background image

 

 

 

 
 
 

 

 

 

26 

 

June 2012 

Gas Controller 

 

AUTOMATIKPRODUKTER 

 

4.8.1 

Service Mode 

For calibration and service work, the alarms are not transmitted to the alarm relays when the service mode is 
active (ON). The service mode  ON  is reset automatically after 60 minutes or manually in the menu “Service 
Mode”. If the calibration is executed with the service tool CGD05-STL or with the CGD-EasyConf Software, the 
alarm suppression is automatically activated during calibration. 
 

Symbol 

Description 

Default 
Status 

Function 

Off 

Service Mode 

Off 

Off  = Alarms activate the associated alarm relays 
On  = Alarms are not transmitted to the alarm relays 

 

4.8.2 

Software Version 

 

Symbol 

Description 

Default 
Status 

Function 

CG05-
XX 

Software 
Version 

 

XX = Software Version 

 

4.8.3 

MP Address Mode 

Adaptation of the value and parameter display to the connected field bus transmitters. 

This configurable functionality is available from version 9.02. This basic setting has to be done prior to all other 
parameter settings for the sensor addressing is influenced by it. 

 

Symbol 

Description 

Default Status  Function 

98 Addr. 
a 1 MP

 

MP Addr. 
Mode 

98 Addr. a  1 

MP 

98 Adr. à  1 MP = only bus transmitters 
48 Adr. à  2 MP= bus transmitters  + analog transmitters 

 

4.8.4 

Language 

This configurable functionality is available from version 9.02. 

 

Symbol 

Description 

Default Status  Function 

German 

Language 

German 

German 
English 
Dutch 
USA English 
French 
Swedish 

 

4.8.5 

Maintenance Concept 

A control of the maintenance intervals required by law or by the customer is integrated in the CGD-05 system. 

At commissioning or after maintenance the date for next maintenance is entered. When this  date is  reached, 
the failure signal is activated the next morning at 9 o'clock, and the phone no. of the service technician occurs 
in the display instead of the measured values. The text message “Maintenance” and the service phone no. can 
only be reset after having accomplished the maintenance by entering the next maintenance date. 

The service phone no. can be entered individually in the next menu. 
 

Symbol 

Description 

Default 
Status 

Function 

TT.MM.JJ  Maintenance date   

TT.MM.JJ = Input of the date for next maintenance. 

0853.... 

Phone No. 

 

Input of the individual service phone no.  

 

Summary of Contents for CG-05

Page 1: ...AUTOMATIKPRODUKTER Gas Controller CGM CGD PCR CG 05 User s Manual June 2012...

Page 2: ...ng Mode 13 4 5 4 Horn Function 13 4 5 5 External Operation of Alarm Relay 14 4 5 6 Delay Mode of Alarm Relay 14 4 6 Menu MP Parameter 15 4 6 1 Activate Deactivate MP 16 4 6 2 Lock or Unlock MP 16 4 6...

Page 3: ...10 Define the Failure Relay 28 4 8 11 Acknowledge a Relay in Latching Mode by a DI 28 4 8 12 Power On Time 28 4 8 13 Registration of Expansion Modules 28 4 8 14 Error Indicator System Bus 29 4 8 15 An...

Page 4: ...controller The total number of connected transmitters however may not exceed 96 respectively 98 transmitters Up to five free programmable alarm thresholds are available for each transmitter For transm...

Page 5: ...s when alarm one or more alarms are active Permanently on when at least one relay is manually operated LED red Flashes when alarm two or more alarms are active Permanently on when at least one relay i...

Page 6: ...nded for the service technician of the installer to change parameters and set points All settings can be edited with this password Priority 2 fixed value not changeable With code level 2 it is possibl...

Page 7: ...errors See from point 4 1 Display of the status of actual alarms See point 4 2 Display of the relay status Manual operation of the relays Reset function of the relays See from point 4 3 Display of th...

Page 8: ...ed in addition 4 1 1 Acknowledge a Fault Attention According to the directives of the gas measuring technique accumulated errors aren t allowed to be acknowledged automatically Therefore acknowledgmen...

Page 9: ...transmitter not calibrated or defective Solution Check cable to analog transmitter make calibration replace the analog transmitter PE00 Error Internal communication error I O Board to LCD Board Cause...

Page 10: ...OFF Relay manual ON Relay in latching mode 4 3 1 Manual Operation of the Relays The manual operation of the alarm relays is managed in the menu Status Relay or externally via an assigned digital inpu...

Page 11: ...addresses MP01 to MP48 are listed with the index XX 1 for the measured value of the bus transmitter and with XX 2 for the measured value of the analog transmitter MP addressing mode 98 bus transmitte...

