The branching 

has no limitation.

AnyWireASLINK 

master

Black: 

DN

Red: DP

Black: DN

Red: DP

Black: DN

Black: DN

Red: DP

Red: DP

Black: DN

Red: DP

2 points

2 points

2 points

2 points

2 points

2 points

2 points

2 points

2 points

8 points

8 points

24V DC

*

Black: DN

Red: DP

Black: DN

Red: DP

24V DC

*

*

 

Make sure to use a 24V DC 
stabilized power supply for 
the power supply to be 
connected.

*

 

When complying with the 
UL Standard, make sure to 
use a 24V DC stabilized 
power supply of “NEC 
Class 2 Output.”

4P link connector is 

convenient for 

branching.

Dedicated flat cable 
1.25mm

2

 (4-wire)

The sum of the 

portions of DP, DN is 

the total line length.

If the load current consumption 

is large, a four-wire (isolated) 

terminal can be selected.

This terminal can correspond 

to I/O of the controller with an 

external power supply.

[Installation Location]

- Locations where this product is not directly subject to vibration 

or shock

- Locations where this product is not directly exposed to dust
- Locations where this product is not directly exposed to 

conductors, such as metal chips or spatters

- Locations without condensation
- Locations where the atmosphere is free of corrosive gases, 

flammable gases, and sulfur

- Locations far from high-voltage or high-current cables
- Locations far from servos, inverters, and other cables and 

controllers that generate high-frequency noise

The AnyWireASLINK can employ a two-wire or four-wire terminal selectively depending on the load current.
If the load current is small, using a two-wire (non-isolated) terminal allows for achieving simplified wiring without local power supply.
In the case of prioritizing the sites of concentrated loads and/or the number of connections, hybridization with a four-wire (isolated) 
terminal, which supports local power supply, is also possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving using an external power supply.

[How to Connect AnyWireASLINK]

AnyWireASLINK terminator

One terminator should be connected to the DP, DN terminal farthest 
from the AnyWireASLINK master unit.  
Connect it correctly so as not to set the wrong polarity.

CAUTION

- Refer to Table 1 so that the size and length of the transmission 

line and the allowable supply current lie within an appropriate 
range.

- Connect the same symbols (DP, DN) correctly between the 

AnyWireASLINK master unit and each device.

- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the 

“total line length.”

- Connect the terminator (with polarity) on the transmission line 

terminal farthest from the AnyWireASLINK master unit.

To connect loads (e.g. I/O ports) that are 

controlled with a power supply other than the 

one used for the AnyWireASLINK system, 

always use a 4-wire (isolated) terminal.

Otherwise, malfunction may be caused.

CAUTION

1.25mm

2

0.75mm

2

MAX

 

2A

MAX

 

1.2A

MAX

 

1A

MAX

 

0.6A

MAX

 

0.5A

MAX

 

0.3A

0.5mm

2

MAX

 

0.8A

MAX

 

0.4A

MAX

 

0.2A

Relationship between the size and length of 

    the transmission line and the supply current (Table 1)

Size of 

the transmission 

line (DP, DN)

Supply current on the transmission line (DP, DN)

Total length:

50m or less

Total length: Over 50m,

no longer than 100m

Total length: Over 100m,

no longer than 200m

[System Configuration Example]

Connection example of load 

NPN

2-wire type sensor

Black: DN

Red: DP

White: 0V

Green: 24V

Black: DN

Red: DP

White: 0V

Green: 24V

Black: DN

Red: DP

White: 0V

Green: 24V

Black: DN

Red: DP

White: 0V

Green: 24V

NPN

3-wire type sensor

PNP

2-wire type sensor

PNP

3-wire type sensor

5m max.

BL2LN87SB-02D –

BL2LN87SB-02DS –

BL2LN87SB-02D –

BL2LN87SB-02DS –

3-wire type sensor

2-wire type sensor
Contact

24VL (Brown)

IN

Black

24VL (Brown)

IN

Black

0VL 
(Blue)

0VL 
(Blue)

24VL (Brown)

No connection: 

Be careful not to touch.

IN

Black

24VL (Brown)

IN

Black

0VL (Blue)

No connection: 

Be careful not to touch.

5m max.

5m max.

5m max.

0VL (Blue)

ASLINK filter

General-purpose 

power supply filter

General-purpose power supply filter

Summary of Contents for ASLINKER BL2LN87SB-02D CC20 Series

Page 1: ...operty damage Note on use A separate Address Writer is required to set addresses and other data For more information refer to Various Settings on page 9 NPN input PNP input CAUTION WARNING System powe...

Page 2: ...t Lot No About Word Transmission 3 Some products have no indication of function version Year Numbers Lower two digits of the Christian era Month Alphabet as per the table below 19E means May 2019 Sing...

Page 3: ...ified replacement function see the lot No and the manual for the slave unit When a slave unit of a new function version is replaced with that of an old function version the single unit simplified repl...

Page 4: ...onditions are satisfied Functions Bit transmission ASLINKER 4 wire isolated cable type General purpose sensors General purpose switches Word 1 2 transmission Single unit simplified replacement 3 Remot...

Page 5: ...a four wire isolated terminal in the case of input and load driving using an external power supply How to Connect AnyWireASLINK AnyWireASLINK terminator One terminator should be connected to the DP DN...

Page 6: ...r lines start running in parallel This will improve noise resistance suppress the adverse effects of crosstalk caused by transmitted signals and stabilize signals The above filters must be inserted re...

Page 7: ...total length of the section where all the DP DN 24V and 0V lines run in parallel is more than 50m 24V DC stabilized power supply General purpose power supply filter Use it if necessary 2 wire termina...

Page 8: ...tings are enabled or not Operation during restoration Power supply line disconnection error will be automatically reset by eliminating the cause of disconnection Signal line disconnection error will b...

Page 9: ...reen Input indicator Orange Input indicator Orange Alarm indicator Red Name of Each Part Input line connection wires Pin No Wire color Applicable LP connector LP4 WW 10P Example of fitting the LP conn...

Page 10: ...ction may be caused depending on the sensor to be connected If that happens change the setting as follows Example 1 Signal line disconnection occurs all the time Set to Monitoring enabled for power su...

Page 11: ...n 3 subsequent to corresponding input signal address setting Example When this unit is set to address 4 Variable Address Description CH0 input CH1 input Bit input information area of master unit CH1...

Page 12: ...voltage drop When ALM bit is normal ON mode When this unit is disconnected from the trunk line of the AnyWireASLINK system at occurrence of DP DN disconnection input signals and ALM bits are all turne...

Page 13: ...ng equipment parameter 12 is manual restoration After execution of the short circuit notification cancel command set this parameter to OFF Otherwise operation of the short circuit notification cancel...

Page 14: ...ion Bit input information area Number of bit input points 2 n 1 Number of bit input points 2 n Example When the number of bit transmission points for the master unit is input 64 points output 64 point...

Page 15: ...rmally connected and the unit is set to the factory set address For S W version A or 3 digit lot No This condition is detected when the master unit executes automatic address recognition LINK Green AL...

Page 16: ...djust the power supply voltage of an external power source connected to the slave unit I O line so that the power supply voltage does not exceed the rated voltage range 21 6V to 27 6V Make sure that w...

Page 17: ...t ON voltage OFF voltage Allowable current at 24VL 24V DC 3 5mA 2 2mA or more 1mA or less 16V or more 24VL IN 8V or less 24VL IN 50mA max 24VL 0VL per point Internal circuit 4 wire isolated NPN input...

Page 18: ...ear short circuit status after short circuit is detected Notification by differentiating disconnected CH When ALM bit is normal OFF Notification by differentiating disconnected CH When ALM bit is norm...

Page 19: ...ransmission line disconnection transmission line short circuit transmission power supply drop and duplicated unregistered ID Transmission specifications 1 Do not use or store AnyWireASLINK devices in...

Page 20: ...8 2019 2020 UMA 16324AK EN BL2LN87SB02D CC20 20 20 Anywire Corporation Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Contact by mail Contact info_e anywire jp Contact by website http ww...

Reviews: