APsystems YC500A/I Installation/User Manual
16
YC500I Installation Procedures
AC connector interface as follows.
Figure 22
Cover any unused connectors with sealing caps to protect the connectors.
Figure 23
WARNING:
Do NOT exceed maximum number of Microinverters
in an AC branch circuit, as displayed on the Technical Data page
(p.23) of this manual.
Step 5 - Install a AC bus protective end cap at the end of AC bus
cable
a. Strip cable jacket.
c. Insert the wires into the cable clamps.
b. Insert the cable end into the seal.
d. Rotate the nut with 3.3N·m until the
latching mechanism meets the base.
Figure 24
Step 6 - Connect APsystems Microinverters to the PV Modules
Figure 25
L1
PE
L2
Nut
Seal
Body
N