Page 12: ...Relay Mode Definition of the relay mode Symbol Description Setting Status Function R 01 Relay No Selection of relay De energized Relay Mode De energized Relay de energized Relay energized Alarm OFF Re...

Page 13: ...two parameters time or digital input is set This function has priority to the latching mode function The following possibilities to reset are available for the alarm relay as horn relay By pressing a...

Page 14: ...to the parameter settings static flashing and energized de energized If external ON and OFF are parameterised on the same relay simultaneously and the both are active at the same time then only the si...

Page 15: ...2 Parameter analog transmitter Activate or deactivate MP See 4 6 1 Lock or unlock MP See 4 6 2 Definition of gas type unit and number of alarms at falling concentrations AF See 4 6 3 Definition measu...

Page 16: ...functionality is available from version 9 02 In the Lock Mode the function of the existing transmitter is put out of service which means there is no alarm or fault message at this measuring point Exis...

Page 17: ...apours Ex infrared Nitrogen trifluoride Percentage Empty ppm LEL ppm ppm ppm Vol ppm ppm ppm ppm ppm Vol ppm ppm ppm ppm ppm ppm F C RH ppm LEL LEL LEL ppm 0 300 0 100 0 50 0 25 0 300 0 25 0 2000 0 10...

Page 18: ...ter with non linear output signal semiconductor 4 6 6 Threshold Hysteresis For each measuring point five alarm thresholds are available for free definition If the gas concentration is higher than the...

Page 19: ...elay Each of the 5 alarms can be assigned to any physically existing alarm relay Unused alarms are not assigned to an alarm relay See also 4 8 16 Relay Multiplication Symbol Description Default Status...

Page 20: ...een tested In this menu the parameters for the long term recording of the USB device are set Main menu See 4 7 1 See 4 7 2 See 4 7 3 See 4 7 4 See 4 7 5 4 7 1 Data Logger Switch On Off Starting the lo...

Page 21: ...etc Time MP1 MP2 MP3 MP4 MP5 MP6 MP7 MP8 MP9 MP10 Or time MP1 1 MP1 2 MP2 1 MP2 2 MP3 1 MP3 2 MP4 1 MP4 2 MP5 1 MP5 2 09_50_02 0 20 20 28 0 0 0 0 09_50_03 0 20 20 28 0 25 29 0 09_50_04 0 20 20 28 0 25...

Page 22: ...itten in the file Time MP Gas CV AV A1 A1R A2 A2R A3 A3R A4 A4R A5 A5R 09_49_47 MP 02 CO 84 40 R01 80 R02 09_49_47 MP 03 CO 194 40 R01 80 R02 100 R03 120 R04 09_50_02 MP 02 CO 20 09_50_02 MP 03 CO 20...

Page 23: ...rce Error date time Error type 10_22_28 MP 79 03_30 10_20 MP79 error 13_48_28 MP 79 03_30 13_46 MP79 error The first column gives the current time the second one the error source The third column indi...

Page 24: ...1 See 4 8 2 See 4 8 3 See 4 8 4 See 4 8 5 See 4 8 5 See 4 8 6 See 4 8 6 See 4 8 7 See 4 8 7 See 4 8 7 See 4 8 8 Software Version CGD 05 XX Next maint Date TT MM JJ System Parameter Service Mode OFF S...

Page 25: ...See 4 8 15 See 4 8 15 See 4 8 16 See 4 8 16 See 4 8 16 Fault Relay 05 Power ON time 30 s Missing Wrong 0 0 Analog Outputs Analog Output 1 Max Calibration AO 1 4 0 4 mA 20 20 0 PE Module 0 Relay active...

Page 26: ...ddressing is influenced by it Symbol Description Default Status Function 98 Addr a 1 MP MP Addr Mode 98 Addr a 1 MP 98 Adr 1 MP only bus transmitters 48 Adr 2 MP bus transmitters analog transmitters 4...

Page 27: ...sec Time for calculating the average value 4 8 7 System Time System Date Input and correction of time and date Selection of time and date format Symbol Description Default Status Function EU Time for...

Page 28: ...arted at the Gas Controller after switching on of the power supply While this time is running out the Gas Controller does not activate alarms The power on status occurs on the first line of the starti...

Page 29: ...A higher error rate mostly comes from incorrect laying of the field bus line 4 8 15 Analog Output The Gas Controller Module as well as the PE 05 Modules 1 to 5 have two analog outputs AO with 4 to 20...

Page 30: ...d in this table Number Description Default Status Function 0 30 IN Relay 0 0 Function off X Relay X should be multiplied information source 0 30 OUT Relay 0 0 Function off X Relay X should switch toge...

Page 31: ...ation techniques and with codes standards and proper safety procedures for control installations and the latest edition of the National Electrical Code ANSI NFPA70 It is also essential to follow stric...

Reviews: