Gas Controller
AUTOMATIKPRODUKTER
4.6.3
Selection Gas Type
Assign gas type of the attached gas transmitter.
Symbol
Description
Setting
Status
Gas type
Unit
1
Measuring
range
1
MP 01
Measuring point
CO
Gas type
CO
CO
Ex
NO
NO
2
NH
3
O
2
CO
2
SO
2
H
2
S
CL
2
ETO
VOC
R4XX
R5XX
R11
R123
R134
R22
TEM
RH
TOX
CH
4
VAP
ExIr
NF3
PTC
Carbon monoxide
Combustible gases
Nitrogen oxide
Nitrogen dioxide
Ammonia
Oxygen
2
Carbon dioxide
3,4
Sulphur dioxide
Hydrogen sulphide
Chlorine
Ethylene oxides
Air quality
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Temperature
Humidity
Toxic gas
Methane
Vapours
Ex infrared
Nitrogen trifluoride
Percentage
Empty
ppm
% LEL
ppm
ppm
ppm
Vol%
ppm
ppm
ppm
ppm
ppm
Vol%
ppm
ppm
ppm
ppm
ppm
ppm
°F/ °C
%RH
ppm
% LEL
% LEL
% LEL
ppm
%
0 – 300
0 – 100
0 – 50
0 – 25
0 – 300
0 – 25
0 – 2000
0 – 100
0 – 200
0 – 100
0 – 20
0 – 100
0 – 300 / 2000
0 – 300
0 – 300
0 – 300
0 – 300 / 2000
0 – 300
XXXX
0 – 100
0 – XXX
0 – 100
0 – 100
0 – 100
0 – 100
XXXX
Symbol
Description
Setting
Status
Function
ppm
Unit
ppm
ppm
%LEL
Vol%
°F
%RH
%
ppk
°C
AF
Direction of the
alarm release
0
Alarm release
0 = at increasing concentration for all alarms
1 = Alarm 1 at falling, Alarm 2- 5 at increasing conc.
2 = Alarm 1 + 2 at falling, Alarm 3-5 at increasing c.
5 = Alarm 1-5 at falling concentration
1
Recommendation without obligation
2
Oxygen measurements: Alarm at falling concentration
3
Carbon dioxide measurements with unit ppk (1 vol% = 10 ppk)
4
Carbon dioxide measurements with unit ppm (1 vol% = 10.000 ppm)