APAR AR553 User Instruction Download Page 9

9

 

Table 9.2. Configuration parameters for the RS485 version

 

Parameter

 

Range of variability of the parameter and description 

Default 

settings

 

0: 

cALo 

 calibration of the zero 

point for temperature 

[°C]

 

-20.0

 ÷ 

20.0 

zero point offset 

0.0 

[°C]

 

1: 

cALg 

 calibration of the 

inclination for temperature [

%]

 

85.0

 ÷ 

115.0 

sensitivity (gain) 

100.0 

[%]

 

2: 

Addr 

MODBUS address 

1

 ÷ 

247 

MODBUS address of the device 

3: 

br

  transmission speed 

0.6

 ÷ 

115.2 

transmission speed [kb/s], for the RS485 and the AR956 
programmer 

2.4 

 
 

10. MESSAGES AND ERROR SIGNALING

 

a) measurement errors: 

Code

 

Possible causes of error 

^^^^ 

the measurement range of the sensor is exceeded from the top

 

____ 

the measurement range of the sensor is exceeded from the bottom 

---- 

no communication with the sensor (the sensor is defective or the electrical connections are broken) 

b) other messages: 

Code

 

Description of message 

ConF

 

the parameter configuration menu was accessed 

 
 

11. CONNECTING THE CONTROLLER TO A COMPUTER AND AVAILABLE SOFTWARE

 

It may be useful (or necessary) to connect the transducer to a computer in order to configure parameters, which 
also enables copying the setting to other transducers of the same type. 
As a standard, the transducers are equipped with a 

PR

 port which enables connection to a computer using an 

AR956 programmer using the MODBUS-RTU communication protocol and the following transmission parameters:  
speed = 2,400 bit/s, MODBUS address = 1. 
The following application is available (on a CD supplied with the AR956 programmer or to be downloaded from 
the Internet at 

www.apar.pl

“Download”

 section, for operating systems Windows Vista/7/8/10): 

Name

 

Software description 

ARsoft-CFG 

(free)

 

- display of current measurement data from the connected device 
- setting configuration parameters, such as the measurement range of the output,  
   the communication options, etc.

 

 

- creation on the disk of a "cfg" file with the current configuration of the parameters for  
   future use (copying of configuration) 
- the software requires communication with the device via the 

PR

 port (AR956 or AR955)

 

A detailed description of the aforementioned application can be found in the installation folder.  

 
NOTE:  

 

Before a connection is established, make sure that the MODBUS address and the transmission speed in the options 
of the ARsoft software are the same as the settings of the device (this applies to the version with the RS485). 
Moreover, in the options of the ARsoft software, set the number of the COM serial port in use (in the case of the 
AR956/AR955 programmer or the RS485/USB converter, it is the number assigned by the operating system during 
installation of the drivers). 

!

Summary of Contents for AR553

Page 1: ...iego 6 Tel 48 22 101 27 31 22 853 48 56 22 853 49 30 fax 48 22 101 27 33 Internet www apar pl email automatyka apar pl USER INSTRUCTION version version without a display with an LCD display TEMPERATUR...

Page 2: ...SIONSAND INSTALLATION DATA 5 7 DESCRIPTION OF TERMINAL STRIPSAND ELECTRICAL CONNECTIONS 6 8 FUNCTIONS OF THE BUTTONS ON THE CONTROL PANEL 7 9 SETTING OF THE CONFIGURATION PARAMETERS 7 10 MESSAGESAND E...

Page 3: ...t vicinity of and parallel to power and supply cables d it is recommended to twist the signal wires in pairs or to use a finished twisted pair cable e avoid proximity of remotely controlled devices el...

Page 4: ...load capacity Ro Usup 12 22 mA voltage 0 10 V max resolution 9 1 mV load capacity Io 4 5 mA Ro 2 5 k output error basic 0 1 additional 0 01 C of the output range Communication interfaces RS485 and PRG...

Page 5: ...th an LCD carefully take out display from bolt connectors perpendicularly to the front surface terminals to connect power supply cables outputs cables and signal cables become accessible see chapter 7...

Page 6: ...sion with the voltage output Terminals Description 1 voltage output UH 0 10 V for the measured temperature value 2 3 common earth minus for the outputs and the power supply 4 supply input V measuring...

Page 7: ...ted parameter UP and DOWN simultaneously canceling changes to the edited value the blinking stops and return to the previous menu one level above returns to the measurement display mode after hold tim...

Page 8: ...check the configuration of the port and the MODBUS address of the device transmission speed 2 400 bit s address MODBUS 1 make sure that the serial port drivers in the computer have been properly insta...

Page 9: ...a PR port which enables connection to a computer using an AR956 programmer using the MODBUS RTU communication protocol and the following transmission parameters speed 2 400 bit s MODBUS address 1 The...

Page 10: ...form the RS485 network e g RS485 converters USB may have integrated polarizing and terminating resistors in such a case there is no need to use external elements Fig 12 Pictorial diagram of the RS485...

Page 11: ...0001 non existing register address 0x0002 wrong write register value 0x0003 improper function number Example 13 5 Error frame for a non existing read register address 0x01 0x84 0x02 0x0001 0x5130 Tabl...

Page 12: ...12 14 USER S NOTES...

Reviews: