sensor 1

V+

A

B

GND

Sensor 2

V+

A

B

GND

Use shielded cable 

Sensor Line Drops

Equivalent 270 Ω

terminating resistor

internal to RST-5003

Note: Terminating resistor size recommended

based on input resistance of RST-5003. Length

of cable and overall impedence of network may

necessitate a different size resistor.

Modbus Daisy Chain Wiring

Modbus System & Network Diagram

Figure 8.1

Figure 8.2

8

Accessing the RST-5003’s Embedded Webpage

Each Modbus sensor attached to your RST-5003 must be configured via the RST-5003’s embedded 

webpage before the next sensor can be added. The easiest way to access access the embedded 

webpage is to type rst_xxx into a web browser on a computer connected to the same local network 

as the RST-5003. xxx represents the numeric portion of the RST-5003’s serial number. See Figures 

8.1 and 8.2.