Coil Address
Read-Write
Function
DNP Data Class
DNP3 Address
From 4001 to 5999
Write
Serial Input Signal
10
0-1998
From 40001 to 40002
Read
Interface Module Data
30
0-1
From 40003 to 40222
Read
Logic Card Data
30
2-221
Coil Address
Function
4001
Acknowledge All
4002
Reset All
4003
Mute All
4004
Test All
4101 to 4210
Single Point Acknowledge
4301 to 4410
Single Point Reset
4501 to 4610
Single Point Mute
4701 to 4810
Single Point Test
4901 to 4904, 4911 to 4914, … , 5991 to 5994
Single Inputg Signal
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
40001
Interface
module data
First-
Up
Com.
Alarm
Crtcl.
Horn
Alarm
Horn
-
-
-
-
-
-
-
-
-
-
-
-
40002
Interface
module data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
40003
Logic card
data
Alrm4
Alrm3
Alrm2
Alrm1
In 4
In 3
In 2
In 1
Ack4
Ack3
Ack2
Ack1
Lmp4
Lmp3
Lmp2
Lmp1
40004
Logic card
data
Flashing
Type 4
(2 bits)
Flashing
Type 3
(2 bits)
Flashing
Type 2
(2 bits)
Flashing
Type 1
(2 bits)
First
-Up
Com.
Alrm
Horn
Crtcl.
Horn
Alarm
Horn
In 4
Crtcl
Set
In 3
Crtcl
Set
In 2
Crtcl
Set
In 1
Crtcl
Set
Interface Module (Common) Registers (40001 and 40002):
Logic Cards’ Registers - 40003 and 40004 (will be repeated up to 40221 and 40222:
Modbus and DNP3 Registers’ List and Spec.:
Communication: RS485, 19200, No Parity, 2 stop bits
Annunciators address (node address): 1 to 7
Modbus address same as Annunciator address
AIS750 Series Annunciators
(24)