-B284SB0*1K**P30  13/16-

LINK ALM IN0

IN1

kPa

[Monitor Display]

IN0 indicator

IN1 indicator

(for 2 points type only)

ALM indicator
LINK indicator

LINK

ALM

LINK

ALM

LINK

ALM

Lit

ON

OFF

Flashing

Flashing

Alternate flashing

Lit

Unlit

Unlit

Lit

Unlit

LINK

ALM

IN

(Orange)

*1  This indication appears when the use of the single unit simplified replacement function fails.

(This operation occurs on the S/W version “B” or later version.)

*2  The duplication is detected when the master unit executes automatic address recognition.
*3  For S/W version “B” or later version: This indication appears when transmission signal and 

power supply are normally connected, and the unit is set to the factory-set address (bit 
address 511). 

  For S/W version “A” or 3-digit lot No.: This indication appears when the master unit is set to 

the factory-set address (bit address 255) during execution of automatic address recognition.

LINK

(Green)

ALM

(Red)

LED

name

Example:

Display status

Description

Model mismatching error*

1

No ALM available

Sensing level drop

Transmission signal received

Slave unit voltage drop

Model mismatching error*

1

Transmission signal error

Model mismatching error*

1

ID duplicated*

2

 or ID unregistered*

3

No transmission signal (disconnection and 

reverse connection of DP and DN lines included)

Lot No. 19ECBNB

S/W version

E-0303

(alternates 

with a 0.5 

sec. 

interval)

[Troubleshooting]

- Single unit 

simplified 

replacement has 

failed.

- The voltage of the 

internal power 

supply to this unit 

(DP-DN) is dropped.

- The AnyWireASLINK 

transmission signal is 

not connected.

- The AnyWireASLINK 

system is not turned 

on.

- The DP-DN line is 

directly connected to the 

24-0V power supply.

- A unit incompatible with 

Ver. 1.1 is connected to 

the AnyWireASLINK 

system for word 

transmission.

Cause

Remedy

IN

LINK

ALM

Unlit

Lit

Flashing

Lit

(alternates 

with a 0.5 

sec. 

interval)

(Lit for 0.5 

sec., unlit 

for 0.5 

sec.)

(Lit for 0.2 

sec., unlit 

for 1.0 sec.)

Flashing

Unlit

Unlit

Unlit

Unlit

Unlit

Unlit

Flashing

Flashing

- Reduce the number of units connected 

to the same AnyWireASLINK system.

- Shorten the transmission line between 

this unit and the master unit.

- Defective connections and the like may have 

caused single unit simplified replacement to fail.

Remove the slave unit after replacement, and 

make connections again.

- When two or more replacement slave units are 

simultaneously connected, the single unit 

simplified replacement function does not work.

- Check if the replacement slave unit is of the 

same type as that of the slave unit before the 

replacement.

- Check if the function version for the 

replacement slave unit is older than that of the 

slave unit before the replacement.

* If the function version of the replacement slave 

unit is older, the single unit simplified 

replacement function does not work.

- Check if the address of the replacement slave 

unit is the same as the address before 

shipment (a bit address of 511).

* If the address of the replacement slave unit is 

not the same as the address before shipment, 

the single unit simplified replacement function 

does not work.

- Check if a disconnection has occurred between 

this unit and the AnyWireASLINK system, and 

repair the connections as required.

- Check the power supply to the 

AnyWireASLINK system, and supply power 

to it.

- Reconnect the power to the 

AnyWireASLINK system.

- A slave unit incompatible with Ver. 1.1 

cannot be used in connection to the 

AnyWireASLINK system for word 

transmission. Check the setting of the 

master unit, and lot No. of the slave unit.

- Check the ASLINKSENSOR status.

- If the following error is indicated on ARW-04, take the following action.

The parameter setting is 

incorrect.

Cause

Display

Remedy

- Should any of the following apply, take the following actions.

- The sensing level 

is low.

- The address of this 

unit remains 

unchanged from the 

factory-set address.

- The address of this 

unit duplicates that 

of another slave unit.

- Set an address correctly.
* You cannot use the unit with the address 

before shipment.

- Set the address again so that it does not 

duplicate another unit’s address.

Detection is 

disabled

- Is the wiring correct?

 

 Re-check the connection of the ASLINKSENSOR transmission 

line.

- Is the power supplied to the AnyWireASLINK system?

 

 Check the power supply.

- Are the parameters set correctly?

 

 Refer to the parameter correspondence table and correct the 

setting.

Setting cannot 

be made with 

the address 

writer

Remedy

Symptom

- Is the wiring correct?

 

 Make sure that the ASLINKSENSOR transmission line is correctly 

connected to the AnyWireASLINK transmission line (DP, DN).

- Are the AnyWireASLINK master unit and slave units supplied with 

appropriate power?

 

 Check the power supply.

- Is the unit used in the rated detection range?

 

 Use it within the rated range.

- Does the address setting exceed the specified number of 

transmission points?

 

 Set the address within the specified number of transmission 

points.

Flashing

Lit

Refer to the parameter correspondence 

table and correct the setting.

Summary of Contents for ASLINKSENSOR

Page 1: ...or serious injury A CAUTION indicates a potentially hazardous situation which if not handled correctly may result in personal injury or property damage If you set equipment parameter 1 alarm bit to en...

Page 2: ...ction version Function version information is given on the lot label The design and contents of the lot label may vary depending on the product model and lot No Indication mode Model Functions Address...

Page 3: ...should be connected to the DP DN terminal farthest from the AnyWireASLINK master unit Connect it correctly so as not to set the wrong polarity Connection with 2 wire non isolated terminals only Syste...

Page 4: ...DC Notes on Combined Use of 4 Wire Isolated Terminal If the total length of the sections where all the DP DN 24V and 0V lines run in parallel in the power supply system is more than 50m connect an AS...

Page 5: ...gth of the section where all the DP DN 24V and 0V lines run in parallel is more than 50m If the total length of the sections A B where all the DP DN 24V and 0V lines run in parallel is more than 50m 4...

Page 6: ...parallel is more than 50m Filter representation in the drawing Local power supply branching If the total length of the section where all the DP DN 24V and 0V lines run in parallel is more than 50m In...

Page 7: ...all be included in the total line length For address setting make sure that the specified number of transmission points is not exceeded If the specified number of transmission points is exceeded detec...

Page 8: ...his unit to the AnyWireASLINK master unit A transmission signal is needed to write or read setting parameters Set parameters with the address writer with a transmission signal connected to the transmi...

Page 9: ...scription 0 to 1000 0 to 100kPa Factory setting 400 40kPa Variable Description 0 to 1000 0 to 1000kPa Factory setting 400 400kPa B284SB 02 1KPP30 B284SB 02 1KNP30 B284SB 02 1KLP30 B284SB 02 1KPLP30 Va...

Page 10: ...mit value The preset response time applies to both ON and OFF operations Input response time selection Equipment parameter 10 This parameter is used to set an alarm judgment monitoring time Alarm dete...

Page 11: ...the master unit A bit corresponding to the status detail area turns ON depending on the contents of the alarm Hysteresis mode Equipment parameter 8 0 Positive logic Equipment parameter 9 0 Window com...

Page 12: ...ime Time Pressure detected by sensor Input 1 point type Input 1 point type Input 1 point type Input 2 points type Hysteresis mode Equipment parameter 8 0 Positive logic Equipment parameter 9 0 Detecti...

Page 13: ...plified replacement function does not work Check if the replacement slave unit is of the same type as that of the slave unit before the replacement Check if the function version for the replacement sl...

Page 14: ...maximum transmission delay time is defined as this time word transmission cycle time Specifications 0 55 C 10 90 RH No condensation 25 75 C 10 90 RH No condensation Based on JIS B 3502 and IEC 61131...

Page 15: ...s B284SB 01 1KPP30 B284SB 02 1KPP30 B284SB 01 1KNP30 B284SB 02 1KNP30 B284SB 01 1KLP30 B284SB 02 1KLP30 1kPa 0 1kPa 0 2kPa 0 1kPa B284SB 01 1KPLP30 B284SB 02 1KPLP30 Mounting panel 1 to 6mm Mounting b...

Page 16: ...17 2018 2019 2020 UMA 14531AJ EN B284SB0 1K P30 16 16 Address Anywire Corporation Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Contact by mail Contact info_e anywire jp Contact by webs...

Reviews: